Sterlco AquaSnap 30RA010-055 Operation And Service Manual

Air-cooled chillers with comfortlink controls 50/60 hz
Table of Contents

Advertisement

Controls, Start-Up, Operation,
Service, and Troubleshooting

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roof, elevated structures, mechanical
rooms, etc.). Only trained, qualified installers and service
mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment, and any other safety precautions that apply. Follow
all safety codes. Wear safety glasses and work gloves. Use
care in handling, rigging, and setting this equipment, and in
handling all electrical components.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation and
service. There may be more than one disconnect switch.
Tag all disconnect locations to alert others not to restore
power until work is completed.
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE
(American National Standards Institute/American Society
of Heating, Refrigeration and Air Conditioning Engineers)
15 (Safety Code for Mechanical Refrigeration). The
accumulation of refrigerant in an enclosed space can
displace oxygen and cause asphyxiation. Provide adequate
ventilation in enclosed or low overhead areas. Inhalation of
high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness or death. Misuse can
be fatal. Vapor is heavier than air and reduces the amount
of oxygen available for breathing. Product causes eye and
skin irritation. Decomposition products are hazardous.
DO NOT attempt to unbraze factory joints when servicing
this equipment. Compressor oil is flammable and there is
no way to detect how much oil may be in any of the
refrigerant lines. Cut lines with a tubing cutter as required
when performing service. Use a pan to catch any oil that
may come out of the lines and as a gage for how much oil
to add to system. DO NOT re-use compressor oil.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903
Catalog No. 533-00047
Book 2
Tab
5c
AquaSnap® Air-Cooled Chillers
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from recom-
mended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the electronic
modules or electrical components.
To prevent potential damage to heat exchanger, always run
fluid through heat exchanger when adding or removing
refrigerant charge. Use appropriate brine solutions in cooler
fluid loop to prevent the freezing of brazed plate heat
exchanger, optional hydronic section and/or interconnecting
piping when the equipment is exposed to temperatures
below 32 F (0 °C). Proof of flow switch and strainer are
factory installed on all models. Do NOT remove power
from this chiller during winter shutdown periods without
taking precaution to remove all water from heat exchanger
and optional hydronic system. Failure to properly protect
the system from freezing may constitute abuse and may
void warranty.
Compressors and optional hydronic system pumps require
specific rotation. Test condenser fan(s) first to ensure
proper phasing. Swap any two incoming power leads to
correct condenser fan rotation before starting any other
motors.
Refrigerant charge must be removed slowly to prevent loss
of compressor oil that could result in compressor failure.
Printed in U.S.A.
Form 30RA-2T
30RA010-055
with ComfortLink™ Controls
Pg 1
1-03
50/60 Hz
Replaces: 30RA-1T

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AquaSnap 30RA010-055 and is the answer not in the manual?

Questions and answers

Summary of Contents for Sterlco AquaSnap 30RA010-055

  • Page 1: Safety Considerations

    Controls, Start-Up, Operation, Service, and Troubleshooting SAFETY CONSIDERATIONS Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, mechanical rooms, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment. When working on this equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply.
  • Page 2: Table Of Contents

    CONTENTS SAFETY CONSIDERATIONS......1 GENERAL......... .2,3 MAJOR SYSTEM COMPONENTS.
  • Page 3: General

    Table 1 — Unit Sizes NOMINAL CAPACITY UNIT (TONS) 50/60 Hz 30RA010 30RA015 30RA018 30RA022 30RA025 30RA030* 30RA032† 30RA035 30RA040* 30RA042† 30RA045 30RA050* 30RA055* *60 Hz only. †50 Hz only. MAJOR SYSTEM COMPONENTS General — The 30RA air-cooled reciprocating chillers contain the ComfortLink™...
  • Page 4: Operating Data

    TURE SENSOR (ACCESSORY) — A well for this sensor is factory installed in each circuit's suction line. If desired, a 5 kΩ thermistor (Sterling part number HH79NZ029) can be installed in this well and connected to the Main Base Board as shown in Table 2.
  • Page 5: T10 - Remote Space Temperature Sensor Or

