Summary of Contents for elsner elektronik KNX AQS/TH-B-UP
Page 1
Combined Indoor Sensor Technical specifications and installation instructions Article numbers 70239 (white), 70240 (aluminium), 70241 (anthracite), 70242 (stainless steel) Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D – 75391 Gechingen Phone +49 (0) 70 56 / 93 97-0 info@elsner-elektronik.de...
Page 2
8 logic inputs in the form of communication objects, may be used as inputs for the logic gates. The output of each gate may optionally be configured as 1 bit or 2 x 8 bits Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
254 Allocations max. 254 Communication objects measurement range 0...2000 ppm resolution 1 ppm accuracy* ± 50 ppm ± 3% of the measuered value Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
Page 4
The heating is compensated by reducing the measured temperture by the self-heating of 1.8°C. The indicated indoor temperature measured value approches the actual room temperature during a 2 hours heating period. Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
(standing or sitting, according to utilization of room). The CO concentration in indoor rooms is highest near the floor and decreases towards the ceiling. Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
Page 6
Catches Openings for air circulation Push button Programming LED (recessed) Programming button (recessed) for teaching device Push button Openings for air circulation (LOWER) Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
After the bus voltage has been applied, the device will enter an initialisation phase lasting a few seconds. During this phase no information can be received via the bus. Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
Mode display with scale display and range. Shows the possible adjustment range (as set in the ETS). The control position in the image reads "Base target value reduced". Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
ETS or be suppressed for Priority 1 operating modes. The individual operating modes can also be locked for manual selection in the ETS. Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
Page 10
2 secs. evening). The period is defined in the ETS (up to 10 hours). The time remaining in Comfort mode is displayed. Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.