INSTRUCTION MANUAL
NT538 ETH
1MN0122 REV. 0
operates with ISO9001 certified quality system
TECSYSTEM S.r.l.
20094 Corsico (MI)
Tel.: +39-024581861
Fax: +39-0248600783
http://www.tecsystem.it
R.1.7 01/08/19
ENGLISH
"Translations of the original instructions"

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NT538 ETH and is the answer not in the manual?

Questions and answers

Summary of Contents for TECSYSTEM NT538 ETH

  • Page 1 INSTRUCTION MANUAL NT538 ETH 1MN0122 REV. 0 operates with ISO9001 certified quality system TECSYSTEM S.r.l. 20094 Corsico (MI) Tel.: +39-024581861 Fax: +39-0248600783 http://www.tecsystem.it R.1.7 01/08/19 ENGLISH “Translations of the original instructions”...
  • Page 2: Table Of Contents

    INTRODUCTION First of all we wish to thank you for choosing to use a TECSYSTEM product and recommend you read this instruction manual carefully: You will understand the use of the equipment and therefore be able to take advantage of all its functions.
  • Page 3 10) FAIL SAFE FUNCTION 11) Pt100 EXTENSION CABLE TECHNICAL ………………………………….. SPECIFICATIONS — ………………………………….. 12) FCD FUNCTION ………………………………….. 13) WARRANTY CONDITIONS — ………………………………….. 14) TROUBLESHOOTING — ………………………………….. 15) EQUIPMENT DISPOSAL ………………………………….. 16) USEFUL CONTACTS — ………………………………….. 17) UL SPECIFICATION AND RATINGS NT538 ETH...
  • Page 4: Safety Requirements

    POWER SUPPLY The NT538 ETH can be supplied from 85 to 260 Vac-Vdc, irrespectively of polarity in Vdc. Before use, ensure that the power cable is not damaged, knotted or pinched. Do not tamper with the power cable. Never disconnect the unit by pulling the cable, avoid touching the clamps.
  • Page 5: Accessories

    2 Pt100 sensor terminal 12 poles pitch 3.81 Code: 2PL0430 - Screws tightening torque 0.25Nm ATTENTION: always install the device using the terminals included in the pack. The use of terminals other than those included with the control unit might cause malfunctions. NT538 ETH...
  • Page 6: Technical Specifications

    NT538 ETH TECHNICAL SPECIFICATIONS POWER SUPPLY 85-260 Vac-Vdc Supply rated values 50/60HZ ● Vdc with reversible polarities INPUTS ● 8 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²) ● Connections on removable terminal strips ● Input channels protected against electromagnetic interference Cable compensation for thermistors 500m (1mm²)
  • Page 7 TECHNICAL SPECIFICATIONS NT538 ETH ● Housing NORYL 94 _V0 ● Absorption 7,5VA ● Digital linearity of sensor signal ● Self-diagnostic circuit Protection treatment of the electronic part Option DISPLAY AND DATA MANAGEMENT ● 2x13mm displays with 3 digits to display temperatures, messages and channels ●...
  • Page 8: Front Panel

    FAN 1 (yellow) LED T-max mode selection (red) LED FAN 2 (yellow) LED Man mode selection (yellow) LED Display mode selection key Auto mode selection (green) LED Fixing block Scan mode selection (yellow) LED UP key Fixing block DOWN key NT538 ETH...
  • Page 9: Display

    We suggest carrying out the control unit LED test regularly. For this operation, press the TEST key briefly; all the displays turn on for 2 seconds. If one of the LEDS does not work, please return the control unit to TECSYSTEM for repair. ALARM RELAY TEST This function allows you to carry out a test of the relay operation without having to use further devices.
  • Page 10: Mounting

    Drill a 92 x 92 mm hole in the panel sheet. 1MN0007 REV. 0 Control unit Panel hole dimensions (+0.8mm tolerance) Identification label Fix the unit securely with the blocks supplied. 1MN0008 REV. 0 Control unit Fixing screw Fixing block Cross-head screwdriver #1X100mm NT538 ETH...
  • Page 11: Electrical Connections

    ELECTRICAL CONNECTIONS NT538 ETH Pt100 sensors (white-red-red) Relays (FAN2-FAN1-ALARM-TRIP-FAULT) Supply 85-260Vac-dc 50/60Hz. RJ45 Ethernet output, Link-Activity LED, see indication on page 30. Note: relay contact image in non-alarm condition, with the exception of the FAULT relay that switches: contacts 11- 12 open (NO) contacts 11-12 closed (NC) fault condition identification.
  • Page 12: Power Supply

    POWER SUPPLY The NT538 ETH control unit can be supplied by 85 to 260 Vac-Vdc, 50/60 Hz irrespectively of polarity in Vdc (terminals 40-42). This is obtained thanks to the use of a tested power supply unit, newly designed and manufactured, that frees installers from worrying about the correct Vac and Vdc supply.
  • Page 13: Programming

    PROGRAMMING NT538 ETH STEP PRESS EFFECT PRESS NOTES Keep the PRG key pressed until the display shows PRG Select PRG SET for entering in the programming mode or PRG 1 default value PRG 1 to restore the default programmed value.
  • Page 14: Programming Notes

    We recommend you check the unit's programming before starting the device. The default parameters set by TECSYSTEM might not match your requirements. Programming the device is the end user's responsibility, the settings of the alarm thresholds and the enabling of the functions described in this manual must be checked (by a specialized engineer) according to the application and features of the system the control unit is installed on.
  • Page 15: Temperature Sensors

