OPERATORS/ INSTRUCTION MANUAL PARTS LIST Before installation or starting the Intellisys System Controller for the first time, this manual should be studied carefully to obtain a clear knowledge of the unit and or the duties to be performed while operating and maintaining the unit.
Page 3
This unit was purchased from ______________________________________________________ ______________________________________________________ ______________________________________________________ Ingersoll-Rand Company reserves the right to make changes or add improvements without notice and without incurring any obligation to make such changes or add such improvements to products sold previously. Customer Order No:______________________________________ Ingersoll-Rand Co.
TABLE OF CONTENTS 0.0 SAFETY AND WARNINGS 5.0 TROUBLE SHOOTING CHART 6.0 REFERENCE DRAWINGS 1.0 INTRODUCTION 6.1 ISC set point map 1.1 application 6.2 “compressor control” set points 1.2 features 6.3 “initial set up” set points 6.4 “pressure settings” set points 2.0 RECEIPT OF EQUIPMENT 6.5 “pressure control”...
The operator should use common sense and good work- Before you install this Intellisys System Controller (ISC) ing practices while operating and maintaining this unit. you should take the time to carefully read all the instruc- All applicable codes should be strictly adhered to.
1. The ISC can manage from 2 to 8 air compressors. 1.0 INTRODUCTION 2. Compressors can be either Intellisys or preIntellisys One Intellisys System Controller (ISC) can sequence (rotary) models. both rotary and reciprocating compressors. To do this, it must have software EPROM version 1.1 or higher.
2.0 RECEIPT OF EQUIPMENT When you receive the Intellisys System Controller (ISC) please inspect it closely. Any indication of careless han- dling by the carrier should be noted on the delivery receipt especially if the ISC will not be immediately unboxed.
3.0 INSTALLATION 3.1 ISC MOUNTING Before beginning Intellisys System Controller (ISC) 1. The ISC can be easily installed on any suitable sur- installation and system operation, the following require- face in the general vicinity of the air compressors. Refer ments and recommendations must be satisfied.
3.5 ISC COMMUNICATION WIRING 3.7 PRESSURE TRANSDUCER CALIBRATION 1. The ISC is connected to each compressor using the This should always be done after first installing the ISC, telephone type wire supplied in the ISC kit. Cut appropri- or after servicing the ISC or pressure transducer. ate lengths for each compressor and route the wires in grounded electrical conduit.
Page 11
• • SEQUENCE SEQUENCE UNIT 7 UNIT 3 SEQUENCER COMPRESSOR • • LOADED LOADED STATUS STATUS • • SEQUENCE SEQUENCE UNIT 8 UNIT 4 • LOADED • LOADED SEQUENCING SEQUENCING SEQUENCING SEQUENCING START STOP FIGURE 4.0-1 INTELLISYS SYSTEM CONTROLLER PANEL...
4.0 OPERATION 4.1.2 SEQUENCER STOP BUTTON Air system performance can be enhanced by carefully setting up the Intellisys System Controller (ISC). This UNLOADED SEQUENCER includes selecting operating parameters that customize STOP STOP the ISC for the specific air system to which it is attached.
4.1.5 SET BUTTON 4.1.9 COMPRESSOR UNIT STATUS LED’s There is a pair of status LED’s, “ Sequence” and “Loaded”, for each compressor under the control of the ISC. Each “Sequence” LED lights to indicate that com- pressor is in Sequence mode through the communica- tion channel to the ISC.
4.2 SETTING UP THE ISC (Continued) Step Action 5. Press the SET button to lock in any changed value and to move to the next set point within a set point Press the SET button once, observe the group. If a value has been changed, the display will flash currently selected language.
4.2.2 PRESSURE SET UP AND CONTROL 2. Each Setting is enabled by specifying its Target Pressure, Day of the Week and Time of Day, or it is dis- The ISC controls the loading and unloading of air com- abled by specifying it as “UNUSED” in place of selecting pressors for the purpose of maintaining a steady system a Target Pressure.
Page 16
PRESSURE CONTROL Step Action The ISC will maintain the Target Pressure by loading While not in any Set Point routine, press the compressors when the pressure is below the “lower SET button once and observe pressure limit”, which is defined as the Target Pressure “PRESSURE SET UP”...
If the system pressure should ever rise above the “maxi- mum pressure limit”, which is defined as 5 PSI above the Step Action “upper pressure limit”, the ISC will tell all compressors to unload at once. If the pressure then drops to the “upper pressure limit”...
Page 18
SEQUENCE SET UP RULES: Step Action 1. Compressors are numbered 1 through 8 with no gaps in the numbering. For example, if there are five compressors, While not in any Set Point routine, press they must be connected to communication channels 1 the SET button once and observe through 5.
4.2.4 COMPRESSOR CONTROL automatically by the ISC or manually by the operator. Automatic rotation occurs when the ISC is put in either Each compressor can be set to Local or Sequence con- TIMED Mode or EVENT Mode. Manual rotation occurs trol through the ISC.
Page 20
EVENT ROTATION MODE Step Action In the EVENT rotation mode, the ISC rotates from the While not in any Set Point routine, press currently running sequence to the sequence specified to the SET button once and observe be active at the moment an Event matches the present “PRESSURE SET UP”...
Page 21
6. In case two or more Events have the same Day of the Week and Time of Day entries, the lower numbered Event Step Action will have priority. Press SET once, observe something like 7. When Event Mode is selected to be active, the “1 A MON 6:45”.
Page 22
MANUAL ROTATION MODE In the MANUAL Rotation Mode, the ISC rotates from what- ever sequence is currently running, regardless of the cur- rent rotation mode, directly to the sequence designated M that is set up in the Manual mode Set Point. This occurs immediately upon exiting the Set Point routine after select- ing MANUAL Mode.
The following list outlines was in when stopped. what to do for each of five types of Ingersoll-Rand Intellisys compressors to enable them to give control to NOTE: When the ISC is stopped, each compressor the ISC.
4.5 COMPRESSOR STATUS 4.6 ALARMS As described in Section 4.1.9 there is a pair of front The “Alarm” LED on the ISC’s front panel will light for panel status LED’s “Sequence” and “Loaded”, for each any one of the following three reasons. compressor under the control of the ISC.
5.0 ISC TROUBLE SHOOTING CHART TROUBLE CAUSE AND/OR DISPLAY WHAT TO DO ISC POWER light is off. No message in display, no lights on. 1. Check fuse and wiring connections. 2. Check power source disconnect box. Bad system air pressure readings. “SENSOR FAILURE”...
The following are instructions to attach 6 position modu- 5. Insert modular plug connector - TAB UP - into die set. lar plugs to communication cable. LOCKING TAB MUST SNAP INTO CAVITY. 1. Trim cable end flush. 6. Squeeze tool handles together until movable anvil is completely bottomed.