5. Guide the other hose end to a suitable drain or sufficiently
dimensioned collection container. Please note that the
hose must not be kinked.
Remove the hose if you want to collect the condensate in the
condensation tank again. Allow the hose to dry prior to storage.
The hose can be connected in any operating mode for
continuous operation.
Automatic defrost
At low ambient temperatures (below 12 °C), ice may form at the
evaporator during dehumidification. The device will then carry
out an automatic defrost. Dehumidification is briefly interrupted
during defrosting. The fan keeps running.
The automatic defrost LED (11) is illuminated throughout the
defrost process.
The duration of the defrost process can vary. Do not switch the
device off during automatic defrost. Do not remove the mains
plug from the mains socket.
Drying laundry
In addition, the device may also be used as a kind of clothes
dryer to dry wet laundry in living or working spaces.
When positioning the device or a clothes horse, please observe
the minimum distances specified in the technical data.
The following humidity values are suitable for drying laundry:
• cupboard dry = 46 % relative humidity
• iron dry = 58 % relative humidity
• slightly dried = 65 % relative humidity
Adjust the settings for the relative humidity level to the device
(e.g. 60 % relative humidity for iron dry laundry). If necessary,
use a measuring device to determine the humidity level.
10
Shutdown
Warning of electrical voltage
Do not touch the mains plug with wet or damp hands.
• Switch off the device.
• Hold onto the mains plug while pulling the power cable out
of the mains socket.
• If necessary, remove the condensation drain hose and any
residual fluid from it.
• Empty the condensation tank, if need be.
• Clean the device according to the Maintenance chapter.
• Store the device according to the Storage chapter.
Errors and faults
The device has been checked for proper functioning several
times during production. If malfunctions occur nonetheless,
check the device according to the following list.
The device does not start:
• Check the power connection.
• Check the power cable and mains plug for damage.
• Check the on-site fusing.
• Check the filling level of the condensation tank and empty
it if necessary. The condensation tank full LED (10) must
not light up.
• Check the condensation tank for correct seating.
• Check the room temperature. Observe the device's
permissible operating range according to the technical
data. Possibly, the device does not start because the
ambient temperature is too low (< 5 °C).
• Wait for 10 minutes before restarting the device. If the
device is not starting, have the electrics checked by a
specialist company or by Trotec.
The device is running, but there is no formation of
condensate:
• Check the float in the condensation tank for dirt. If
necessary, clean the condensation tank. The float must be
able to move freely.
• Check the room temperature. Observe the device's
permissible operating range according to the technical
data. Possibly, the device does not start because the
ambient temperature is too low (< 5 °C).
• Ensure that the relative room humidity complies with the
technical data.
• Check the preselected relative room humidity. The
humidity in the room must be above the selected range.
• Check the air filter for dirt. If necessary, clean or replace
the air filter.