    (parallel only are supported), connect the dual chiller leaving fluid temperature sensor (5 k Ω ther- mistor, Sterling part no. HH79NZ029) to the space temperature input of the Master chiller. If space temperature is required for reset applications, connect the sensor to the Slave chiller and configure the slave chiller to broadcast the value to the Master chiller.
  • Page 6 Fig. 1 — Typical Control Box for 30RA010-030 (022-030 Shown)
  • Page 7 Fig. 2 — Typical Control Box for 30RA032-055 (042-055 Shown)
  • Page 8 30RA010-018 AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018...
  • Page 9 AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (010-018) SEE NOTE 8 SEE NOTE 8 Fig. 3 — Wiring Schematic 30RA010-018 (cont)
  • Page 10 30RA022-030 AQUA SNAP Fig. 4 — Wiring Schematic 30RA022-030...
  • Page 11 AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (022-030) Fig. 4 — Wiring Schematic 30RA022-030 (cont)
  • Page 12 30RA032-040 AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040...
  • Page 13 AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (032-040) Fig. 5 — Wiring Schematic 30RA032-040 (cont)
  • Page 14 30RA042-055 AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055...
  • Page 15 AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (042-055) Fig. 6 — Wiring Schematic 30RA042-055 (cont)
  • Page 16 RED LED - STATUS CEPL130346-01 MODE Run Status Service Test Temperature Pressures Setpoints Inputs Alarm Status Outputs ESCAPE Configuration Time Clock Operating Modes Alarms Fig. 8 — LEN/SCN Interface, Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations GREEN LED - YELLOW LED - SCN (STERLCO COMFORT NETWORK) LEN (LOCAL EQUIPMENT NETWORK)
  • Page 17: Energy Management Module

    SPT (T10) PART NO. 33ZCT55SPT SENSOR Fig. 9 — Typical Space Temperature Sensor Wiring SCN+ TO SCN SCN GND COMM 1 BUS (PLUG) AT UNIT SCN- Fig. 10 — SCN Communications Bus Wiring to Optional Space Sensor RJ11 Connector Energy Management Module (Fig. 11) — factory-installed option (FIOP) or field-installed accessory is used for the following types of temperature reset, demand limit, and/or ice features:...
  • Page 18 CEBD430351-0396-01C STATUS RED LED - STATUS Table 6 — Part Load Data Percent Displacement, Standard Units without Minimum Load Valve CONTROL 30RA UNIT SIZE STEPS 010,015 (60 Hz) 015 (50 Hz), 018 022 (60 Hz) 022 (50 Hz), 025, 030 032, 035 (60 Hz) 035 (50 Hz) 042, 045 (50 Hz), 050,...
  • Page 19 Table 7 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve CONTROL 30RA UNIT SIZE STEPS 010 (50/60 Hz) 015 (60 Hz) 015 (50 Hz) 018 (50/60 Hz) 022 (50/60 Hz) 025 (50/60 Hz) 035 (50/60 Hz) 045 (60 Hz) 045 (50 Hz), 050 *Minimum Load Valve energized.
  • Page 20: Minutes Off Time

    MINUTES LEFT FOR START — This value is displayed only in the network display tables (using Service Tool, ComfortVIEW™ or ComfortWORKS® software) and represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations.
  • Page 21: Head Pressure Control

    Head Pressure Control — The Main Base Board (MBB) controls the condenser fans to maintain the lowest condensing temperature possible, and thus the highest unit efficiency. The MBB uses the saturated condensing tempera- ture input from the discharge pressure transducer to control the fans.
  • Page 22: Operation Of Machine Based On Control Method And Cooling Set Point Selection Settings

    DETAIL A PRESSURE TRANSDUCER INSTALLED HERE Fig. 15 — Typical Motormaster® V Controller and Pressure Transducer Location (Sizes 022-030 Shown) Operation of Machine Based on Control Method and Cooling Set Point Selection Set- tings — Machine On/Off control is determined by the configuration of the control method (CTRL) [Configuration, OPT2] and cooling set point select (CLSP) [Configuration, SLCT] variables.
  • Page 23: Marquee Display Usage

    Table 8 — Control Methods and Cooling Set Points CONTROL OCCUPANCY TYPE STATE (CTRL) Occupied 0 (switch) Unoccupied Occupied 2 (Occupancy) Unoccupied Occupied 3 (SCN) Unoccupied *Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed. †Cooling set point determined from 4 to 20 mA input to Energy Management Module (EMM) to terminals TB6-3,5.
  • Page 24: Optional Factory-Installed Hydronic Package

