Building Air Conditioning Control System
System Remote Controller
Schedule Timer
ON/OFF Remote Controller
Installation Manual
This manual describes only the installation of the System Controller, capable of managing and controlling air conditioners, and LOSSNAY. Refer to
the installation manuals enclosed with the air conditioner for details on wiring and installing the air conditioner unit.
1 Safety Precautions
To ensure safety, always read
1 Safety Precautions
• The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:
This symbol denotes what could lead to serious injury or death if you misuse above remote controllers.
WARNING
This symbol denotes what could lead to a personal injury or damage to your property if you misuse above remote controllers.
CAUTION
• After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.
When someone moves, repairs or uses above remote controllers, make sure that this manual is forwarded to the final user.
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric
shock or fire.
Install in a place which is strong enough to withstand the weight
of above remote controllers.
Any lack of strength may cause above remote controllers to fall down,
resulting in personal injury.
Firmly connect the wiring using the specified cables. Carefully
check that the cables do not exert any force on the terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair above remote controllers.
Any deficiency caused by your modification or repair may result in an
electric shock or fire.
Consult with your dealer about repairs.
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of above remote
controllers may cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and
sulfuric gas may deteriorate the performance significantly or give
damage to the component parts.
When installing the remote controller in a hospital or communication facility, take ample countermeasures against noise.
Inverters, emergency power supply generators, high-frequency medical equipment, and wireless communication equipment can cause the remote
controller to malfunction or to fail. Radiation from the remote controller may effect communication equipment and prevent medical operations on
the human body or interfere with image transmission and cause noise.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Completely seal the wire lead-in port with putty.
Any dew, moisture, insects entering the unit may cause an electric
shock or a malfunction.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not install in any place at a temperature of more than 40
;
less than 0
or exposed to direct sunlight.
Doing so may cause deformation or a malfunction.
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew. Doing so may
cause an electric shock or a malfunction.
PAC-SF44SRA
PAC-YT34STA
PAC-YT40ANRA
below before starting installation.
WARNING
Ensure that installation work is done correctly following this
installation manual.
Any deficiency caused by installation may result in an electric shock or
fire.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation may
result in an electric shock or fire.
Do not move and re-install above remote controllers yourself.
Any deficiency caused by installation may result in an electric shock or
fire.
Ask your distributor or special vendor for moving and installation.
CAUTION
Do not install in any place where acidic or alkaline solution or
special spray are often used.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not touch any PCB (Printed Circuit Board) with your hands or
with tools. Do not allow dust to collect on the PCB.
Doing so may cause fire or an electric shock.
Do not remove the insulation sheet on the PCB.
Doing so may cause an electric shock.
Do not touch any control button with your wet hands.
Doing so may cause an electric shock or a malfunction.
;
or
Do not press any control button using a sharp object.
Doing so may cause an electric shock or a malfunction.
Never apply 100VAC or 200VAC. The maximum voltage that can
be applied on this unit is 30VDC.
Applying an excessive voltage may cause damage, igniting or fires.


Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PAC-SF44SRA

  • Page 1 Building Air Conditioning Control System System Remote Controller PAC-SF44SRA Schedule Timer PAC-YT34STA ON/OFF Remote Controller PAC-YT40ANRA Installation Manual This manual describes only the installation of the System Controller, capable of managing and controlling air conditioners, and LOSSNAY. Refer to the installation manuals enclosed with the air conditioner for details on wiring and installing the air conditioner unit.
  • Page 2: System Configurations

    Schedule timer [105] [106] [107] [108] remote controller remote controller PAC-YT34STA PAC-YT40ANRA PAC-SF44SRA Group 7 [201] [202] [203] Group 4 Group 5 Group 6 * Number of units that can be supplied with power supply unit (For above system) Power supply unit Model: PAC-SC34KUA 1×1/2...
  • Page 3 "slaves". The "master/slave" functions of the system controller used together are as follows. The functions have a priority in order of G50A (MJ-103MTRA) > PAC-SF44SRA > PAC-YT34STA > PAC-YT40ANRA > PAC-SC30GRA > LMAP02-E. System remote controller (44SRA)/Schedule timer (34STA)
  • Page 4 4 Using the External Input and Output When using the external input and output functions, use the external input and output cables provided with the remote controller. (5 wire cable for input and 4 wire cable for output are provided.) 1.
  • Page 5: Setting The Functions

