3 General description Application This connection box can only be used in conjunction with ZIEHL-ABEGG ECblue fans with motor size B (IP20). Function ECblue fans combined with the ECblue (LON) connection box provide the following functions: •...
Page 3
Operating Instructions Connection box ECblue (LON) Mounting 4 Mounting Proceed as follows: Create the installation cut-out and fastening hole as shown in the drawing. " Insert the device into the installation cut-out from the front and secure with a screw.
3 Line input connection box (Wieland plug series GST 18i3, suitable socket part e.g. GST 18i3 S B1 Z R1 or GST 18i3 1 F B2 Z R1) 4 LED green = Operation / Flashing error code (see ECblue assembly instructions, chapter “Operating state display”) 5 LED red = Fault (see ECblue assembly instructions, chapter “operating state display”)
Page 5
Operating Instructions Connection box ECblue (LON) Electrical installation BUS1, BUS2 and Service pin assignment 1. Net A 2. Net B 3. not connected 4. not connected 5. not connected 6. not connected 7. GND (V-) 8. ID +5V (V+) PIN 1 on BUS1, BUS2 and Service are through connected (NET bus connection A for fan).
Page 6
Operating Instructions Connection box ECblue (LON) Electrical installation Communication 5.4.1 Bus connection The connection is made using the RJ45 sockets, Bus 1 and Bus 2. A minimum of CAT5 (STP) are recommended as the cables. The cable shield is connected to PE by an RC element inside the connection box.
Page 7
You can use nciEnable to enable the motor controller function. The variables nvoVisual, nvoParameter and nviParameter are available for use with ZIEHL-ABEGG software and installation devices. For dynamic operation, i.e. operation in which the speed changes very often (e.g. control applications), a different operating mode has to be selected as the static rotational speed specifications nciSpeedx...
Page 8
Operating Instructions Connection box ECblue (LON) Electrical installation Objekt Type #1 Open Loop Sensor Inputs/outputs Type Value range Default Description nvoSpeed SNVT_rpm 0...65.534, Measured absolute speed (102) 0xFFFF nvoAlarm SNVT_a- Option larm_2 (164) nvoError* uint (1 Byte) 128 – 255, 0 128 no fault >...
Technical data Type Connection box ECblue (LON) Part-No. 380100 Voltage supply 10 V DC, I 30 mA, from ECblue motor size B (IP20) Transceiver TP/FT10 Communication Connection box - ECblue RS485 Electromagnetic compatibility Interference emission EN 61000-6-3 (domestic household applica-...
Page 10
Operating Instructions Connection box ECblue (LON) Enclosure Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau...
Need help?
Do you have a question about the ECblue and is the answer not in the manual?
Questions and answers