Contents General information .........1 Installation........... 14 Notice symbols ........1 Safety information........ 14 1.1.1 Instruction symbols.....1 Preconditions ........14 Important safety information ......1 Tightening torques of screw-type connections according to DIN 13....15 Personnel ..........2 Mounting feet ........15 Personal protective equipment....2 Avoid resonance frequencies ....
General information | General information Notice symbols Danger Direct hazard Failure to comply with this warning will lead directly to death or to serious injury. Warning Potential hazard Failure to comply with this warning may lead to death or serious injury. Caution Hazard with a low risk Failure to comply with this warning may lead to moderate injuries.
Note: The operator is responsible for ensuring that personnel are instructed and have understood the contents of the operating instructions. If something is unclear, please contact Systemair or its representative. Personal protective equipment Wear protective equipment during all work in the vicinity of the fan.
Delivery, transport, storage | ♦ Make sure that there is nobody under a suspended load. Delivery Each fan leaves our plant in an electrically and mechanically proper condition. We recommend transporting the fan to the installation site in the original packaging. Checking delivery ♦...
| Description Storage more than 12 months ♦ We recommend an inspection by the after-sales service of Systemair before commissioning. Test the motor windings: ♦ Measure the insulation resistance of each motor winding against grounding at 500 V DC. The insulation resistance must be >...
| Description 5.2.2 Types Table 3 Constructive features Type Constructive features As a default, the fans are provided in protection class IP55, ISO F. AXC-G Fans constructed as garage version. Arrangement of two fans in series, switched behind one another. The conveying direction can be reversed by switching the direction of rotation.
Description | 5.2.3 Dimensions 1/2 W Ø B x T ØDa Size Motor size B3/IEC Motor size B30/ Ø Di Ø Da Ø Tk Ø B [mm] (AXC/ [mm] [mm] [mm] [mm] AXR) 45° 71/80/90 80/90 45° 71/80/90 80/90 45° 71/80/90/100 80/90/100 45°...
Mounting foot Rubber anti-vibration mounts Spring anti-vibration mounts Suspension spring anti-vibration mounts Air operated damper Counter flange Outlet cowl Note: Some accessories are also available for jet fans and AXCBF, please check our online catalogue or contact Systemair. | 003...
Description | Description Jet fans 5.3.1 Description AJR/AJ8 • In B3 conventional motors, the motor bracket is made from galvanized steel sheet. B30 “pad mounted” motors are fitted in the housing via threaded rods or a welded motor support. • The fan conveys air in an axial direction from the intake side via the electric motor to the outlet side. •...
Description | 5.3.2.2 Dimensions Size A [mm] B [mm] C [mm] D [mm] E [mm] F [mm] H [mm] I [mm] 6xØK [mm] 1248 13.5 1140 1184 1220 1900 13.5 Description AXCBF Directly powered axial fan with motor outside the air flow. The fan can be run in permanent operation up to a conveying media temperature of 200°C.
| Description 5.4.2 Dimensions Size 250 — 500 Size 630 — 800 Size A [mm] ØB [mm] ØC [mm] ØD [mm] ØF [mm] ØH [mm] 4x90° 8x45° 8x45° 12x30° 12x30° 16x22.5° Intended use • The maximum admissible operating data on the name plate apply to an air density of 1.2 kg/3³ (sea level) and a maximum air humidity of 80%.
This Powered Smoke and Heat Control ventilator shall be installed as per the manufacturer's instruction. Installation and Operating Instructions are within the delivery. Systemair GmbH - Seehöferstraße 45 - 97944 Boxberg - Germany Table 6 Type key (-)(K), (B), (F) /10°*...
| Installation Table 7 AXCBF Type key AXCBF 500– 20° Axial fan bifurcated Nominal diameter of 3-phase motor 2– Blade angle International the fan pole efficiency Table 8 IV Type key 50– Temperature- Time Induction fan Thrust 50N Number of poles information (smoke extraction fan), see 5.1.5 Temperature types, page 5...
Mounting feet Depending on the kind of fan and the construction size, mounting feet are either included in the delivery or available as accessories. If you are not sure, check the online catalogue or contact Systemair. Avoid resonance frequencies Important Risk of damage to the fan due to resonance frequencies ♦...
