Electrical Wiring - Fujitsu AGU9RLF Installation Manual

Indoor unit (floor type)
Hide thumbs Also See for AGU9RLF:
Table of Contents

Advertisement

When using conventional fl are tools to fl are R410A pipes, the dimension A should be
approximately 0.5 mm (1/32 in.) more than indicated in the table (for fl aring with R410A
flare tools) to achieve the specified flaring. Use a thickness gauge to measure the
dimension A.
Width across flats
flats
diameter [mm (in.)]
6.9.2. Bending pipes
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it
diffi cult to bend or stretch them any more.
• Do not bend or stretch the pipes more than 3 times.
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
6.9.3. Pipe connection
Be sure to install the pipe against the port on the indoor unit correctly. If the centering
is improper, the fl are nut cannot tighten smoothly. If the fl are nut is forced to turn, the
threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before
connecting the connection pipe.
Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to
tighten the fl are nut correctly.
Tighten the flare nuts with a torque wrench using the specified tightening method.
Otherwise, the fl are nuts could break after a prolonged period, causing refrigerant to
leak and generate hazardous gas if the refrigerant comes into contact with a fl ame.
Connect the piping so that the control box cover can easily be removed for servicing
when necessary.
In order to prevent water from leaking into the control box, make sure that the piping is
well insulated.
When the flare nut is tightened properly by your hand, hold the body side coupling
with a wrench, then tighten with a torque wrench. (See following table for the fl are nut
tightening torques.)
Tighten with two wrenches.
Wrench (fi xed)
Torque wrench
Flare nut [mm (in.)]
6.35 (1/4) dia.
9.52 (3/8) dia.
12.70 (1/2) dia.
15.88 (5/8) dia.
19.05 (3/4) dia.

7. ELECTRICAL WIRING

Cable
Cable size
Connection cable
14AWG UL 1505
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage
drop is 2% or more.
Pipe outside
Width across fl ats of
Flare nut [mm (in.)]
6.35 (1/4)
17 (21/32)
9.52 (3/8)
22 (7/8)
12.70 (1/2)
26 (1-1/32)
15.88 (5/8)
29 (1-5/32)
19.05 (3/4)
36 (1-13/32)
CAUTION
CAUTION
Indoor unit pipe
Flare nut
Connection pipe
Tightening torque [N·m (kgf·cm)]
16 to 18 (160 to 180)
32 to 42 (320 to 420)
49 to 61 (490 to 610)
63 to 75 (630 to 750)
90 to 110 (900 to 1,100)
Remarks
3 cable+Earth (Ground),
1φ 208/230 V
] 1
7.1. Wiring system diagram
Before connecting the wires, make sure the power supply is OFF.
Every wire must be connected fi rmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any moving
part.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fi re
hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.
INDOOR UNIT SIDE
INDOOR UNIT
TERMINAL
DISCONNECT
SWITCH
(FIELD SUPPLY)
] 1
7.2. Indoor unit wiring
(1) Remove the terminal cover.
(2) Remove the cable clamp.
(3) Bend the end of the connection wire as shown in the fi gure.
(4) Connect the end of the connection wire fully into the terminal block.
(5) Fasten the connection wire with a cable clamp.
Cable
clamp
Terminal
cover
Cable
clamp
Connection
cable
• To connect the indoor unit wires to the terminal correctly, refer to the fi gure for proper
length.
Earth (Ground) wire
14AWG
10 (6/16)
10 (6/16)
65 (2-9/16)
85 (3-6/16)
Conduit connector
WARNING
OUTDOOR UNIT
or BRANCH BOX
Power line
Connect it to
Control line
the specifi ed
Earthing
terminal.
(Grounding) line
Unit: mm (in.)
En-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents