Reading the Status Display
[0120.] Indicates Phase A is drawing 120 amps.
[0121] Indicates Phase B is drawing 121 amps.
NOTE: Decimal points are not present in the
readouts for Phases B and C.
[0120] Indicates Phase C is drawing 120 amps.
[G002] Indicates that there are 2 amps of current flowing
to ground in the motor leads or motor.
[H083] Indicates the motor has 83% of its thermal capacity
remaining (H = Heat).
[0060] Indicates there is 60 minutes remaining on the
Process Timer. If flashing, the timer is active.
[13.30] Indicates the time base of the Time Clock
Controller is 1:30 PM (24hr time). If flashing, the
time clock is active and pending the next event.
[0120.] Loop back to Phase A current indication
5.3
There are three modes of display: the Status Display Mode, the
Program Mode, and the Fault Mode.
5.3.1
The Status Display Mode displays seven "screens" of information. Motor
Currents (3 phases), Remaining Thermal Capacity, Ground Current,
Remaining Time on the Process Timer, and Time Base of the Time
Clock Controller. This is also the entry screen for going into the Program
Mode.
Status mode:
[0000.] The initial display on power up is four digits and the decimal.
This indicates the motor current for Phase A of the motor.
[0000] Scroll UP to display four digits only (no decimal). This indicates
the motor current for Phase B. While viewing Phase B, press the UP
arrow again to view Phase C current.
[G000] Scroll UP to display the "G". This indicates that this value is the
current flowing to ground on the motor leads.
[H000] Scroll UP to display the "H". This indicates that this value is the
remaining thermal capacity percentage of the motor (i.e. H070 = 70%
remaining thermal capacity)
[0000] Scroll UP again to display the Process Batch Timer (described in
Section 5.6.7). If this entire screen is flashing, the Timer is active.
[00.00] Scroll UP to display two pairs of digits separated by a point: This
indicates the time base of the Time Clock Controller (described in
section 5.6.7). If the display shows [00.00], the TCC is not enabled. This
follows the time settings in F075 – F080.
Press the UP arrow
Press the UP arrow
Press the UP arrow
Press the UP arrow
Press the UP arrow
Press the UP arrow
Press the UP arrow
Digital Solid State Soft Starters 18 – 1250A

Display Modes

Status Display Mode (Default Display)
Press
Key...
24
Display
Means...
Shows...
Phase A
0120.
Current
Phase B
0121
Current
Phase C
0120
Current
Ground Fault
G 002
Current
Remaining
H083
Thermal Capacity
Process Timer
0060
Remaining Time
Time Clock
13. . 30
Time Base
Loop Back to
0120.
Phase A Current
Figure 5.3.1: Reading the Status Display