Leroy-Somer PROXIDRIVE Installation And Commissioning Manual
Leroy-Somer PROXIDRIVE Installation And Commissioning Manual

Leroy-Somer PROXIDRIVE Installation And Commissioning Manual

Ip66/nema 4x variable speed drive
Hide thumbs Also See for PROXIDRIVE:
Table of Contents

Advertisement

IP66/Nema 4X variable speed drive
Installation and commissioning manual
PROXIDRIVE
10V
0-10V analog reference
ADI1
0V
4-20mA analog reference
ADI2
0V
0-10V motor speed image output
ADIO3
Zero speed output
DIO1
+24V
Run FWD/Stop
DI2
DI3
Run REV/Stop
+24V
Selection of ADI1/ADI2
DI4
SDI1
Secure input
SDI2
3739 en - 06.2007/e
COM
RL1C
Fault relay
RL1O
SDO1
Secure contact
SDO2
DI4
Selection
0
0-10V analog reference (ADI1)
1
4-20mA analog reference (ADI2)
Nota : SDI2 input must be closed before giving
Run command.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PROXIDRIVE and is the answer not in the manual?

Questions and answers

Summary of Contents for Leroy-Somer PROXIDRIVE

  • Page 1 Run FWD/Stop 0-10V analog reference (ADI1) Run REV/Stop 4-20mA analog reference (ADI2) +24V Selection of ADI1/ADI2 Nota : SDI2 input must be closed before giving SDI1 Run command. Secure input SDI2 PROXIDRIVE IP66/Nema 4X variable speed drive Installation and commissioning manual...
  • Page 2 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive NOTE LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments. The information contained in this document may therefore be changed without notice.
  • Page 3 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive SAFETY AND OPERATING INSTRUCTIONS FOR VARIABLE SPEED DRIVES (In accordance with the low voltage directive 73/23/EEC modified by 93/68/EEC) • Throughout the manual, this symbol warns of...
  • Page 4 IP66/Nema 4X variable speed drive FOREWORD This manual describes the installation and commissioning of IP66/Nema 4X PROXIDRIVE variable speed drives. It also gives details of all its options and extensions which the user may choose to suit his requirements. PROXIDRIVE - SET...
  • Page 5: Table Of Contents

    3.5 - Connection of the control ..........................18 3.5.1 - Terminal characteristics........................18 3.5.2 - Connection of a PROXIDRIVE CP control terminal block ..............19 3.5.3 - Preset configurations for the control terminal block................20 3.6 - EMC recommendations ..........................27 3.6.1 - Using EMC cable glands ........................
  • Page 6 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive ONTENTS 6 - OPERATING EXTENSIONS....................... 65 6.1 - Add-on options............................. 65 6.1.1 - Access to slots..........................65 6.1.2 - XPressKey ............................65 6.1.3 - PX-Encoder ............................66 6.1.4 - PX-Brake Contactor..........................
  • Page 7: General Information

    Rating in kVA supplying 3-phase induction motors. 230 V 3-phase power supply (TL) In the standard version, the PROXIDRIVE is an open loop 400 V 3-phase power supply (T) ) flux vector drive with very high performance levels PROXIDRIVE : IP66 flux vector...
  • Page 8: Electrical Characteristics

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive GENERAL INFORMATION 1.4 - Electrical characteristics 3-phase mains, 208V -10% to 240V +10% PROXIDRIVE Power Current 1.4.1 - General characteristics Size Rating at 230V at 230V at 4.5 kHz...
  • Page 9: Electromagnetic Compatibility (Emc)

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive GENERAL INFORMATION 1.5 - Electromagnetic compatibility (EMC) WARNING: Conformity of the drive is only assured when the mechanical and electrical installation instructions described in this manual are adhered to.
  • Page 10: Ul Conformity

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive GENERAL INFORMATION 1.6 - UL conformity • For UL conformity, the operating temperature must not exceed 40 °C. • Motor overload protection The drive has motor overload protection.
  • Page 11: Mechanical Installation