♦ Screw the fittings with the correct tightening torques, see Table 9 Tightening torques according to DIN 13, page 15 ♦ If you are not sure, contact Systemair. Installation axial fans/AXCBF Installation is possible in any mounting position. From size 1250 and above, please contact Systemair if the mounting position should be different to horizontal or vertical. 7.7.1 Installation of the ventilation system 7.7.1.1 Preconditions...
Installation | 7.7.2 Distance from the wall/ceiling ♦ Ensure enough distance between the ceiling and the wall. • The duty point may not be reachable. • The fan may make noise. If the minimal distances are not possible for construction reasons, install a deflector in front of the fan in a way that en- sures a direct, smooth and constant flow of air.
Ensure that the air gap between the housing and the impeller is complied with. ♦ Check if the air gap complies with the table. ♦ Do not install the fan if the gap in the table below is not complied with. ♦ Contact Systemair. Table 11 Air gap AXC/AXR AXC/AXR (Standard...
Ensure that the air gap between the housing and the impeller is complied with. ♦ Check if the air gap complies with the table. ♦ Do not install the fan if the gap in the table below is not complied with. ♦ Contact Systemair. Table 12 Air gap AJR/AJ8 (Standard temperature)
Electrical connection | A — Position the fins to the specified angle and secure them with 4.2 x 13 self-drilling screws.. B — Use M4 x 12 self- locking screws to fasten the deflector to the fan. C— Fasten the deflector with an M6 x 40 screw, an M6 nut and a Ø6 serrated washer.
| Electrical connection Table 13 Motor protection Type Motor protection Thermal protection, Speed regulation standard AXC,-B,-D,-G,-P By customer Possible via frequency converter AXC (B),(F),(K) By customer- must be without (PTC optional) Possible via frequency converter— AXR (B),(F),(K) bypassed in case of fire must be bypassed in case of fire By customer Possible via frequency converter...
Electrical connection | 8.4.1 Connection diagrams 3–phase motor with optional thermal contacts or cold conductor. Dahlander motor with optional thermal contacts or cold conductor. Motor, 2 windings with optional thermal contacts or cold conductor. Frequency converter (if used) Risk from resonant frequencies when using frequency converter. ♦...
| Commissioning Commissioning of the frequency converter ♦ Install the fan and frequency converter as near as possible to one another. ♦ Use shielded cables. ♦ All components (fan, frequency converter and motor) must be grounded. ♦ We recommend using all-pole sinus filters. Operation of the frequency converter ♦...
Adjusting the blade angle If the working point of the fan has to be changed and it is necessary to adjust the blade angle, please contact Systemair! Operation 10.1 Safety information Warning: Hazard from electrical voltage or moving components.
Ambient temperature too Check, if the correct fan is used for your application high Note: For all other damage/defects, please contact Systemair. Defective fans must be completely replaced. 11.3 Maintenance Draw up maintenance plan ♦ Draw up a regular maintenance plan.
Fan unit in rare use (less than once a month) or in emergency operation Fan unit in use under normal conditions Note: The following sections contain suggestions from Systemair on the maintenance intervals. ♦ Shorten the intervals if the fan unit is used in a particularly dirty environment. 11.3.3...
♦ Remove all assembly residues and foreign bodies from the area around the fan unit. 11.5 Spare parts ♦ Use original spare parts from Systemair only! ♦ When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate.
Deinstallation/dismantling | ♦ The rotor is at a standstill. 12.3 Procedure Note: Keeping the fan clean extends its service life. ♦ Install a filter monitor. ♦ Do not use steel brushes or sharp-edged objects. ♦ Do not use a high-pressure cleaner (steam jet cleaner) under any circumstances. ♦...
Commissioning Report | Commissioning Report Description: Article no.: Manufacturing order no.: Installer Company: Contact person: Company address: Tel. no.: Email: Operator (Place of installation) Company: Contact person: Company address: Tel. no.: Email: Type of connection □ □ Directly to mains □...
Page 36
Please keep the completed commissioning report in a safe place. In the case of a warranty claim, this report can be requested by Systemair GmbH. This document can also be downloaded from our online catalogue. For technical questions, please contact the technical support division of Systemair GmbH (tel. +49 7930/9272 730). | 003...