STULZ UltraSonic Humidifier Technical Manual System for duct humidification ENS ENS 14 A ENS 18 A Original instructions - Read carefully before use - Index 1000720 EN - Keep for later reference - Issue 08.2016...
Page 2
A B O U T S T U L Z Since it was founded in 1947, the STULZ company has evolved into one of the world’s leading system suppliers of air-conditioning technology. With the manufacture of precision air-conditioning units and chillers, the sale of...
Page 3
STULZ UltraSonic Humidifier System for duct humidification ENS Dear Customer, Many thanks for choosing to buy a STULZ product. STULZ has been a purveyor of sophisti- cated technical solutions for comfort and precision air conditioning applications since 1947. Best regards,...
If you have any questions, please call the hotline. 1.1. Validity This Technical Manual applies to STULZ UltraSonic humidifiers UltraSonic ENS 14 A - ENS 18 A. 1.2. Target group This document is intended for qualified electricians and specialist planners. The work described in this document may only be performed by persons with the requisite qualifications (see "2.3.
Page 8
Information on this document STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Abbreviation Name Explanation Float switch ─ Ground Ground wire or signal ground Auxiliary relay Voltage drop in V Current in A kg/h Kilograms per hour...
Following the assembly and operating instructions in this Technical Manual is a prerequisite for safe operation of the product and for attaining the specified product characteristics and performance features. STULZ shall not be liable for any injury or property damage or any financial loss resulting from non-compliance with the assembly and operating instructions.
Any other use besides or beyond this shall be regarded as improper use. STULZ cannot be held liable for damages resulting from the above. The risk shall be borne by the plant operator alone.
Danger of death. Electric shock risk. There is an immediate danger of death from electric shock if live parts are touched. The STULZ UltraSonic ENS ultrasonic humidifier may only be installed, connected and started up by specialist electricians. To change the settings of DIP switches or to remove the connections, always switch off the power- ●...
2.4. Compatible products The STULZ UltraSonic ENS ultrasonic humidifier is compatible with the following STULZ products: STULZ ion exchanger SD 2800 ● STULZ UltraWater reverse osmosis system ●...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Safety 2.5. Other applicable documents Besides this technical documentation, the following documents must also be observed: Circuit diagrams of the control system used ● Technical documentation of the control system used ●...
Product package STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Product package STULZ UltraSonic ENS ultrasonic humidifier ● Quick-start Guide to STULZ UltraSonic ENS ultrasonic humidifier ● The Technical Manual and Start-up Report of the STULZ UltraSonic ENS ultrasonic humidifier are available to download at www.stulz.com.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Product description The STULZ UltraSonic ENS model series is designed for duct humidification using ultrasonic atomiza- tion. Here, a transducer installed in a water bath produces a cold mist, which is expelled out of the unit into the duct due to the air flow within the duct.
4.2. Rating plate The rating plate contains the most important data for identification of the STULZ UltraSonic ENS ultra- sonic humidifier and about the application limits. The rating plate is affixed to the side of the humidifier. The data on the rating plate are required for the following: Safe use of the STULZ UltraSonic ENS ultrasonic humidifier ●...
Product description STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- odules,asolenoidvalveandtwofloatswitches.Theairintakefeaturesamaintenance-friendlyins 4.3. Description of unit thstainlesssteelguiderails,inwhichawashabledustfilterisinserted. Units in the UltraSonic ENS model series 14 A to ENS 18 A are duct humidifiers that work on the princi- hecompactUltraSonicatomizationmoduleismountedonthefloorofthewatertank.Toincrease...
4.4. Operating principle of ultrasonic humidification Ultrasonic humidifiers from the STULZ UltraSonic model series work on the principle of ultrasonic atom- ization. A 48 V alternating voltage is rectified on an nebulizer print plate and converted into a high-fre- quency signal of 1.65 MHz. This signal is transferred to an transducer installed in the water bath, which converts it into a high-frequency mechanical oscillation.
4.5. Technical data The STULZ UltraSonic ENS ultrasonic humidifier works on the principle of ultrasonic atomization. The airflow in the duct blows the mist, which was produced in a water tank with the aid of an transducer, into the room to humidify it. The ultrasonic humidifier consists of the atomization modules, the supply module with solenoid valve that lets in the water supply, float switches and a housing accommodating a fan.