    100 mm above and below to ensure that air can flow freely installation must be approved. around the heatsink. - Do not place the PROXIDRIVE above a heat source. 2.3 - Dimensions and weight Sizes 1 and 2 Size 3...
  • Page 12: Connections

    See section 6.5 • The plugs fitted as standard on the plate can be used as cable bushes if the PROXIDRIVE is installed in an enclosure which is not subject to condensation (damp enclosure and/or enclosure subject to significant temperature variations) or if the environment permits a protection index limited to IP 54/Nema 12.
  • Page 13: Location Of Terminal Blocks

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.3 - Terminal block locations Control terminal blocks Analog I/O Digital I/O Secure disable Relay outputs input Removable screw terminal block: tightening torque = 0.3 N.m/0.22 Ib ft = 1.5 mm 2...
  • Page 14: Ac 3-Phase Power Supply, In Accordance With Safety Standard En954-1 - Category 1

    The special way in which the secure disable input is managed is not compatible with the Run/Stop commands being controlled by the PROXIDRIVE CP and SET keypads. When control via a keypad is required, input SDI2 should be viewed as a simple unlocking input. In this case, the power diagram must comply with the usual safety regulations.
  • Page 15: Ac 3-Phase Power Supply, In Accordance With Safety Standard En954-1 - Category 2 Or 3

    The special way in which the secure disable input is managed is not compatible with the Run/Stop commands being controlled by the PROXIDRIVE CP and SET keypads. When control via a keypad is required, input SDI2 should be viewed as a simple unlocking input. In this case, the power diagram must comply with the usual safety regulations.
  • Page 16: Cables And Fuses

    3.4.4 - Cables and fuses • It is the responsibility of the user to connect and provide protection for the PROXIDRIVE in accordance with current legislation and regulations in the country of use. This is particularly important as regards the size of the cables, the type and rating of fuses, the earth or ground connection, powering down, acknowledging faults, insulation and protection against overcurrents.
  • Page 17 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS Notes...
  • Page 18: Connection Of The Control

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.5 - Connection of the control ADI2 Analog or digital input 2 Analog voltage (common Characteristics • PROXIDRIVE positive logic mode) or unipolar current configuration.
  • Page 19: Connection Of A Proxidrive Cp Control Terminal Block

    3.5.2 - Connection of a PROXIDRIVE CP Digital input control terminal block Absolute maximum voltage 0V to +35V range As standard, the PROXIDRIVE CP cannot be used to access parameter setting. Load 15 kΩ Follow the connection diagram below for commissioning Input threshold 7.5V...
  • Page 20: Preset Configurations For The Control Terminal Block

    3.5.3 - Preset configurations for the control terminal block WARNING: These configurations can be accessed from a PROXIDRIVE SET or from a PROXIDRIVE N combined with an LCD keypad or the PROXISOFT software. The PROXIDRIVE enables the user to configure the terminal block very easily by selecting one of the different preset configurations from a single parameter (05).
  • Page 21 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.5.3.3 - Configuration A2.Pr: current reference (4-20mA) 3.5.3.4 - Configuration 4Pr: 4 preset references or 3 preset references (Before modifying 05, the drive must be...
  • Page 22 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.5.3.5 - Configuration 8Pr: 8 preset references 3.5.3.6 - Configuration E.Pot: motorised potentiometer (Before modifying 05, the drive must be (Before modifying 05, the drive must be 05 = E.Pot...
  • Page 23 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.5.3.7 - Configuration Torq: Speed or torque control 3.5.3.8 - Configuration PID: PID control (Before modifying 05, the drive must be (Before modifying 05, the drive must be...
  • Page 24 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.5.3.9 - Configuration PUMP: pump control 3.5.3.10 - Configuration A.CtP: voltage or current input and PTC sensor management (Before modifying 05, the drive must be (Before modifying 05, the drive must be = A.CtP...
  • Page 25 CONNECTIONS 3.5.3.11 - Configuration HoiS: control of travelling crane 3.5.3.12 - Configuration Pad: control via keypad or hoist (PROXIDRIVE CP factory setting, invalid for the PROXIDRIVE N) (Before modifying 05, the drive must be 05 = HoiS disabled, SDI2 open).
  • Page 26 INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive CONNECTIONS 3.5.3.13 - Configuration HuAC: auto-manual mode (invalid for the PROXIDRIVE N) (Before modifying 05, the drive must be = HuAC disabled, SDI2 open). ADI1 4-20mA auto speed...
  • Page 27: Emc Recommendations

