Autocall TrueAlert ES Installation Instructions Manual

Addressable ceiling mount visual indoor notification appliances

Advertisement

Quick Links

TrueAlert ES Addressable Ceiling Mount Visual Indoor Notification Appliances Installation
Cautions, warnings, and regulatory information
Important: When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate atten-
tion of all occupants.
SAFETY: Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions
may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical
hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance Circuit is disconnected at the control
panel before installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances
(such as visible strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH
EXPOSED CIRCUITRY.
LOCATION REFERENCE: Location and quantity of appliances required must conform to the applicable local standards and guidelines (the National
Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes,
etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These notification appliances are not intended for installation within
hazardous locations as defined by the National Electrical Code (NEC) or NFPA.
UL Listed TrueAlert ES indoor product identification reference
Type
TrueAlert ES Ceiling Mount Visible
Only (VO) Appliance
Kit Contents
Not Included
Note: For information about appliance testing, see TrueAlert ES Addressable Appliances Troubleshooting Guide (579-1049AC).
Mounting instructions
1.
Select the correct location and install the electrical box using screws suitable for the mounting surface.
2.
Connect the building wires to the terminal block on the rear of the appliance. See
3.
Use the hardware provided to secure the appliance to the electrical box. Installing the appliance using a single gang electrical box requires a
49VO-APCS adapter plate. You can mount the adapter plate in two orientations, see
4.
Set the appliance settings. See
5.
Attach the cover to the appliance.
Models
Components:
A49VO-APPLC
A49VO-APPLC-BA
A49VOH-APPLC
A49VOH-APPLC-BA
A49VOH-APPLCA
A49VOH-APPLCA-BA
A49VOH-APPLCB
A49VOH-APPLCB-BA
Accessories:
49VO-APCS
Covers:
A49VOC-CRALT
A49VOC-CRBF
A49VOC-CRFEU
A49VOC-CRF
A49VOC-CRS
Appliance x1, with 8-32 1 in. mounting screws x 2.
Order a cover separately for each appliance.
Electrical box, 1.5 in. (3.81 cm) minimum depth required, 4 in. (10.16 cm) square or single gang with an adapter
plate.
49VO-APCS adapter plate for use with the single gang electrical box, with 4-40 screws x2, and 6-32 screws x 2.
Setting the address DIP
switch.
Cover colors
A49VOC-CWALT
• Red
A49VOC-CWBF
• White
A49VOC-CWFEU
• Black
A49VOC-CWF
A49VOC-CWS
A49VOC-CK
A49VOC-CRBAF
A49VOC-CRBCF
A49VOC-CWBAF
A49VOC-CWBCF
A49VOC-CRBAA
A49VOC-CWBAA
Wiring
instructions.
Wiring
instructions.
Instructions
Operation
These appliances provide a visible
only (VO) warning of an alarm
condition when activated from the
control panel of a compatible UL/
ULC Listed, Autocall Fire Alarm
System. Consult Autocall Fire
Alarm panel documentation for
compatibility information.
VO models '49VOH' have Hi
intensity strobes; models '49VO'
have standard range strobes.
579-1227AC Rev D
*05791227ACD*

Advertisement

loading
Need help?

Need help?

Do you have a question about the TrueAlert ES and is the answer not in the manual?

Questions and answers

Summary of Contents for Autocall TrueAlert ES

  • Page 1 49VO-APCS adapter plate for use with the single gang electrical box, with 4-40 screws x2, and 6-32 screws x 2. Note: For information about appliance testing, see TrueAlert ES Addressable Appliances Troubleshooting Guide (579-1049AC). Mounting instructions Select the correct location and install the electrical box using screws suitable for the mounting surface.
  • Page 2: Wiring Instructions

    TrueAlert ES Addressable Ceiling Mount Visual Indoor Notification Appliances Installation Instructions Figure 1: Mounting to the 4 inch square electrical box Figure 2: Mounting to the single gang electrical box Wiring instructions Warning: Ensure that all power is disconnected before starting the installation At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the assembly.
  • Page 3 Setting the address DIP switch Each addressable TrueAlert ES IDNAC notification appliance has a unique address that is set using an eight-position DIP switch (ADDR1). Assign up to 127 unique addresses to an SLC, but the total appliance loading available may be less due to appliance current requirements. For legacy fire panel models, Autocall 4009T and 4100/TPS, only addresses 1 to 63 are available.
  • Page 4 TrueAlert ES Addressable Ceiling Mount Visual Indoor Notification Appliances Installation Instructions Setting the strobe candela setting The jumpers are factory set to FACP. Use this setting when programming the candela setting at the 4100ES FACP. The candela setting is visible through the slot on the side of the appliance.
  • Page 5: Appliance Specifications

    49VO: also Special Application17-31 VDC For connection to legacy fire panel models, Autocall 4009T and 4100/TPS. High candela (49VOH) appliances are not compatible with Autocall 4009T and TPS; see fire panel compatibility charts for more information. Temperature Range 32 °F to 120 °F (0 °C to 49 °C) Humidity range 10 % to 93 %, non-condensing at 104 °F (40 °C)
  • Page 6 © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Autocall product supplier for the latest status. Listings and approvals under Tyco Fire & Security GmbH, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).