Z-WRG RONDO PLUS
End Assembly on the Room Side
4.b
In the heat exchanger
slide into the wall
5
Low-voltage connection between
Fan and circuit board
6
communication settings
on the DIP switch
Example:
1 Station = Master
3 Stationen = Slave
All stations have a uniform group setting of DIP switches 5-9.
1 Station = Master
1 Station = Slave
The master and the slave station of the DIP switch no. 5 is set to ON.
Note: The DIP switches 2,3 and 4 must be set to OFF; other settings are intended only for customer service!
4.c
Fan unit slide into the wall
5.a
6.a
Operating from 6 devices into two groups
Group 1 consists of four devices; Group 2 consists of two devices
DIP-Switch 1 on ON
set
DIP-Schalter 1 on OFF
set
DIP-Switch 1 on ON
set
DIP-Switch 1 on OFF
set
›
MOUNTING INSTRUCTION
DIP-Switch
ON
OFF
ON
OFF
ON
OFF
ON
OFF
4. Push the system unit into the wall
a) the coming of the circuit board plug
(bottom left of the room-side plus housing)
put down to make room for the insertion
to provide
b) First of the ceramic heat exchanger in
the tube insert (until just before the tube end)
c) then the fan unit until it stops
Slide to the heat exchanger.
The fan grille shows on room side.
5. Fan connection
a) The low-voltage fan (12V DC)
is via a quick plug connection
connected to the circuit board (Fig. 5.a)
b) from the circuit board coming
low-voltage Round cable in the right
cable notch on the housing Push
c) The devices are now in the factory
preset single-mode operation ready for use
6. Presetting units for group function
The devices are still disconnected from Voltage!
ON
OFF
define group
via DIP switch no. 5-9
define Master / Slave
via DIP-Switch
no.
1
ON = Master / OFF = Slave
Master / Slave
The data exchange between installed
V-WRG devices takes via the mains.
Other physical connections or
Control lines are not required.
About the setting function of the DIP switch "1"
is a station per group on "Master"
set (DIP switch # 1 ON).
As a control for setting the DIP switch
Master on the Master LED on the display lights
green. All other stations of this group
work as "slave" (DIP switch No.1 OFF).
Within each group observes a master
one or more slave stations (max. 13).
Setting group
Via the DIP switch no. 5-9, the
Group settings are defined.
All stations of the same group have
each have the same switch setting.
After setting the DIP switch
the RESET is a first on the master and to the
Slave stations required (see. Page 10).
Thus, each station being given at the first switch
-on operation assigned to a station number.
Attention:
All ventilation units in a group must
be connected to the same phase!
09