EQJW245
Resistance values for the Ni1000 sensors
10
Resistance values for the
www.sauter-controls.com
Ni1000 sensors
The temperature sensors required depending on the use of the EQJW 125 must
conform to DIN 43760.
The resistance value of the nickel measuring resistor changes in relation to the
temperature. The temperature coeffi cient is always positive, i.e. the resistance
increases as the temperature rises. See the table of values (DIN 43760). Within
the specifi ed tolerances, the sensors can be exchanged without calibration.
Temperature (°C)
Resistance value (Ω) Ni1000
90
1549
80
1483
70
1417
60
1353
50
1291
40
1230
30
1171
20
1112
10
1056
0
1000
-10
946
-20
893
-30
842
-40
791
Tab.11
Resistance value Ni1000
105/127
Need help?
Do you have a question about the equitherm EQJW245 and is the answer not in the manual?