    Optional Factory-Installed Hydronic Package — If the chiller has factory-installed chilled fluid pumps, specific steps should be followed for proper operation. The pump(s) in the hydronic package come factory pre-wired into the main unit power supply/starter. In order to check proper pump rotation, use the Service Test function to test the condenser fans and observe them for proper rotation (counter clockwise when viewed from the top).
  • Page 25 Opened During Normal Operation Alarm will be generated and the machine will stop. If the control detects the chilled water pump interlock open for 25 seconds after initially being closed, a T194 — Cooler Pump 1 Contacts Opened During Normal Operation Alert is generated and the unit is shut down.
  • Page 26: Configuring And Operating Dual Chiller Control

    As part of a pump maintenance routine, the pumps can be started to maintain lubrication to the pump seal. To utilize this function, Cooler Pmp Periodic Start (PM.P.S) [Configuration, UNIT] must be set to YES. This option is set to NO as the fac- tory default.
  • Page 27 Table 10 — Run Status Mode and Sub-Mode Directory KEYPAD SUB-MODE ITEM DISPLAY SUB-ITEM ENTRY XXX.X °F VIEW ENTER XXX.X °F XXX.X °F SETP XXX.X °F CTPT LOD.F STAT LD.PM YES/NO LS.AC YES/NO MODE YES/NO XXX % STGE ALRM TIME XX.XX MNTH DATE...
  • Page 28 Table 10 — Run Status Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY SUB-ITEM ENTRY PM (cont) ENTER STRN ENTER ENTER S.T.DN S.T.MN ENTER COIL ENTER ENTER C.L.DN C.L.MN ENTER VERS ENTER MARQ NAVI *Press simultaneously to obtain version number. ENTER ESCAPE DISPLAY...
  • Page 29 Table 11 — Service Test Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY TEST ENTER OUTS ENTER CMPA ENTER CMPB ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 12 —...
  • Page 30 Table 13 — Pressure Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY PRC.A ENTER PRC.B ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 14 —...
  • Page 31 Table 16 — Outputs Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY GEN.O ENTER CIR.A ENTER CIR.B ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 17 —...
  • Page 32 Table 17 — Configuration Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM ENTRY OPT1 FLUD ENTER MLV.S MMR.S RG.EN PM1E PM2E PM.P .S PM.SL PM.DY PM.DT ROT.P OPT2 CTRL ENTER SCNA SCNB BAUD LOAD LLCS LCWT DELY ICE.M CLS.C LS.MD LS.ST LS.ND LS.LT...
  • Page 33 Table 17 — Configuration Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY ENTRY RSET (cont) XXX.X °F RM.F XX.X °F RM.DG XXX.X ∆F RT.NO XXX.X ∆F RT.F XX.X °F RT.DG DMDC DM20 XXX % SHNM SHDL XXX % SHTM DLS1 XXX % DLS2...
  • Page 34 Table 18 — Time Clock Mode and Sub-Mode Directory KEYPAD SUB-MODE ITEM DISPLAY ENTRY TIME HH.MM XX.XX ENTER DATE MNTH ENTER YEAR XXXX STR.M ENTER STR.W STR.D MIN.A STP .M STP .W STP .D MIN.5 SCH.N SCH.L PER.1 ENTER ENTER PER.2 ENTER ENTER...
  • Page 35 Table 18 — Time Clock Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY ENTRY SCH.L (cont) PER.3 ENTER ENTER PER.4 ENTER ENTER PER.5 ENTER ENTER PER.6 ENTER ENTER ITEM SUB-ITEM DISPLAY EXPANSION OCCUPANCY PERIOD 3 OCC.3 XX:XX PERIOD OCCUPIED TIME UNC.3 XX.XX PERIOD UNOCCUPIED TIME...
  • Page 36 Table 18 — Time Clock Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY ENTRY SCH.L (cont) PER.7 ENTER ENTER PER.8 ENTER ENTER OVR.T ENTER OVR.L T.OVR YES/NO ITEM SUB-ITEM DISPLAY EXPANSION THU.6 YES/NO THURSDAY IN PERIOD FRI.6 YES/NO FRIDAY IN PERIOD SAT.6 YES/NO SATURDAY IN PERIOD...
  • Page 37 Table 19 — Operating Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY MODE ENTER LEGEND — Flotronic™ System Manager — Saturated Condensing Temperature — Water System Manager Table 20 — Alarms Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY CRNT AXXX OR TXXX ENTER RCRN ENTER...
  • Page 38 Table 21 — Dual Chiller Configuration (Master Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISP UNIT OPT1 OPT2 ENTER CTRL ENTER ESCAPE ENTER SCNA ENTER ESCAPE SCNB ENTER ESCAPE ESCAPE RSET ENTER LLEN ENTER ENTER LLEN ENTER ESCAPE MSSL ENTER ESCAPE SLVA ENTER ENTER...
  • Page 39 Table 21 — Dual Chiller Configuration (Master Chiller Example) (cont) SUB-MODE ITEM KEYPAD ENTRY RSET LLBL ENTER ESCAPE LLBD ENTER ESCAPE LLDY ENTER ENTER LLDY ENTER ESCAPE ESCAPE PARA ENTER NOTES: 1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-SCN. 2.
  • Page 40 Table 22 — Dual Chiller Configuration (Slave Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISP UNIT OPT1 OPT2 ENTER CTRL ESCAPE CTRL SCNA ENTER ENTER SCNA ENTER ESCAPE SCNB ENTER ESCAPE ESCAPE RSET ENTER LLEN ENTER ENTER LLEN ENTER ESCAPE MSSL ENTER ENTER MSSL...
  • Page 41 MODE ITEM EXPANSION FSM CONTROLLING CHILLER WSM CONTROLLING CHILLER MASTER/SLAVE CONTROL RAMP LOAD LIMITED TIMED OVERRIDE IN EFFECT LOW COOLER SUCTION TEMPA LOW COOLER SUCTION TEMPB SLOW CHANGE OVERRIDE MINIMUM OFF TIME ACTIVE DUAL SETPOINT TEMPERATURE RESET DEMAND/SOUND LIMITED COOLER FREEZE PROTECTION LOW TEMPERATURE COOLING HIGH TEMPERATURE COOLING MAKING ICE...
  • Page 42 Table 24 — Example of Reading and Clearing Alarms KEYPAD SUB-MODE ENTRY CRNT AXXX or TXXX ENTER CRNT ESCAPE ENTER RCRN ENTER KEYPAD SUB-MODE ITEM ENTRY RSET ENTER CRST CRT1 CRT2 DGRC NOTE: The example above shows how to configure the chiller for 4-20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA.
  • Page 43: Temperature Reset