    This may be the case in the Given that the PROXIDRIVE cable gland plate is made of event of lightning strikes or earth faults associated with long metal, and connected to the general earth, the use of EMC cable lengths (>30 m).
  • Page 28: Commissioning

    Function display Display comprising 4 x 7-segment digits for indicating: The PROXIDRIVE SET operator panel consists of a display, three control buttons and three parameter-setting keys. - the drive operating status - certain operating data The PROXIDRIVE CP operator panel consists of a display, - the adjustment parameters (01 to 80) and their three control buttons and a potentiometer button.
  • Page 29: Commissioning The Proxidrive Cp

    INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.2 - Commissioning the PROXIDRIVE • As standard, the PROXIDRIVE CP cannot be used access parameter setting. Before commissioning, check that the factory settings are suitable for the application.
  • Page 30: Commissioning The Proxidrive Set

    4.3.1 - Parameter setting WARNING: • This procedure has been drawn up for initial The PROXIDRIVE factory configuration can be modified in commissioning. order to meet the requirements of the application. • If the drive is already powered up, the first parameter The parameter-setting keys are used to select and modify a displayed may not be 01.
  • Page 31: Selection Of The Parameter Access Level

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.3 - Selection of the parameter access level 4.3.6 - Security code • Selection of level 2 In some cases, it is necessary to prevent modification of the drive parameters, while still allowing them to be read.
  • Page 32: Commissioning Using A Preset Configuration

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7 - Commissioning from a preset configuration • The parameter values affect the motor protection and the safety of the system. • Parameters concerning the motor must be set using the information given on the nameplate of the motor used.
  • Page 33 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.2 - Configuration A1.Pr: selection of a voltage reference (0-10V) or 3 preset references via 2 digital inputs • Connection of the control terminal block (reminder)
  • Page 34 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.3 - Configuration A2.Pr: selection of a current reference (4-20mA) or 3 preset references via 2 digital inputs • Connection of the control terminal block (reminder)
  • Page 35 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.4 - Configuration 4Pr: selection of 4 preset references via 2 digital inputs • Connection of the control terminal block (reminder) Reference select ADI1...
  • Page 36 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.5 - Configuration 8Pr: selection of 8 preset references via 3 digital inputs • Connection of the control terminal block (reminder) Reference select ADI1...
  • Page 37 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.6 - Configuration E.Pot: motorised potentiometer • Connection of the control terminal block (reminder) ADI1 Main reference 0-10V RL1C Fault relay (if necessary) RL1O...
  • Page 38 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.7 - Configuration TorQ: selection of speed control or torque control with speed limiting via digital input • Connection of the control terminal block (reminder)
  • Page 39 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.8 - Configuration PID: PID control • Connection of the control terminal block (reminder) PID reference ADI1 RL1C Fault relay RL1O PID feedback ADI2...
  • Page 40 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.9 - Configuration PUMP: pump regulation • Connection of the control terminal block (reminder) Pressure reference (PID control) or speed reference (manual mode) ADI1...
  • Page 41 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • List of corresponding parameters 01 to 58 Parameter Name Address Type Configuration setting Adjustment range 1.07 R-W 0 to (parameter 02) min Minimum reference clamp 1.06 R-W...
  • Page 42 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.10 - Configuration A.CtP: Voltage or current input and PTC sensor management • Connection of the control terminal block (reminder) ADI1 RL1C Analog reference...
  • Page 43 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.11 - Configuration HoiS: Control of travelling crane or hoist • Connection of the control terminal block (reminder) Setting the speed reference to the max...
  • Page 44 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.7.12 - Configuration Pad: control via keypad • Connection of the control terminal block (reminder) ADI1 RL1C Fault relay RL1O ADI2 PTC sensor *...
  • Page 45 Run/Stop commands and the reference come Manual SDI1 Secure disable/ from the PROXIDRIVE SET keypad Drive enable input SDI2 • Parameters to be set Check that the drive has been disabled (terminal SDI2 open). Set parameter 05 to "HuAC", then set the drive parameters. Set parameter 10 to "L2"...
  • Page 46: Commissioning (Continued)