Product description STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 4.7. Application limits During the planning and installation of UltraSonic humidifiers, take care to ensure that all materials that come into contact with demineralized water are resistant to it. See table at bottom of page for the most...
ENS霧化水槽A1 STE002 STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Product description L50021 112357 Nebulizing Box A2 \240 4.8. Service life of materials Only demineralized water may be used to operate ultrasonic humidifiers. Please pay attention to the ENS霧化水槽A2...
To prevent this, we urgently recom- mend the installation of downstream demineralizing equipment with conductivity monitor (e.g. STULZ ion exchanger SD 2800 in combination with the STULZ conductivity measuring kit).
Page 25
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Product description In demineralization, all ionic compounds dissolved in the water are completely removed by the ion ex- change process. A mixed bed ion exchanger is filled with a mixture of cation and anion exchange resin.
Page 27
Systeme so sicher wie möglich konstruiert und betrieben werden. Stellungnahme Bei den Ultrasonic-Befeuchtern der Firma Stulz kann das hygienische Risiko als niedrig angesehen werden. Es ist Dr. Holger Brill (Arbeitshygieniker) davon auszugehen, dass die hochfrequenten Schwingungen im Ultraschall-Befeuchter Bakterien in ihrer Lebend- keimzahl reduzieren.
Design and planning STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Design and planning This section deals only briefly with the main aspects of design and planning. You can obtain more detailed information in our STULZ UltraSonic Planning Guide.
Note Adiabatic behavior. STULZ UltraSonic humidifiers atomize the water in minuscule droplets (< 0.001 mm). The mist (aero- sols) produced in this way draws heat from the surrounding air (enthalpy) and changes its state from flu- id to aqueous. This "adiabatic" behavior (removal of heat from surrounding air) cools the air in the room.
Design and planning STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 5.2. Applications The type of water treatment may differ depending on the application. Note CAUTION Reducing conductivity. Depending on the planned application, it may make sense to further reduce conductivity.
Open-loop and closed loop control STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 6.1. Master/slave control cabinet for ultrasonic humidifier (USM/USS controller) The USM controller is an open-loop and closed-loop control unit with inbuilt microprocessor for monitor- ing, operating and controlling an ultrasonic humidifier, and for actuating additional control units (USS) in the same humidity control circuit.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Open-loop and closed loop control 6.2. Accessory sets (controlled by on-site switch gear cabinet) Accessory sets consist of individual components for creating a control system in the on-site switch gear cabinet.
Page 34
Open-loop and closed loop control STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Accessory set proportional control Accessory set for mounting a proportional control for an external control signal Interference Proportional Item Con tac- Transformer Condenser...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation Installation Please check that the product package is complete before installation CAUTION WARNING DANGER Danger of death. Electric shock risk. Faulty wiring of the switch gear cabinet can cause the humidifier to become defective.
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Systemskizze für Ultrasonic ENS 1200 A - ENS 9600 A mit proportionaler Steuerung 7.1. Installation diagram Waste water Drinking water Voltage supply Voltage supply 230V/50-60Hz/1Ph 230V/50-60Hz/1Ph Waste water...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation 7.2. Installation clearances IMPORTANT CAUTION Duct dimension The installation clearances are not mentioned for dimensioning the duct. Installing the humidifier in the duct can cause a higher air flow rate which will exceed the maximum ●...
Perforated plates reduce the free diameter by more than 60%, and therefore effectively lower the air speed through the humidifier. Both perforated plates and the bracket are available from STULZ as optional accessories (see section "3.1. Optional accessories" on page 11).
Verteilung der Feuchtigkeit im Luftstrom zu erzielen. STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation 7.3.3. Example frame Ein entsprechendes Gestell für die Aufnahme der Befeuchter im Luftbehandlungsgerät kann wie abgebildet aussehen.
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 7.3.4. Installation accessories UltraSonic air humidifiers from the ENS model series can be used for laminar flows with air speeds from 1.5 to 3 m/s. If this air speed is exceeded, a perforated plate must be mounted in front of the air inlet of the humidifier.