    Table 26A — Configuring Outdoor Air and Space Temperature Reset MODE KEYPAD SUB- (RED LED) ENTRY MODE DISP ENTER UNIT OPT1 OPT2 CONFIGURATION RSET *4 items skipped in this example. Table 26B — Configuring Return Temperature Reset MODE KEYPAD SUB-MODE (RED LED) ENTRY DISP...
  • Page 44: Demand Limit

    2.0 F (1.1 C) cooler ∆T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler ∆T. The variable RT.NO should be set to the cooler temperature difference (∆T) where no chilled water tempera- ture reset should occur. The variable RT.F should be set to the cooler temperature difference where the maximum chilled wa- ter temperature reset should occur.
  • Page 45: Demand Limit (Scn Loadshed Controlled)

    100% CAPACITY AT 4 mA Care should be taken when interfacing with other manufac- turer’s control systems, due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A sig- nal isolation device should be utilized if a full wave bridge signal generating device is used.
  • Page 46: Protection

    KEYPAD MODE SUB-MODE ENTRY CONFIGURATION DISP ENTER UNIT OPT1 OPT2 RSET *Seven items skipped in this example. TROUBLESHOOTING Complete Unit Stoppage and Restart — ble causes for unit stoppage and reset methods are shown be- low. (See Table 28 also.) Refer to Fig. 22-26 for Component Arrangement and Control Wiring Diagrams.
  • Page 47: Thermistor Failure

