Installation and Operating Instructions
CHAPTER 4
FUNCTION
m
NOTE
CHAPTER 5
USER MAINTENANCE
m
WARNING
m
WARNING
Flat EC Centrifugal Fan Boxes – SlimVent SV.. EC ...
3.2

Accessories

The use of accessories not offered or recommended by Helios is not permitted. Any potential damage is not covered
by warranty.
Pipe clamp connectors
Flexible mounting clamp
Backdraught shutter
Outside wall cover flap
Outside wall cover grille
Protection grille
Speed potentiometer
Three-step switch
Universal control system
Differential pressure/temperature controller
Flexible sound attenuator
Warm water heater battery
Temp. control system for warm water heater battery
Electric heater battery
– with integrated temp. control
Temp. control system for EHR-R..
Air filter box
Duct system:
All Helios components fit standard duct Ø. For example, rigid spiral ducts, flexible aluminium or plastic ducts can be
used. The relevant fire-protection regulations must be observed if more than two stories of a building are connected.
4.0
Functional description SV.. EC ...
The SlimVent SV.. EC..are variable speed controllable by means of a 0-10 V control voltage. Suitab-
le potentiometers (Type PU/A 10), three-step switches (Type SU/A) are available in the Helios accessory
range. Variable speed control is possible with a universal control system (Type EUR EC). Alternatively,
the electronic differential pressure/temperature controller EDR / ETR can be used.
m
Activation / deactivation:
EC fans can be frequently activated and deactivated via the 0-10 V control input or the release input
depending on the type. This is gentle on the electronics and ensures a long service life. Control via the
power supply (on/off) is not recommended. In general, there must be an interval of at least 120 seconds
between activation and deactivation.
m
In case of strong vibrations and/or odours, maintenance must be carried out by a specialist according to
chapter 1.4.
5.0

Swing-out motor impeller unit

1. Isolate the unit from the power supply and secure against switching on again!
2. Loosen the four outer fixing screws (do not remove screws!)
Turn cover so that it swings out (Fig.2/3).
Fig.2
5.1

Cleaning

m
An insulation/installation fault may result in electric shock! Before cleaning, isolate the fan from the mains
power supply and protect against being switching on again!
Waiting period of at least 5 minutes!
m
When using capacitors, there is a danger to life after deactivation due to the direct touching of live parts.
Terminal compartment access is only permitted after the power supply is disconnected and a 5 minute waiting
period.
m
The unexpected rotating impeller can crush fingers.
Before cleaning, isolate the fan from the mains power supply and protect against being switching on again!
– Clean casing and impeller with a damp cloth
– The motor must not come into contact with water!
– Do not use aggressive cleaning agents that could damage the paintwork!
– High pressure cleaners or water jets are not permitted!
BM..
FM..
RSKK / RSK
VK..
G / RAG..
SGR
PU/A 10
SU/A
EUR EC
EDR/ETR
FSD..
WHR
WHST.. / WHS HE.. -
EHR-R..
EHR-R..TR
EHS
LFBR..
Fig.3
5
EN
only SVR EC types
only SVS EC types
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Chapters

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SlimVent SVR EC Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Slimvent svr ec 160 aSlimvent svr ec 160 bSlimvent svr ec 200Slimvent svs ec 125Slimvent svs ec 160 aSlimvent svs ec 160 b ... Show all

Table of Contents