ThermoPlus Air KACE Series Installation, Operation And Maintenance Manual

Water cooled, horizontal & vertical r410a

Advertisement

Quick Links

WATER COOLED AIR CONDITIONERS
HORIZONTAL & VERTICAL MODELS
INSTALLATION, OPERATION AND MAINTENANCE
SERIES
Warning
Mechanical Thermostat may affect Electronic
Control card in unit. Connect an electronic
Thermostat to unit.
Each air conditioner has been operated and checked out
prior to shipment. Failure to operate after installation
indicates damage in transit or improper installation.
INSPECTION
Check packaging during unloading. Note transit damage on
all copies of bill of lading. Inspect air conditioners for hidden
shipping damage after packaging is removed. Transit
damage claims must be filed promptly with Freight
Company by purchaser.
HANDLING
Always handle Vertical units upright and Horizontal
units flat on their base. Moving a vertical unit on its side,
placing a horizontal unit on end, or dropping it may damage
internal parts and displace oil from the compressor's
crankcase.
STORAGE
If job site storage is necessary, place the unit in a clean,
warm dry area. Follow instructions under Handling.
LOCATION
Note that units with different capacities may have identical
dimensions. Labels on unit packaging must be carefully
scrutinized and matched to job location. These units are not
approved for outdoor installation and therefore must be
installed inside the space being conditioned.
PLACEMENT
Install air conditioners in a level plane and locate unit
around the service panel to ensure that proper access is
available including that for filter removal.
¨
For Vertical Units: Install the air conditioner with a piece of
sound insulating material between unit and floor to avoid
possible transmission of noise into the building structure.
(rubber backed carpeting will suffice for vertical models).
For units installed in closets adjacent to conditioned space,
provide insulated return air ducting with at least one 90
elbow or provide a sound baffle between the return air grille
and unit filter.
1
R410A
KACE-009A
KACE-024A
KACE-048A
KACE-120A
KACE-012A
KACE-030A
KACE-060A
KACE-144A
Horizontal units are provided with isolation hanger
¨
support. See Fig. 2 for proper installation when the unit is
suspended.
LOCATION OF SUPPLY & RETURN CONNECTIONS
(SEE FIG. 1 & 2)
WIRING
All wiring should conform to the CEC and/or local code
requirements. Power disconnect shall be field provided (by
others). The wiring diagram is located on electrical box
cover on vertical models and on the back of the service
panel on horizontal models. Make certain the line voltage
and the 24 volt control circuit are properly identified and
wired in accordance with the unit wiring diagram.
¨
Water cooled air conditioners are classified as direct
(permanently) connected devices by the CEC. Air
conditioners must be properly grounded as per instructions
on the unit wiring diagram.
CONDENSATE DRAINAGE
Vertical Units: Ensure that the plastic drain tube is
connected to the bottom of the coil drain pan at one end
and the other end of the condensate drain tube should
extend through the left post on the front side of the unit, see
Fig. 1. Connect the drain through a trap to the condensate
drain system in conformance to local plumbing codes.
Slope the drain line for proper gravity flow of condensate
away from unit. The top of the trap and further connections
must be below the unit drain connection level.
Horizontal Units: The condensate drain tube should be
connected to the side of the unit, see Fig. 2. Follow the
above instructions (given for the vertical units) for proper
condensate draining.
WATER SUPPLY (UNIT CONNECTED ON OPEN WATER
CIRCUIT)
The source of water for air conditioner operation is the
responsibility of the owner and/or the installing contractor.
The air conditioner must not function without water, and
predetermined rates of flow (l/s or USGPM) must be
maintained for the unit to opera-te at rated capacity. Since
the water function is to absorb heat from the refrigerant, the
flow rate for each model varies with the entering water
o
temperature (EWT). A pressure-operated water valve is
installed for this reason inside the unit and SAE-13 calibra-
KACE-015A
KACE-036A
KACE-072A
KACE-018A
KACE-042A
KACE-096A

Advertisement

loading
Need help?

Need help?

Do you have a question about the KACE Series and is the answer not in the manual?

Questions and answers

Summary of Contents for ThermoPlus Air KACE Series

  • Page 1 WATER COOLED AIR CONDITIONERS HORIZONTAL & VERTICAL MODELS R410A INSTALLATION, OPERATION AND MAINTENANCE SERIES KACE-009A KACE-012A KACE-015A KACE-018A KACE-024A KACE-030A KACE-036A KACE-042A KACE-048A KACE-060A KACE-072A KACE-096A KACE-120A KACE-144A Horizontal units are provided with isolation hanger ¨ Warning support. See Fig. 2 for proper installation when the unit is Mechanical Thermostat may affect Electronic suspended.
  • Page 2 ted at the factory for a condensing pressure of 1400 kPa "gauge" (205 PSIG.). Piping size to and from unit must WATER CONNECTIONS If flexible hoses are used to make the water in-out match or exceed the inlet and outlet water connection connections to the unit, certain precautions must be taken sizes on the air conditioner.
  • Page 3 FIGURE 1 SUPPLY AIR BLOWER AND MOTOR ACCESS PANEL RETURN AIR ELECTRICAL ACCESS PANEL BLOWER ACCESS PANEL RIGHT SIDE POWER IN LEFT SIDE LOW VOLTAGE IN WATER OUT CONDENSATE WATER IN WATER REGULATING DRAIN TUBE ACCESS PANEL FRONT ELECTRICAL AND COMPRESSOR ACCESS PANEL...
  • Page 4 FIGURE 2 3/8 WASHER (BY OTHERS) 3/8-16 NUTS (DOUBLE) (BY OTHERS) 3/8-16 THREADED ROD (BY OTHERS) BLOWER AND MOTOR ACCESS PANEL Detail C CONDENSATE DRAIN CONNECTION RETURN AIR RIGHT SIDE ELECTRICAL ACCESS PANEL LOW VOLTAGE IN POWER IN SUPPLY AIR FRONT WATER OUT LEFT SIDE...
  • Page 5: Installation

    Connect the cable to the modular telephone jack on the back of the display. Screw the display to its sub-base here. Snap the front cover over the display. Data subject to change without notice. ThermoPlus Air, Inc. February 2007...
  • Page 6 Do not press at the same time. Data subject to change without notice. ThermoPlus Air, Inc. February 2007...
  • Page 7 . Note that “I/O Board address : bb” disappears. The screen Display address changed at right appears briefly, followed by the unit default screen. Default Screen HUMIDITY aaa / bbb % ROOM AIR ccc / ddd F xxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxx Data subject to change without notice. ThermoPlus Air, Inc. February 2007...
  • Page 8: Supervisaire ® Controller Interface

    This screen is the gateway to other screens used to set the internal clock (where used). See Startup - Pre-Startup Adjustments. This screen is the gateway to other screens used for service GO TO SERVICE MENU monitoring or modification. Data subject to change without notice. ThermoPlus Air, Inc. February 2007...
  • Page 9 (if any) ON. This will allow the compressor crankcase heater(s) to function. The crankcase heaters must be on continuously for at least 10 hours before the compressors are started. Data subject to change without notice. ThermoPlus Air, Inc. February 2007...