Page 43
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation Bracket ENS 14 A - ENS 18 A Humidifiers can be installed in the duct or air handling unit using brackets of an appropriate width for the duct or air handling unit.
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 7.4. Connecting water supply line(s) CAUTION IMPORTANT Demineralized drinking water. The ultrasonic humidifier is operated with demineralized drinking water, to ensure that the transducers retain their function throughout the unit's service life. Furthermore, if the mineral content of the water is too high for the planned application, this may lead to the formation of deposits in the humidified room.
Wasserhahn 12 Liter Wasserspeicher Gehäuseschüs \2,700 Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- available 7.4.1. Connecting the pipe for the demineralized drinking water 210-00U The supplied connection material consists of the following: Optional accessories...
Page 47
ULTRASONIC STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation Connection to PE plastic tube: ULTRASONIC Clean all components (plastic tube, 8 connector). Inlet joint on ultrasonic humidifier Screw the threaded end of the connec- tor into the inlet joint on the ultrasonic Connector humidifier.
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 7.4.2. Waste water connection Ultrasonic humidifiers from the ENS model series have two waste water connections. CAUTION WARNING Regulations from water supply companies. Regulations from water supply companies must be complied with.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation 7.4.2.1. Overview connection Proceed as follows to connect the overflow: Push a drainage hose (inside diameter 15 mm) over the overflow fitting. Überlauf Überlauf Overflow pipe 1/2", provided on site Use a clip to fix the hose in place.
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 7.4.2.2. Drain connection Connection to a drainage pipe with solenoid valve is only necessary if the water needs to be drained during longer periods of ultrasonic humidifier downtime, due to hygiene requirements.
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 7.5. Electrical connection • The operating voltage is 230 V, 50 Hz (control cabinet). • Connect the power supply cable to the terminal block of the control cabinet, i.e. L1 - N - PE.
Page 53
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation Pre-assembled cables ULTRASONIC Ansicht von Lötseite ULTRASONIC Ansicht von Lötseite ULTRASONIC Ansicht von Lötseite Ansicht von Lötseite (weiß) (schwarz) (weiß) (schwarz) (black) (schwarz) (white) (weiß) (white) (red) weiß...
BNB 5000-8000 Befeuchter Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 7.5.1.1. Connection of humidifier to USM control cabinet USM 1303 Color code black white green white black ENS 8400P-9600P Befeuchter In circuit diagram 00VA...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation 7.5.1.3. Connection of humidifier accessory sets CAUTION Note Connection of accessory sets. To connect accessory sets, please pay attention to the circuit diagrams in the technical documentation for accessory sets.
Page 56
Installation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Example: A ENS 14 A is installed and the associated switch gear cabinet is situated at a distance of 5 m. The wir- ing will therefore have a cable cross-section of 2.5 mm .
Start-up STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Start-up All steps from section "7. Installation" on page 31 must have been completed prior to start-up. CAUTION WARNING Electrical connections are secure. After transport/delivery, check that electrical connections are secure and re-tighten if necessary.
Page 59
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Start-up Proceed as follows to ensure safe start-up: Establish a supply of demineralized drinking water: a) Open the on-site stop cock in the drinking water supply pipe. b) Check the demineralized drinking water at the ultrasonic humidifier.
Start-up STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 8.1. Reports and checklists for STULZ UltraSonic humidifiers We have provided you with a checklist to facilitate start-up. You can find the Start-up Checklist, Test Report and Maintenance Checklist on the final pages of this manual or available to download on our web site at www.stulz.com.
Operation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 9.1. Operation The humidifier is operated using the connected control module. The manuals of this module are available to download on our web site at www.stulz.com. CAUTION Pay attention to controller.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Operation 9.1.1. Using the USM 9.1.1.1. Changing the menu levels In the control system, you can choose between three menu levels. After the unit has started and follow- ing automated cleaning, the main menu interface is displayed.
Page 64
Operation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- drü Proceed as follows to change to the main menu: und zusä Menüaufbau Anwe Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) ca. 5 s C Press "OK". betätigen Befeuchtungssteuerung ü...
