Pump speed
min / max
30 / 64
Siemens
Building Technologies
6.6.5
Collector overtemp prot
Line no.
Operating line
3850
Collector overtemp prot
If there is a risk of overtemperature at the collector, storage tank charging is
continued to reduce the amount of excess heat. Charging stops when the storage
tank's safety temperature is reached.
T
Tkol
TSpSi
TSp
On
Off
TSpSi
Storage tank safety temperature
TSp
Storage tank temperature
TKolUe
Collector temperature for overtemperature protection
TSpmax
Maximum charging temperature
Tkol
Collector temp
On / Off
Collector pump
T
temperature
t
Time
6.6.6
Medium's evaporation temperature
Line no.
Operating line
3860
Evaporation heat carrier
If there is a risk of the heat carrying medium evaporating due to high collector
temperatures, the collector pump will be deactivated to prevent it from exceeding
certain temperature levels. This is a protective pump function.
6.6.7
Speed control
Line no.
Operating line
3870
Pump speed min
3871
Pump speed max
3872
Speed Xp
3873
Speed Tn
The solar pump motor speed is limited by a minimum and maximum permitted
speed.
Solar compact controller
The settings in detail
1°C
TSpMax
TKolUe
1°C
t
CE1U2396en
18.08.2010