    SYMPTOMS Cooler Circulating Pump Does Power line open Not Run Control fuse or circuit breaker open Compressor over temperature sensor open (06D) Tripped power breaker Cooler circulating pump not running Loose terminal connection Improperly wired controls Low line voltage Compressor motor defective Seized compressor Compressor Cycles Loss of charge control erratic in action...
  • Page 48 LEGEND — Contactor, Compressor — Circuit Breaker — Cooler/Pump Heater Contactor — Chilled Water Pump — Energy Management — Fan Contactor FIOP — Factory-Installed Option — Fuse — Ground — Main Base Board — Motormaster® MMPT — Motormaster Pressure Transducer —...
  • Page 49 LEGEND — Contactor, Compressor — Circuit Breaker — Cooler/Pump Heater Contactor — Chilled Water Pump — Energy Management — Fan Contactor FIOP — Factory-Installed Option — Fuse — Ground — Main Base Board — Motormaster® MMPT — Motormaster Pressure Transducer —...
  • Page 50 LEGEND — Contactor, Compressor — Circuit Breaker — Cooler/Pump Heater Contactor — Chilled Water Pump — Energy Management — Fan Contactor FIOP — Factory-Installed Option — Fuse — Ground — Main Base Board — Motormaster® MMPT — Motormaster Pressure Transducer —...
  • Page 53: Alarms And Alerts

    Alarms and Alerts — These are warnings of abnormal or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assigned code numbers as described in Table 29. Automatic alarms will reset without operator intervention if the condition corrects itself.
  • Page 54 Table 29 — Alarm and Alert Codes (cont) ALARM/ ALARM ALERT DESCRIPTION CODE ALERT T093 Alert Circuit B Suction Pressure Transducer Failure T110 Alert Circuit A Loss of Charge T111 Alert Circuit B Loss of Charge T112 Alert Circuit A High Saturated Suction Temperature T113 Alert...
  • Page 55 Table 29 — Alarm and Alert Codes (cont) ALARM/ ALARM ALERT DESCRIPTION CODE ALERT A140 Alert Reverse Rotation Detected A150 Alarm Emergency Stop A151 Alarm Illegal Configuration A152 Alarm Unit Down Due to Failure T153 Alert Real Time Clock Hardware Failure A154 Alarm Serial EEPROM...
  • Page 56 ALARM/ ALARM ALERT DESCRIPTION CODE ALERT T196 Alert Flow Lost While Pump 1 Running T197 Alert Flow Lost While Pump 2 Running T198 Alert Cooler pump 1 Aux Contacts Closed While Pump Off T199 Alert Cooler pump 2 Aux Contacts Closed While Pump Off T200 Alert...
  • Page 57 ALARM/ ALARM ALERT DESCRIPTION CODE ALERT T301 Alert Cooler Pump 2 Scheduled Maintenance Due T302 Alert Strainer Blowdown Scheduled Maintenance Due T303 Alert Condenser Coil Maintenance Due T950 Alert Loss of Communication with Water System Manager T951 Alert Loss of Communication with Flotronic™...
  • Page 58: Service

    SERVICE ELECTRIC SHOCK HAZARD. Turn off all power to unit before servicing. The ENABLE/OFF/REMOTE CONTACT switch on control panel does not shut off control power; use field disconnect. Electronic Components CONTROL COMPONENTS — Unit uses an advanced elec- tronic control system that normally does not require service. For details on controls refer to Operating Data section.
  • Page 59 COMPRESSOR BASE Fig. 27 — Typical Compressor Mounting — All Sizes LEGEND HPS — High-Pressure Switch Fig. 28 — Compressor Wiring COMP B2 COMP B1 COMP A2 COMP A1 COMP A2 COMP A1 Fig. 30 — Compressor Location — 30RA032-055 Fig.
  • Page 60: Check Oil Charge

    Use only Sterling-approved compressor oil: Totaline ....... . . PP680002 Penreco .
  • Page 61: Check Refrigerant Feed Components

    • Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle. Harsh Chemical and Acid Cleaners — Harsh chemical, household bleach or acid cleaners should not be used to clean outdoor or indoors coils of any kind.
  • Page 62: Pressure Relief Devices

    Fig. 34 — Mounting Locations for TXV Sensing Bulb The amount of capacity reduction achieved by the mini- mum load valve is not adjustable. The total unit capacity with the minimum load valve is shown in Table 7. PRESSURE RELIEF DEVICES — All units have one pres- sure relief device per circuit located in the liquid line which re- lieves at 210 F (100 C).
  • Page 63: Cooler Freeze-Up Protection