The parameter that is to be set depends on the type of signal from the humidity sensor. Please read the technical documentation of the humidity sensor. You can find additional setting parameters for individual applications in the Technical Manual for STULZ UltraSonic master/slave control units USM/USS on our web site at www.stulz.com.
Page 66
Menüaufbau Anwe Operation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) Befeuchtungssteuerung ü drü Proceed as follows to set the operating mode: und zusä ca. 5 s C Main menu (factory setting) is selected.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Operation drü und zusä ca. 5 s C Press "OK". betätigen Befeuchter mode Ext. Anford. capacit 1.00 Anfrd supp 15.00 room 20.00 Ausg: drü drü und zusä Grundmenü...
Page 68
Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) drü Befeuchtungssteuerung ü Operation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- und zusä ca. 5 s C Press and hold the "Esc" button until the betätigen -> setpoint cursor is under the first parameter.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Operation 9.2. Booster fan (optional) 9.2.1. Description of booster fan UltraSonic air humidifiers are frequently installed in air ducts and air handling units. If infinitely adjustable fans are used in air handling units, the air speed may fall below 1.5 m/s, which is the minimum permitted for the UltraSonic air humidifier.
Operation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 9.2.3. Dimensional drawing of booster fan View "B" View "A" Item number Description Humidifier ENS 14 / 18 A Droplet separator Connector Oscillator connection Control system connection...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Operation 9.2.4. Installing the booster fan Please check that the product package is complete before installation CAUTION WARNING DANGER Danger of death. Electric shock risk. Faulty wiring of the switch gear cabinet can cause the humidifier to become defective.
Page 72
Operation STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Installation Proceed as follows to install the booster fan: Remove the feet of the ENS humidifier. Mount the ENS humidifier on the supplied brackets of the booster fan.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Decommissioning Decommissioning 10.1. Switching off IMPORTANT CAUTION Interrupted water supply. Only turn off the water supply if there is no electrical power to the fill valve. The coil needs the cold water for cooling. There is a danger it might melt! ●...
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance CAUTION WARNING DANGER Danger of death. Electric shock risk. Power to the system must be switched off during maintenance checks. The water supply line valve must also be closed.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance 11.1. Maintenance cycles Content of general maintenance checks: Job to be performed Scope of checks Time interval Page Check for secure - Tightness of connections of water-bearing parts...
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 11.2. Checklist for hygiene checks CAUTION Note Separate logbook. All tests and measurements must be documented in a separate logbook. Note CAUTION Shortened inspection intervals. If the specified recommended values are exceeded, the inspection intervals described here must be halved until the results of inspections are no longer critical and remain so over the long term.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance 11.3. Visual inspection CAUTION IMPORTANT Time intervals of maintenance cycles . If mineral salt residues or other major impurities are discovered, check the water treatment system and its monitoring devices (conductivity measuring equipment/humidity sensors).
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 11.4. Cleaning CAUTION WARNING DANGER Danger of death. Electric shock risk. Switch off power to the system before cleaning! 11.4.1. Cleaning water-bearing parts If checks reveal that the above parts feature bacteria or mineral salts, clean the unit as follows:...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance 11.4.2. Cleaning the water tank, oscillators and mist outlets Proceed as follows to clean the water tank, oscillators and mist outlets: Slacken but do not fully remove the screws.
Page 80
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Clean the water tank. Only clean the surface of the oscillator with a soft cloth, to prevent scratches. CAUTION IMPORTANT Float switches . Take care not to damage the float switches!
Page 81
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance Disinfect the water tank: a) Brush or spray all parts with 5 % hydrogen peroxide solution (H minimum of three times at 15-minute intervals. b) After an exposure time of approx.
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 11.5. Inspecting the electrical system 3 4 7 12 Proceed as follows to inspect the electrical system: CAUTION WARNING Specialist personnel. MIST OUTLET This work may only be performed by specialist 110...
Page 83
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance Check whether there is any humidity or corrosion in the control system. Make sure that the unit has no leaks Check the fill valve, coil and body.
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- 11.5.1. Replacing the relay PCB Proceed as follows to replace the relay PCB: CAUTION Note Marked cables . When inserting cables later on, there cannot be any confusion as both the PCB and the cables are marked.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance 11.5.2. Replacing the fill valve and float switch Proceed as follows to replace the float switch: Perform steps 1-4 from section Slacken and fully remove the screws.
Page 86
Schalter. Wasserversorgung ON Status Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- OFF Status Operating principle of float switches: Fehlfunktion bei Vertauschen Malfunction if interchanged Der Magnetring hält den Switch Schalter Schalter in geöffneter Position, so dass das...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance 11.5.3. Replacing oscillators and the atomizer PCB Proceed as follows to replace the oscillators: Perform steps 1-6 from section "11.5. Inspecting the electrical system" on page 78.
Page 88
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- IMPORTANT CAUTION Color coded cables . The cables are color coded and must not be inter- changed! ORG = orange cable, YEL = yellow cable Detach the orange and yellow oscillator cables from the atomizer PCB.
Page 89
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Maintenance Proceed as follows to replace the atomizer PCB: CAUTION Note Replacing the oscillator . We recommend also replacing the oscillators if you are replacing the atomizer PCB.
Page 90
Maintenance STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Reconnect the orange and yellow cables of the oscillator and the black and white or red and green supply cable, and assem- ble the unit in reverse order.
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Dismantling and disposal Dismantling and disposal 12.1. Dismantling CAUTION WARNING Specialist personnel. This work may only be performed by specialist personnel. Proceed as follows to dismantle the unit: Shut down the ultrasonic humidifier.
Spare parts lists STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Spare parts lists All sizes in mm. Pos. STULZ Exploded assembly drawing Description Code Eliminator Mist outlet STEL001 M01855 Nebulizer unit NB59S AC48V STE007 L50070...
Page 93
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Spare parts lists Silicon Sheet STEL019 M01318 Spacer for transducer STEL009 L50099 O-ring for heat sink STE006 34.6mm I.D. L50090 Solenoid valve 48V AC stainless steel STEL036 M75224...
Page 94
Spare parts lists STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Coil fill valve STE039 M59860 Float switch water supply FS-0850B STEL006 M01858 Float switch low level cut off FS-0850A STEL007 M01859 Relay plate STEL008 M01861...
Page 95
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Spare parts lists Relay plate protection STEL015 M01867 Protector AD-100 STEL016 M01868 Protector AD-100 STEL017 M01869 Thermostat incl. wiring l=1170mm STEL018 M01871 Cord control with metal connector 3pin 4m...
Page 96
Spare parts lists STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Cord main with metal connector 4pin 4m STEL024 M25370 Cord control with stainless steel connector 3pin 2m STEL012 M01865 Cord main with stainless steel connector...
Page 97
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Spare parts lists Metal connector receptacle 4pin SNW4P STEL013 M01446 Metal connector receptacle 3pin SNW3P STEL014 M01866 Drain pipe STEL028 M45143 Gasket drain pipe STEL027 M35991 Ring and nut for...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Troubleshooting Troubleshooting Troubleshooting table ENS 14 A - 18 A Situation Cause Solution Explanation No mist Unit is not in Start up the unit; check function of control...
Page 100
Troubleshooting STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Index Maintenance .......72 Maintenance check .
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Start-up Checklist Start-up Checklist Start-up Checklist for STULZ UltraSonic® Humidifiers The technical documentation of all units to be started up and their accessories is to hand All humidifiers are precisely horizontal and securely mounted...
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Humidification Test Report Humidification Test Report TEST REPORT TEST REPORT STULZ GMBH STULZ UltraSonic® KLIMATECHNIK Air Conditioning & Humidifying Ultrasonic Humidifier STULZ GMBH Systems Division STULZ UltraSonic® KLIMATECHNIK...
Page 109
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A- Humidification Test Report Installation Controller type: Software version: Number of humidifiers in master/slave arrangement: Electrical connections checked Humidity sensor 1 connected Type of signal used: ...
Page 110
STULZ UltraSonic Humidifier ENS O R I G I N A L I N S T R U C T I O N S STULZ Top Service – More than just quick emergency assistance Technical Manage- Advice Maintenance Implementation Test Center...