7. Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case
of a malfunction.
FAULTS
The circulator is
noisy
Loud noises of
water circulation
Circulator is not
running although
the electrical
power supply is
switched on
Building does not
get warm.
8. Unlocking Procedure: A red light in the LED indicates the circulator is locked or sticking. Disconnect and connect power supply
to start the automatic release process. The circulator makes 100 attempts to restart (process lasts approximately 15 minutes).
Every restart is signalled by a short white flash of LED light. If the locking is not removed through the automatic release process
after 100 attempts to restart the circulator, it goes into standby and the LED remains red. In this case follow the manual procedure
described in the next steps: during any attempt, the red LED light keeps blinking; after that the circulator tries again to start. If
the locking is not removed through the automatic release process (the warning light returns to be red), perform the manual steps
described below.
1. Disconnect power supply - the warning light switches off
2. Close both isolating valves and allow cooling. If there are no shut-off devices, drain the system so that the fluid level is
beneath that of the circulator
3. Loosen 4 motor bolts. Remove motor from casing. Carefully pull the rotor/impeller from the motor
4. Remove impurities and deposits from the impeller and casing
5. Reinsert the rotor/impeller into the motor
6. Connect power supply. Check for impeller rotation
7. If the circulator still doesn't run it will need to be replaced
6
CONTROL
CAUSES
PANEL
Suction pressure is
LED on
insufficient - cavitation
Presence of foreign bodies
LED on
in the impeller
Flashing white
Air in the system. Pump
may be air-bound.
LED
Lack of power supply
Circuit breaker might be
tripped
The circulator is defective
LED off
Overheating
LED red
The rotor is blocked
Insufficient supply voltage
LED on
System may be air-bound
REMEDIES
Increase the system suction
pressure within the
permissible range.
Disassemble the motor and
clean the impeller.
Vent the system. Repeat
fill and purge steps.
Verify voltage value of the
electric plant.
Verify the connection of the
motor.
Check circuit breaker at panel
and reset if necessary
Replace the pump.
Let the pump cool down for
some minutes. Then try to re-
start it. Verify that the water
and ambient temperature are
within the indicated
temperature ranges.
Disassemble the motor and
clean the impeller. See
unlocking procedure below.
Verify that the power supply
matches the data on the name
plate.
Vent system.
Repeat fill and purge steps.