    2. External signal output function (1) External output In the case when one or more air conditioner units are "ON", and an error is occurring on one or more air conditioner units, a signal indicating that an error is occurring is output. (2) External output specification Lead wires (4 wires, with black tube) Detail of each terminal...
  • Page 6 (3) List of switch settings System remote controller (SF44SRA) Default Name Switch NO. Function Setting method setting Master SC setting To set system controller as master System controller master/slave SW3-1 setting changeover Slave SC setting To set system controller as slave External input signal function Input state Do not use external inputs...
  • Page 7: How To Install

    Extra space around 6 How To Install remote controller External size of remote controller (1) Choose a location in which to install the system remote controller (electric box) in accordance with the following requirements: The space as shown in the diagram at right is required whether the controller is installed on the wall or in the electric box.
  • Page 8: Initial Settings

    (4) Connect the remote controller cord to the terminal block on the lower case. Install wiring correctly in accordance with the diagram below. No polarity (Terminal block) Remote controller cord procured locally. Do not use crimp terminals to connect to remote controller terminal blocks. It connects to the circuit board and CAUTION will cause trouble.
  • Page 9: Précautions De Sécurité

    PAC-SF44SRA PAC-YT34STA PAC-YT40ANRA Ce manuel d'installation décrit uniquement la procédure d'installation du contrôleur de système capable de gérer et de contrôler des climatiseurs ainsi que des unités LOSSNAY. Veuillez consulter les modes d'emploi fournis avec le climatiseur pour plus de détails sur le câblage et l'installation proprement dite du climatiseur Afin de garantir votre sécurité, veuillez toujours lire:...
  • Page 10: Configurations Du Système

    Groupe 1 Groupe 2 Groupe 3 SW2-1[ON] CN41 [052] 2 3 4 5 6 7 8 9 10 [005] [006] [007] [008] [105] [106] [107] [108] PAC-YT40ANRA PAC-YT34STA PAC-SF44SRA Groupe 7 [201] [202] [203] Groupe 4 Groupe 5 Groupe 6...
  • Page 11 "esclaves" par les contrôleurs ayant le moins de fonctions. Les fonctions "maître/esclave" du con- trôleur système utilisées ensemble sont: L'ordre des priorités est comme ceci: G50A (MJ-103MTRA) > PAC-SF44SRA > PAC-YT34STA > PAC-YT40ANRA > PAC-SC30GRA > LMAP02-E.
  • Page 12 4 Utilisation de l'entrée et de la sortie externe Veuillez utilisez le câble d'entrée et de sortie externe fourni avec le contrôleur externe si vous voulez utiliser les fonctions d'entrée et de sortie externe. (Un câble à 5 fils pour l'entrée ainsi qu'un câble à 4 fils pour la sortie sont fournis avec l'appareil.) 1.
  • Page 13: Réglage Des Fonctions

    2. Fonction de signal externe en sortie (1) Signal externe en sortie Un signal indiquant la présence d'une erreur sera émis en sortie lorsqu'un ou plusieurs climatiseurs marchent ensemble sur "ON " et qu'une erreur se produit sur un d'entre eux. (2) Caractéristiques du signal externe en sortie (3) Exemple de circuit recommandé...
  • Page 14 (3) Liste des réglages des commutateurs...
  • Page 15: Procédure D'installation

    6 Procédure d'installation (1) Choisissez un emplacement adéquat pour l'installation du contrôleur système à distance (boîtier électrique) en suivant les consignes ci-dessous: L'espace requis pour l'installation du contrôleur au mur, ou dans un boîtier électrique est indiqué sur le schéma ci-contre. Procurez-vous les pièces suivantes.
  • Page 16: Configuration Initiale

    (4) Connectez le cordon du contrôleur à distance au bloc des bornes du boîtier inférieur. Effectuez le câblage en suivant les instructions ci-dessous. Pas de polarité Le cordon du contrôleur à distance fourni localement. (Bloc de bornes) (5) Trou de passage des câbles pour installation au mur (pour un câblage exposé) Cordon du contrôleur à...