    / electrical fault of the Pt100 sensors c) damage to the Pt100 inputs of the control unit. TECSYSTEM S.r.l. has designed its own special cable to transfer the measurement signals, CEI-compliant, with all the protection requirements provided for: model CT-ES NOTE: the use of cables not complying with the above might cause reading anomalies.
  • Page 16: Temperature Sensor Diagnostics

    VOTING (see below) or FCD (see page 31) according to the conditions of the system. CAL message display: it appears when damage is found in the measurement circuit. The temperature values displayed might be incorrect. Return the control unit to TECSYSTEM for repairs. VOTING FUNCTION The voting function is derived from the concept of redundancy which consists of the duplication of components of a system with the intention of increasing reliability.
  • Page 17: Programmed Data Diagnostics

    (programmed parameter display) and modified in PRG (programming) mode. COOLING FAN CONTROL The unit NT538 ETH has two contacts FAN (FAN1 and FAN2), if properly programmed, can control ON-OFF of fans for cooling system checked. The high flexibility of the NT538 ETH allows you to select, for each channel, an operation mode for contact management of FAN1 and FAN2.
  • Page 18: Ethernet Modbus Tcp Output

    The ETH module is always in slave mode. The NT538 ETH control unit is in communication with the network only when it is in temperature reading mode, while it is inactive when in the following modes: display, programming and relay test.
  • Page 19: Notes For Remote Programming

    If WRITE data must always respect the rule T_trip> T_alarm and FAN_ON> FAN_OFF. In case you try to set these thresholds incorrectly, the control unit NT538 ETH will not proceed with the programming and storage of data, therefore in subsequent readings will read the data from the previous schedule.
  • Page 20: Illegal Data

    Vers. Fw – MSD(ASCII) Space (20H) Vers. Fw – LSD(ASCII) Vers. Fw - 2° Digit (ASCII) Channels qty (2*ASCII) Options (see note) Options (see note) Wrong datum received R-see tab. Info various causes R-see tab Commands W-see tab. NT538 ETH...
  • Page 21 1° to÷ 240° 2’compl. sign Fan_1 OFF 1°C ÷ 200°C (*) 1° to÷ 240° 2’compl. sign Fan_2 ON 1°C ÷ 200°C (*) 1° to÷ 240° 2’compl. sign Fan_2 OFF 1°C ÷ 200°C(*) (*) for version –40°C ÷ +200°C NT538 ETH...
  • Page 22 1°C÷200°C (*) –10°C ÷ 240°C 2’compl. sign 2’compl. Ch6 temper. –48°C÷200°C (*) 0°C ÷ 240°C 2’compl. sign 2’compl. Ch6 max temperat. 0°C÷200°C (*) 2’compl. Ch6 temper. 1°C ÷ 240°C 2’compl. sign As (AL) alarm set point 1°C÷200°C (*) NT538 ETH...
  • Page 23 See Note CHx Ch2 Setting See Note CHx Ch3 Setting See Note CHx Ch4 Setting See Note CHx Ch5 Setting See Note CHx Ch6 Setting See Note CHx Ch7 Setting See Note CHx Ch8 Setting See Note CHx NT538 ETH...
  • Page 24 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 FAN2 FAN1 CAN_enabl CHn STATUS BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 BIT 7 TRIP ALARM FAN_2 FAN_1 NT538 ETH...
  • Page 25 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 PT ERROR FCD Fault CPU SETTING BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 Failsafe Failsafe Failsafe trip fault alarm NT538 ETH...
  • Page 26: Ethernet Module Parameter Programming

    X Windows Vista, 7, 8. ETH0 CONNECTIONS Using an Ethernet cable, connect the RJ45 ETH0 of the NT538 ETH control unit to the ethernet card of a PC. TELNET ENABLING Use the Telnet program to set the Ethernet IP parameters.
  • Page 27: Telnet Screen

    13) Enter: OPEN 14) Press ENTER 192.168.10.120 9999 15) Enter: 16) Press ENTER 17) Enter the Password: TECS 18) Press ENTER Note: In this screen we have the MAC address and the software version of the ETH port available. NT538 ETH...
  • Page 28: Ip Parameter Programming Menu

    IMPORTANT WARNING For the device to work correctly, we advise you not to access or modify menus 2-3-4-7. The modification of the values in the stated menus might cause communication anomalies with the loss of the Ethernet IP communication. NT538 ETH...
  • Page 29 3) Enter the new Netmask, press ENTER; if you wish to keep the set address press ENTER 4 times.  At the end of the operation, the system will ask if you wish to modify the Telnet Password: Enter: to modify the Telnet Password. not to modify the Telnet Password and go to the following step. NT538 ETH...
  • Page 30: Fail Safe Function

    FAIL SAFE FUNCTION The NT538 ETH has n.o selection (contact open) / n.c (normally closed contact) for ALARM, TRIP and FAULT relays, programming steps 26 to 31 page 14. The selection of the setting YES/NO introduces functions Fail Safe and No Fail Safe.
  • Page 31: Pt100 Extension Cable Technical Specifications

    FCD function from activating during motor start-up, or where the ΔT/sec. increase varies quickly. (*) The ΔT value shows the temperature range for each second. NOTE: you should not enable the FCD function with active VOTING. NT538 ETH...
  • Page 32: Warranty Conditions

    Returning used electrical devices: contact TECSYSTEM or your TECSYSTEM agent for information on the correct disposal of the devices. TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the correct and environmentally-friendly disposal of its devices.
  • Page 33: Useful Contacts

    External switch or circuit breaker 5 relay Output: 10A 250Vac-res COS=1 OUTPUTS RELAYS PORT Ethernet Suitable for use on a flat surface of a type 1 enclosure if back panel is provided with two short fixing screws tightening torque: 0.57Nm NT538 ETH...