Samsung AC MXADKH Series Installation Manual page 24

Table of Contents

Advertisement

Installation Procedure
Key
Push type
1st
Heating test mode
K1
Short
2nd
Defrost test mode
3rd
1st
Cooling test
2nd
Inverter check
K2
Short
3rd
Pump down
4th
Reset Release Eco
K3
Short
1st
 Defrost test mode
Condition 1: The outdoor temperature is under 10°C
Condition 2: All the temperature conditions should meet
the defrost conditions
4 After 12 minutes of stationary condition check each
indoor unit air treatment:
• Cooling mode (indoor unit check) → Inlet air temp.
- Outlet air temp.: From 10°C to 12°C
• Heating mode (indoor unit check) → Outlet air
temp. - Inlet air temp.: From 11°C to 14°C
• In heating mode, the indoor fan motor can remain
off to avoid cold air blown into air-conditioned
space.
5 How to reset the power supply of the outdoor unit
and deactivate the eco mode (standby mode):
• Press K3 button over 1 sec to reset the power
supply of the outdoor unit and deactivate the eco
mode (standby mode).
 Eco mode : Standby for minimizing power onsumption
6 View mode: When the K4 switch is pressed, you can
see information about our system state as below.
24
English
Display
Mode
SEG
SEG
SEG
1
2
3
Stop
Stop
mode
K1
K2
K3
K4
SEG
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents