Procedure for Changing /removing the alarm CL on the LAE AT1-5
The front panel of the LAE RL2 Controller has an LED display and four push-
buttons which will be referred to in numerical order 1-4 from left to right. The LED
Display normally shows the measured temperature.
In order to remove the alarm CL (CONDENSER CLEAN) , it is now necessary to
operate these push-buttons in certain combinations as outlined below. The
following points correspond in number with the diagrams on the following page.
1. Press and hold buttons 1 and 4 simultaneously.
2. After 5 seconds, the LED display shows 'ScL' – release buttons 1 and 4.
3. Press button 3 until the display shows ACC
4. Display will now reads ACC
5. Press and hold button 1
6. Immediately the LED display shows the current setting (25)
7. While still holding button 1, repeatedly press button 3 to increase the
setting
8. While still holding button 1, repeatedly press button 2 to decrease the
setting (advised to take this to zero to deactivate the alarm)

Controller

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AT1-5 and is the answer not in the manual?

Questions and answers

Summary of Contents for LAE AT1-5

  • Page 1 Procedure for Changing /removing the alarm CL on the LAE AT1-5 Controller The front panel of the LAE RL2 Controller has an LED display and four push- buttons which will be referred to in numerical order 1-4 from left to right. The LED Display normally shows the measured temperature.
  • Page 2 When the preferred setting has been selected, release all buttons, the LED display will then revert back to normal...

Table of Contents

Save PDF