Febco 805Y Operation And Maintenance

Double check assembly 3/4"-2"

Advertisement

Quick Links

FEATURES AND OPERATING PROCEDURES
This device consists of two independently operating poppet type check valves. Each check valve is spring loaded to maintain a minimum
of 1 PSIG differential pressure across the check in a no-flow condition. In a normal flow condition the checks open an amount correspond-
ing to the flow rate. During a backflow (backpressure) situation the seat discs close and seal to prevent any flow reversal. Sizes 3/4"
through 2" (805Y, 805YB, 805YS, 805YR) include two spring-loaded, Y-pattern bronze check valves, two bronze shut-off valves and four
testcocks for field testing. All valves are threaded type and the unit is shipped completely assembled.
GENERAL SERVICE PROCEDURES (General service instructions applicable to all sizes.)
1. Rinse all parts with clean water prior to assembly.
2. DO NOT USE ANY PIPE DOPE, OIL, GREASE OR SOLVENT ON ANY PARTS unless instructed to do so.
4. Do not force parts. Parts should fit freely together. Excess force may cause damage and render the device inoperable.
5. Carefully inspect seals, seating surfaces, etc. for damage or debris.
5. Test unit after servicing to insure proper operations.
6. Refer to applicable parts list and figures for more information.
7. A table on page 3 provides size and material information for standard parts (non-special design). These parts can usually be
purchased locally from parts distributors.
8. Some water conditions can cause a buildup of calcium or similar material deposits on some moving parts. Normally this condition
would not occur on devices used in systems with varying flow rates. The scraping action of moving parts helps to remove any deposits.
However, with devices used on static systems such as firelines, any deposits would not be scraped away and could interfere with the
check valve operation. Devices in these applications should be disassembled and inspected on a periodic basis depending on water
quality. Any deposits should be removed from the center guiding stem and bushings. Use care to avoid damage to guiding surfaces.
TROUBLESHOOTING GUIDE
Symptom #1
Check fails to hold 1.0 PSID min.
Symptom #2
Chatter during flow conditions.
Symptom #3
Low flows passing through the
mainline valve.
FEBCO Operation and Maintenance
805Y / 805YB / 805YS
Double Check Assembly (
Cause:
A. Debris on sealing surfaces
B. Leaking shut-off valve
C. Damaged seat disc or seat ring
D. Damaged guide holding check open
E. Weak or broken spring
Cause:
A. Worn or damaged guide
Cause:
A. Mainline check fouled
3
/
" – 2")
4
®
Solution:
Disassemble and clean
Disassemble and clean or repair
Disassemble and replace
Disassemble and replace guide pin
and/or sleeve bushing
Disassemble and replace spring
Solution:
Disassemble and repair or replace guide
Solution:
Inspect and clean, or repair

Advertisement

loading
Need help?

Need help?

Do you have a question about the 805Y and is the answer not in the manual?

Questions and answers

Summary of Contents for Febco 805Y

  • Page 1 During a backflow (backpressure) situation the seat discs close and seal to prevent any flow reversal. Sizes 3/4" through 2" (805Y, 805YB, 805YS, 805YR) include two spring-loaded, Y-pattern bronze check valves, two bronze shut-off valves and four testcocks for field testing.
  • Page 2 SERVICE PROCEDURES FOR MODELS 805Y, 805YB, 805YS 1. Disassembly-Check Valves a. Close inlet and outlet shut-off valves. Bleed residual pressure by opening 3 and 4 testcocks. b. Unscrew cap using appropriate size wrench. NOTE: Cap is spring loaded. c. Remove the spring and check assembly.
  • Page 3 905-053 905-053 Check Assembly (Items: 8, 9, 10, 11, 12) 905-044 905-044 905-055 905-055 Model 805YB Model 805YB utilizes the same components as the 805Y with the exception of the following: Fig No. Description Qty. " 1" " 2" Spring...
  • Page 4 FREEZE PROTECTION The backflow prevention assembly may be subject to damage if the internal water is allowed to freeze. The unit must be protected from freezing using a heated enclosure, insulation heat tape, or other suitable means. The unit must always be accessible for testing and maintenance.