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.3.8 - Commissioning (continued) Key: RO = read-only parameter; R-W = read-write parameter. = Open loop flux vector control; = Closed loop flux vector control.
  • Page 47 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • If 36 = COnt, rEI, USEr: Parameter Name Address Type Factory setting Adjustment range 12.42 R-W Upper current threshold 0 to 200% 12.43 R-W...
  • Page 48 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING Parameter Name Address Type Factory setting Adjustment range FrEE: freewheel stop; rAMP: stop on ramp; rP.dC: stop on ramp with DC injection; 6.01 R-W...
  • Page 49: Detailed Explanation Of Parameters

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.4 - Detailed explanation of the : Selection of preset configuration A1.A2 : One 0-10V voltage reference input and one 4- parameters 20mA current reference input selectable via digital input.
  • Page 50 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • Configurations A1.A2, A1.Pr, A2.Pr, E.Pot, TorQ, Pid • Configurations A1.A2, TorQ, Pid, PUMP and HuAC: ADI2 and PUMP: ADI1 mode mode Used to define the type of signal on the ADI1 input.
  • Page 51 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • Configurations A1.Pr, A2.Pr, 4Pr and 8Pr: Preset • Configurations A1.Pr, A2.Pr, 4Pr and 8Pr: Preset reference 3 reference 4 Used to define preset reference Pr3.
  • Page 52 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • Configuration Pid: ADIO3 input scaling • Configuration 8Pr: Preset reference 6 Used if necessary to scale the analog input. However, this Used to define preset reference Pr6.
  • Page 53 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • If 25 = oP.LP: Open loop mode select ( • If 25 = cL.LP or Srvo: Drive encoder filter ( This parameter is used to insert a filter in the encoder speed Determines the open loop control mode.
  • Page 54 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING : Current loop proportional gain • If 36 ≠ dis: Brake release frequency : Current loop integral gain Used to set the frequency threshold at which the brake will be •...
  • Page 55 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • All configurations except PUMP configuration: Start/stop logic select • Configuration PUMP: Run time: hours.minutes Used to choose one of 3 Run/Stop command and Direction of This parameter records the number of hours and minutes of rotation management modes.
  • Page 56 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • All configurations except configuration PUMP: ADIO3 • All configurations except configuration PUMP: Jog feature reference This parameter is used to assign the ADIO3 function quickly Operating speed when the jog input has been selected (see 50).
  • Page 57 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING • All configurations except configuration PUMP: Deceleration ramp mode select Fst: Deceleration ramp imposed. If the deceleration ramp which has been set is too fast in relation to the inertia of the load, the DC bus voltage exceeds its maximum value and the drive switches to overvoltage trip "OU".
  • Page 58 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING dC-O ( ): Stop by DC injection braking, and elimination at zero speed. • All configurations except configuration PUMP: Stop The drive decelerates the motor by setting a low frequency...
  • Page 59 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING : Motor rated frequency • All configurations except configuration PUMP: Mains This is the point at which motor operation changes from loss mode constant torque to constant power.
  • Page 60 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING : Parameter cloning : Selection of load display Disable the drive (terminal SDI2 open). This parameter is used to obtain an indication of the load or the total current on the display.
  • Page 61: Commissioning For Brake Control

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive COMMISSIONING 4.5 - Commissioning for brake control 4.5.1 - Introduction To control an electromechanical brake from an AC single-phase source, use the optional PX-Brake Contactor (or PX-Brake Contactor Secure if the secure disable input function is also used for the application).
  • Page 62: Trips - Diagnostics

