Energi Savr Node
Please refer to the daylight sensor installation guide for details on sensor placement.
Infrared (IR) Remote Receivers
Energi Savr Node QS units are programmable to turn lights on and off based on signals provided by
compatible Lutron
IR transmitters and received by compatible Lutron IR receivers. To ensure proper operation
®
of the Energi Savr Node QS unit:
• Use only Lutron IR receivers (EC-DIR-WH, EC-IR-WH, CC-1BRL-WH, CC-4BRL-WH)
• See Lutron IR receiver literature for compatible IR transmitters.
• Only wire one receiver to a single IR input

Advanced Button Programming

Each Energi Savr Node QS unit zone has several parameters that can be set or adjusted. Follow the steps
below to adjust a zone's setting.
Configure Zone Parameters
1. Simultaneously press and hold the Program and Input buttons for 3 seconds to enter Zone Set-up Mode.
'Program' and Group A LEDs will flash rapidly.
2. Press Zone button to select the zone for which you wish to set parameters.
3. Use the Option button to select a parameter to set or adjust as listed below. The option LEDs will turn on to
indicate your selection:
Option LED(s) Parameter
Set zone to respond to wired Occupancy
'Def'
sensor as either Occupancy or Vacancy
sensor
Set daylight sensor setpoint for each
'Opt1'
zone
4. Repeat steps 2 and 3 for each desired zone.
5. Simultaneously press and hold the Program and Input buttons for 3 seconds to exit Zone Set-up Mode.

Scene Programming Mode

Scene Programming
Each output zone on the Energi Savr Node QS unit has 16 scenes plus Off. Each scene can be programmed
to turn the zone on or off, or the zone can be set to be unaffected in a scene, so that changing to that scene
will not change the unaffected zone from its current level. Note: Scene Off cannot be modified.
Follow the steps below and in the QS Link Input(s) Set-up section.
Scenes 1-4
1. Simultaneously press and hold the Program and Option buttons on the Energi Savr Node QS unit for 3
seconds to enter Scene Programming Mode. 'Program' and Group B LEDs will flash rapidly.
2. Use the Option button to select a scene to define for each zone. Option LED will be steady on, to indicate
current scene selected:
LED Legend:
= steady on
LEDs
Scene # LEDs
Scene 1
3. Use the and buttons to set the selected scene to On or Off. The 'H', 'M', and 'L' LED group indicates your
choice: all LEDs on = On; all LEDs off = Off.
4. To make a zone unaffected, press and hold the button until only the 'M' LED turns on.
|
Energi Savr Node
QS
TM
QS | Programming Guide
TM
= flashing
Scene # LEDs
Scene 2
Programming Guide
Method
Use the and
· ' H' LED indicates Occupancy mode (Auto on/off).
· ' M' LED indicates Vacancy mode (Manual on/
auto off)
Use the button to increase the set point.
Use the button to decrease the set point.
= off
Scene # LEDs
Scene #
Scene 3
Scene 4
buttons to select response mode.
|