    Contents General Information 1.1 Overview 1.2 Applicable Products 1.3 Warnings 2. Installation 2.1 Installation safety 2.2 Installation Condition 2.2.1 Climate condition 2.2.2 Site selection 2.2.3 Tilt angle selection 2.3 Mechanical Installation introduction 2.3.1 Fixation with screws 2.3.2 Fixation with clamps at long sides of frames 2.3.3 Fixation with clamps at short sides of frames 2.3.4 Fixation with clamps at the long &...
  • Page 3: General Information

    [键入文字] 1. General Information 1.1 Overview Thanks for choosing Jinko Solar PV modules. In order to ensure the PV modules to be installed correctly, please read the following operation instructions carefully before modules to be installed and used. Please remember that the products would generate electricity, thus certain safety measures need to be taken to avoid danger.
  • Page 4: Warnings

    JKMxxxP-48/JKMxxxPP-48/JKMxxxP-48-J/JKMxxxPP-48-J/JKMxxxP-48(Plus)/JKM xxxPP-48(Plus)/JKMSxxxP-48/JKMSxxxP-48-J/JKMSxxxP-48Plus) (XXX=170~225, in increment of 5) With 5” mono c-Si: JKMxxxM-72/JKMxxxM-72-J/JKMxxxM-72B/JKMSxxxM-72/JKMSxxxM-72-J (XXX=160~215, in increment of 5) JKMxxxM-96/JKMxxxM-96-J/JKMxxxM-96B/JKMSxxxM-96/JKMSxxxM-96-J (XXX=210~285, in increment of 5) Notes: *PP: the EAGLE Series module ** (Plus):the eagle+ Series module ***JKMS: the smart module ****B: module with black back sheet Make sure the array of modules installed within the Maximum permitted system voltage and the rating current and voltage of the sub-equipments such as regulators and inverters.
  • Page 5 · Front protective glass is utilized on module. Broken solar module glass is an electrical safety hazard (may cause electric shock and fire). These modules cannot be repaired and should be replaced immediately.  Electric Shock and Burn Hazard  This photovoltaic module produces Electricity when exposed to the sun Warning...
  • Page 6  Do not remove any part installed by Jinko Solar or disassemble the module.  All instructions should be read and understood before attempting to install, wire, operate and maintain the module.  Please don‟t lift up PV modules using the attached cables or the junction box.
  • Page 7: Installation

    2. Installation 2.1 Installation safety  ways wear protective head gear, insulating gloves and safety shoes (with rubber soles).  Keep the PV module packed in the carton until installation.  Do not touch the PV module unnecessarily during installation. The glass surface and the frame may be hot.
  • Page 8: Installation Condition

    2.2.2 Site selection In most applications, Jinko solar PV modules should be installed in a location where they will receive maximum sunlight throughout the year. In the Northern Hemisphere, the module should typically face south, and in the Southern Hemisphere, the modules should typically face north.
  • Page 9: Tilt Angle Selection

    generate hydrogen gas when charging, which can be explosive. Do not light matches or create sparks near the battery bank. When a battery is installed outdoors, it should be placed in an insulated and ventilated battery case specifically designed for the purpose.
  • Page 10: Fixation With Screws

    Note: ﹡ All installation methods herein are only for reference, and Jinko solar will not provide related mounting components, the system installer or trained professional personnel must be responsible for the PV system‟s design, installation, and mechanical load calculation and security of the system.
  • Page 11 Figure 2: PV module installed with Screw fitting method Module type Cell type Cell Pmax Dimensions(mm) JKMXXXM-72 Module:1580*808 JKMXXXM-72-J 5 inch Mono 6*12 160~215Wp Frame: 35*25 & 35*35 & 40*30 & 40*35 JKMXXXM-72B & 45*35 & 50*35 JKMXXXM-96 Module:1575*1082 JKMXXXM-96-J 5 inch Mono 8*12 210~285Wp Frame: 40*30 &...
  • Page 12 JKMXXXM-60 Module:1650*992 JKMXXXM-60-J 6 inch Mono 6*10 210~280Wp Frame:40*30 & 40*35 & 45*35 & 50*35 JKMxxxM-60-(Plus) & 35*35 JKMXXXM-60B JKMXXXP-72 JKMXXXP-72-J JKMXXXPP-72 Module:1956*992 6 inch Poly 6*12 250~340Wp JKMXXXPP-72-J Frame: 40*30 & 40*35 & 50*35 JKMSxxxP-72(Plus) JKMXXXP-72B JKMXXXM-72 JKMXXXM-72-J Module:1956*992 6 inch Mono 6*12 250~335Wp JKMxxxM-72(Plus)
  • Page 13: Fixation With Clamps At Long Sides Of Frames

    2.3.2 Fixation with clamps at long sides of frames The applicable Products please refer to Table 2, and only allow using clamps at long side of frames. The module clamps should not come into contact with the front glass and must not deform the frame.
  • Page 14 Figure 3: PV module installed at long side with Clamp fitting method Dimension(mm) Cell Cell Pmax Module type type quantity (Wp) Frame 1580*804 300 400 30*20 & 35*25 & 40*20 JKMSXXXM-72 5 inch 30*20 & 35*25 & 35*35 6*12 160~215 JKMSXXXM-72-J Mono 1580*808...
  • Page 15 JKMXXXP-60 35*25 & 40*30 & JKMXXXP-60-J 1650*992 40*20 & 40*35 & JKMXXXPP-60 45*35 & 50*35 6 inch JKMXXXPP-60-J 6*10 210~280 280 420 Poly JKMxxxP-60(Plus) 1650*990 40*20 & 40*35 JKMxxxPP-60(Plus) JKMXXXP-60B JKMXXXM-60 35*25 & 40*30 & JKMXXXM-60-J 6 inch 6*10 210~280 1650*992 280 420 40*20 &...
  • Page 16 2) Light PV module: Figure 4: Light PV module installed at long side with Clamp fitting method Dimension (mm*mm) Longer Frame Section: 28*6.9 28*15 Short Frame Section: Beam Section: 19*15 - 14 -...
  • Page 17 Dimension(mm) Cell Pmax Module type Cell type quantity (Wp) JKMXXXM-72 JKMXXXM-72-J 5 inch Mono 6*12 160~215 1580*808 JKMXXXM-72B JKMXXXM-96 JKMXXXM-96-J 5 inch Mono 8*12 210~285 1575*1082 JKMXXXM-96B JKMXXXP-60 JKMXXXP-60-J JKMXXXPP-60 JKMXXXPP-60-J 6 inch Poly 6*10 210~280 1650*992 JKMxxxP-60(Plus) JKMxxxPP-60(Plus) JKMXXXP-60B JKMXXXM-60 JKMXXXM-60-J 6 inch Mono...
  • Page 18: Fixation With Clamps At Short Sides Of Frames

    JKMSXXXP-72 1952*990 JKMSXXXP-72-J 6 inch Poly 6*12 250~335 1956*992 JKMSxxxP-72(Plus) JKMSXXXM-72 1952*990 JKMSXXXM-72-J 6 inch Mono 6*12 250~335 1956*992 JKMSxxxM-72(Plus) 2400Pa mechanical load Max. Pressure: Table 3: Mechanical dimensions when modules installed at long side with Clamp fitting method 2.3.3 Fixation with clamps at short sides of the frames The applicable Products please refer to Table 4, only refer to the Normal PV module, and only allow using clamps at short side of frames.
  • Page 19 Figure 5: PV module installed at short side with Clamp fitting method Cell Dimension(mm) Cell Pmax Module type quantit type (Wp) Frame JKMSXXXP-60 6 inch JKMSXXXP-60-J 6*10 210~280 1650*992 40*35 Poly JKMSxxxP-60(Plus) JKMSXXXM-60 6 inch JKMSXXXM-60-J 6*10 210~280 1650*992 40*35 Mono JKMSxxxM-60(Plus) JKMSXXXP-72...
  • Page 20 JKMXXXM-60 JKMXXXM-60-J 6 inch 6*10 210~280 1650*992 40*35 JKMxxxM-60-(Plus) Mono JKMXXXM-60B JKMXXXP-72 JKMXXXP-72-J JKMXXXPP-72 6 inch 6*12 250~340 1956*992 40*35 JKMXXXPP-72-J Poly JKMSxxxP-72(Plus) JKMXXXP-72B JKMXXXM-72 JKMXXXM-72-J 6 inch 6*12 250~335 1956*992 40*35 JKMxxxM-72(Plus) Mono JKMXXXM-72B JKMxxxM-48 6 inch 170~220 1324*992 40*35 JKMxxxM-48-J Mono...
  • Page 21: Fixation With Clamps At The Long & Short Sides

    2.3.4 Fixation with clamps at the long & short sides The applicable Products please refer to Table 5, only refer to the Normal PV module, and only allow installing modules at the long and short sides with clamps respectively. The considerations and requirements about mounted by using clamps, please refer to the instructions in 2.3.2, and find detailed mounting information in the below illustration as Figure 6, the mounting place distance is suggested bigger than J and less than K for short sides,bigger than M and less than N for long sides, as shown...
  • Page 22 Dimension(mm) Cell Cell Pmax Module type type quantity (Wp) Frame JKMSXXXP-60 6 inch JKMSXXXP-60-J 6*10 210~280 1650*992 240 280 420 40*35 Poly JKMSxxxP-60(Plus) JKMSXXXM-60 6 inch JKMSXXXM-60-J 6*10 210~280 1650*992 240 280 420 40*35 Mono JKMSxxxM-60(Plus) JKMSXXXP-72 6 inch JKMSXXXP-72-J 6*12 250~335 1956*992...
  • Page 23 JKMXXXM-72 JKMXXXM-72-J 6 inch 6*12 250~335 1956*992 240 280 480 40*35 JKMxxxM-72(Plus) Mono JKMXXXM-72B JKMxxxM-48 6 inch 170~220 1324*992 240 240 270 40*35 JKMxxxM-48-J Mono JKMSxxxM-48-J 6 inch 170~220 1324*992 240 240 270 40*35 JKMSxxxM-48(Plus) Mono JKMxxxP-48 JKMxxxPP-48 6 inch 170~225 1324*992 240 240 270...
  • Page 24: Fixation With Screws & Clamps At The Long &Short Sides

    2.3.5 Fixation with screws & clamps at the long & short sides The applicable Products please refer to Table 6, only refer to the Normal PV module, and only allow installing modules at the long and short sides with screws and clamps respectively.
  • Page 25 Dimension(mm) Cell Cell Pmax Module type type quantity (Wp) Frame JKMSXXXP-60 6 inch JKMSXXXP-60-J 6*10 210~280 1650*992 40*35 Poly JKMSxxxP-60(Plus) JKMSXXXM-60 6 inch JKMSXXXM-60-J 6*10 210~280 1650*992 40*35 Mono JKMSxxxM-60(Plus) JKMSXXXP-72 6 inch JKMSXXXP-72-J 6*12 250~335 1956*992 40*35 Poly JKMSxxxP-72(Plus) JKMSXXXM-72 6 inch JKMSXXXM-72-J...
  • Page 26: Wiring And Connection

    JKMXXXP-72 JKMXXXP-72-J JKMXXXPP-72 6 inch 6*12 250~340 1956*992 40*35 JKMXXXPP-72-J Poly JKMSxxxP-72(Plus) JKMXXXP-72B JKMXXXM-72 JKMXXXM-72-J 6 inch 6*12 250~335 1956*992 40*35 JKMxxxM-72(Plus) Mono JKMXXXM-72B JKMxxxM-48 6 inch 170~220 1324*992 40*35 JKMxxxM-48-J Mono JKMSxxxM-48-J 6 inch 170~220 1324*992 40*35 JKMSxxxM-48(Plus) Mono JKMxxxP-48 JKMxxxPP-48 6 inch...
  • Page 27 maximum reverse current that a module can withstand, i.e. when one string is in shade then the other parallel strings of modules will be load by the shade string and the current will pass through to create a current circuit. Thus based on the maximum series fuse rating of module and local electrical installation criteria, make sure the modules strings in parallel for connection need to be assembled with appropriate string fuse for circuit protection.
  • Page 28: Maintenance And Care

    based on your condition. Please take the cable length into consideration before designing the wiring layout. i)It is recommend to adopt inverter negatively earthed installation to avoid the PID effect for non-PID free modules. Figure 9: Junction box 4. Maintenance and care It is required to perform regular inspection and maintenance of the modules, especially within warranty scope.
  • Page 29: Cleaning

    4.2 Cleaning a) A built up of dust or dirt on the module(s) front face will result in a decreased energy output. Clean the panel(s) preferably once per annum if possible (depend on site conditions) using a soft cloth dry or damp, as necessary. Water with high mineral content may leave deposits on the glass surface and is not recommended.
  • Page 30: Disclaimer Of Liability

    6. Disclaimer of Liability Because the use of the manual and the conditions or methods of installation, operation, use and maintenance of photovoltaic (PV) product are beyond Jinko‟s control, Jinko does not accept responsibility and expressly disclaims liability for loss ,damage, or expense arising out of or in any way connected with such installation, operation, use or maintenance.
  • Page 31 Global Sales & Marketing Center Jiangxi Manufacture Base Zhejiang Manufacture Base 16F, Building No.2 No.1 Jinko Road, No.58 Yuanxi Road, 428# South Yang Gao Road, Shangrao Economic Development Zone, Haining Yuanhua Industrial Park, Jiangxi Province, China 334100 Zhejiang Province, China 314416 Shanghai, China 200127 Tel: +86 21 6061 1799 Tel:+86 793 858 8188...