    • The user must not attempt to repair the drive himself, nor perform diagnostics other than those listed in this section. If the drive malfunctions, it should be returned to LEROY-SOMER via your usual contact. The PROXIDRIVE display gives a certain amount of information which simplifies the diagnostic process. This information is broken down into 2 categories:...
  • Page 63 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive TRIPS - DIAGNOSTICS Trip code No. Reason for trip Solution • Read the battery value in 4.19 It.AC Motor overload i x t • Check that the motor is not overloaded •...
  • Page 64 LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive TRIPS - DIAGNOSTICS Trip code No. Reason for trip Solution Secd Secure disable input trip • Give a stop command before enabling the drive Motor sensor trip •...
  • Page 65: Operating Extensions

    6.1.2.1 - General 6.1 - Add-on options The XPressKey option is used to save a copy of all the PROXIDRIVE parameters so that they can be duplicated very • It is imperative that these options (apart from simply in another drive.
  • Page 66: Px-Encoder

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive OPERATING EXTENSIONS 6.1.3 - PX-Encoder 6.1.3.2 - Connection of an incremental encoder 0V for the encoder power supply The PX-Encoder option can be used to manage the motor...
  • Page 67: Px-Brake Contactor

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive OPERATING EXTENSIONS 6.1.4 - PX-Brake Contactor 6.1.5 - PX-Secure Digital output connection 6.1.5.1 - General The PX-Secure option allows terminal SDI2 to be used as a secure disable input in accordance with safety standard 6.1.4.1 - General...
  • Page 68: Sm-Profibus Dp Module

    It integrates a 16-bit microprocessor, and its transmission speed can be as high as 12 Mbps. speed can be as high as 500 Kbps. The PROXIDRIVE powers the module internally. The module should be powered by the DeviceNet power supply.
  • Page 69: Sm-Canopen Module

    The SM-Ethernet module is used to communicate with an CANopen network. It integrates a 16-bit microprocessor and Ethernet network. its transmission speed can be as high as 1 Mbps. The PROXIDRIVE powers the module internally (current The PROXIDRIVE powers the module internally. consumption 280 mA). • Connection •...
  • Page 70: Parameter-Setting Options

    - printing of a complete file or differences compared to the factory setting - supervision - representation of parameters in table or graphic form. Optional resistor To connect the PC to the PROXIDRIVE, use the CT Comms Cable.
  • Page 71: Electrical Characteristics

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive OPERATING EXTENSIONS 6.3.3 - Electrical characteristics When using an optional braking resistor, the internal resistor must be disconnected. This can easily be done by removing •...
  • Page 72: Mechanical Characteristics

    • PX-Brake Resistors Weight: 5kg/Protection: IP20 Fixings (mm) Dimensions (mm) Type Ø 11 RF-MD-2000-75 Weight: 2.5 kg max/Protection: IP66/Nema 4X Proxidrive (PX-N and PX-SET) Dimensions (mm) + PX-Brake Resistor Size Rating 1TL to 1.5TL 1.5T to 2.5T 2TL to 3.5TL 3.5T to 5.5T...
  • Page 73: Rfi Filter

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive OPERATING EXTENSIONS 6.4 - RFI filter 6.4.3 - Connection L1 L2 L3 Size 1 and 2 drives conform to the drive standard EN 61800- 3 since they have an RFI filter integrated internally.
  • Page 74: Px-Cabling Kit

    LEROY-SOMER INSTALLATION AND COMMISSIONING MANUAL 3739 en - 06.2007/e PROXIDRIVE IP66/Nema 4X variable speed drive OPERATING EXTENSIONS 6.5 - PX-Cabling kit 6.6 - PX-Disconnect The PX-Cabling Kit option consists of the elements below: - 2 x M20 EMC cable glands (metal)
  • Page 75: Maintenance

    There are very few maintenance and repair operations on V : AC voltmeter impedance > 1000 Ω/V. PROXIDRIVE drives to be performed by the user. Regular servicing operations and simple methods for checking that the drive is operating correctly are described below.