O2MaxManVariable and O2MinManVariable – These parameters set how much the O
in an attempt to achieve the O
O2MaxManVariable sets how much the system can increase the air rate.  Likewise, O2MinManVariable 
sets how much the system can decrease the air rate. 
Menu path:  Params & Display > O2Contr/Alarm > Gas Settings > Control Param 
 
These trim limits must be set so that the O
should not be set in a way that allows the burner to run at an unsafe fuel‐air ratio. 
 
Ideally, the O
 trim system must compensate for two main environmental conditions.  These conditions 
2
are ambient air temperature and barometric pressure.  Figure 6‐8 illustrates how much the manipulated 
variable needs to change to compensate for these environmental conditions.  The chart in Figure 6‐8 
and the example in Figure 6‐9 serve as a guideline for setting the O2MaxManVariable and 
O2MinManVariable parameters. 
 
 
Figure 6‐8:  Theoretical Change of the Manipulated Variable with Changes in Ambient Temperature 
 
When the O
 Control Curve is commissioned, all burners will be at (0, 0) on the chart, where the X‐axis 
2
and Y‐axis cross.  As air temperature and barometric pressure change from the air temperature and 
 
SCC Inc. 
 
 
 setpoint ‐ essentially the trim limits for the O
2
 system can achieve the O
2
and Pressure 
Page 21 
HOME
Technical Instructions 
Document No. LV5‐1000 
 system can trim 
2
 system.  
2
 setpoint.  However, the limits 
2
 
Section 6 
 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents