Wireless Field Level Network Transceiver (FLNX)
(Version 1.x)
Channel
Network I.D.
Figure 1. Wireless Field Level Network Transceiver
(FLNX).

Product Description

The Wireless Field Level Network Transceiver
(FLNX) is mounted at or near the FLN device
and is powered by 24 Vac. The antenna can be
mounted directly to the radio or mounted remotely for
installations where the location of the FLNX causes
the antenna to be shielded—for example, when the
FLNX is mounted inside a TEC enclosure.
Product Numbers
563-004
Wireless Field Level
Network Transceiver (FLNX)
(Version 1.x)
563-007
Direct Mount Antenna
563-008
Remote Mount Antenna
Transceivers do not come with antennas.
Antennas must be ordered separately.
Item Number: 563-002, Rev. BA
24 Vac 1.2VA
E H N
F L N
Installation Instructions
Accessories
563-027
Pre-terminated Cable Kit
(Includes two 14" cables:
power and communication)
Recommended for factory mounting
Warning/Caution Notations
WARNING:
Personal injury/loss of life may occur if you
do not follow the procedures as specified.
CAUTION:
Equipment damage or loss of data may
occur if you do not follow the procedures
as specified.
Expected Installation Time
10 minutes
Required Tools and Materials
Electro-static discharge wrist strap
Small flat-blade screwdriver
Cordless drill/driver set
Prerequisites
All wiring must conform to NEC and local
codes and regulations.
24 Vac Class II power source is available.
Metal Oxide Varistors (MOVs) must be used
for TECs that switch high voltage devices. For
details, see the FSN for Terminal Equipment
Controllers (TECs) Failing when Switching
High Voltage Powered Devices.
Any application specific hardware or device
is installed.
Document No. 563-002
January 12, 2007
Page 1 of 4

Advertisement

loading

Summary of Contents for Siemens 563-004

  • Page 1: Product Description

    Cordless drill/driver set FLNX is mounted inside a TEC enclosure. Prerequisites Product Numbers • All wiring must conform to NEC and local 563-004 Wireless Field Level codes and regulations. Network Transceiver (FLNX) • 24 Vac Class II power source is available.
  • Page 2: Antenna Mounting

    Wireless TEC Transceiver (TTX, P/N 550-205) and the TEC, be sure to use a ground isolated transformer (P/N 550-710) between the TTX and the power transformer. Figure 2. FLNX Mounting Options – No Enclosure. Siemens Building Technologies, Inc. Page 2 of 4...
  • Page 3 1/2” knockout and use the articulated. locknut to secure the body of the liquid tight fitting into the knockout. c. Connect the antenna wire securely to the FLNX. Siemens Building Technologies, Inc. Page 3 of 4...
  • Page 4 Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2007 Siemens Building Technologies, Inc. Your feedback is important to us. If you have Document No.

This manual is also suitable for:

563-007563-008