    15 F (8.3 C) below the leaving-fluid temperature set point. Failure to provide the proper brine mixture is consid- ered abuse and may void the Sterling warranty. The Main Base Board (MBB) monitors leaving fluid tem- perature at all times. The MBB will rapidly remove stages of capacity as necessary to prevent freezing conditions due to the rapid loss of load or low cooler fluid flow.
  • Page 64 Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop (Voltage Drop for Entering, Leaving Water and Outside-Air Thermistors T1, T2, T9) VOLTAGE TEMP RESISTANCE DROP (Ohms) –25 3.699 98,010 –24 3.689 94,707 –23 3.679 91,522 –22 3.668 88,449 –21 3.658 85,486 –20...
  • Page 65 Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop (Voltage Drop for Entering, Leaving Water and Outside-Air Thermistors T1, T2, T9) VOLTAGE TEMP RESISTANCE DROP (Ohms) –32 3.705 100,260 –31 3.687 94,165 –30 3.668 88,480 –29 3.649 83,170 –28 3.629 78,125 –27...
  • Page 66 Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop VOLTAGE TEMP RESISTANCE DROP (Ohms) –25 4.758 196,453 –24 4.750 189,692 –23 4.741 183,300 –22 4.733 177,000 –21 4.724 171,079 –20 4.715 165,238 –19 4.705 159,717 –18 4.696 154,344 –17 4.686 149,194 –16...
  • Page 67 Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop VOLTAGE TEMP RESISTANCE DROP (Ohms) –32 4.762 200,510 –31 4.748 188,340 –30 4.733 177,000 –29 4.716 166,342 –28 4.700 156,404 –27 4.682 147,134 –26 4.663 138,482 –25 4.644 130,402 –24 4.624 122,807 –23...
  • Page 68: Installation

    Strainer — Periodic factory-installed strainer cleaning is required. Pressure drop across strainer in excess of 3 psi (21 kPa) indicates the need for cleaning. Normal (clean) pres- sure drop is approximately 1 psi (6.9 kPa). Open the factory- installed blowdown valve to clean the strainer. If required, shut the chiller down and remove the strainer screen to clean.
  • Page 69: Programming

    NOTE: Since faults may be reset as incoming power is cycled, you may need to observe current fault code before the Sterling unit control turns off the VFD. Most recent faults can be accessed using parameter 50. If necessary, remove start jumper and energize condenser fan contactor using Service Test.
  • Page 70 BUTTONS Mode Fig. 37 — Motormaster® V Mode Buttons and Mode Display Fig. 38 — Pressure Transducer and Start Command Jumper Wiring Mode DANGER TERMINAL BLOCK T1 T2 T3 DISPLAY NOMINAL CONTROL INPUT MODE VOLTAGE (PIN 5) 208*/230/ Internal PI control, 460/575 0-5V feedback Internal PI control,...
  • Page 71: Fault Code

    FAULT CODE High Temperature Fault: Ambient temperature is too high; Cooling fan has failed (if equipped). Control Fault: A blank EPM, or an EPM with corrupted data has been installed. Incompatibility Fault: An EPM with an incompatible parame- ter version has been installed. CURRENT LIMIT: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current.
  • Page 72 Table 38 — Motormaster® V Program Parameters for Operating Modes PARAMETERS DESCRIPTION Line Voltage: 01 = low line, 02 = high line Sterlco Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz Startup mode: flying restart Stop mode: coast to stop Standard Speed source: 01= keypad, 04=4-20mA (NO PI), 05= R22, 06=R134a...
  • Page 73: Replacing Defective Modules

    30RA units are shipped with a single impeller size available for that pump. The pump was selected based on the flow and head requirements as provided to Sterling. It is not uncommon for actual pump duty to be different than what was anticipated at time of selection.
  • Page 74: Maintenance

    Routine: For machines with E-coat Condenser Coils: • Check condenser coils for debris, clean as necessary with Sterling approved coil cleaner. • Periodic clean water rinse, especially in coastal and industrial applications. Every month: • Check condenser coils for debris, clean as necessary with Sterling approved coil cleaner.
  • Page 75: Check Refrigerant Charge

    During charging or removal of refrigerant, be sure water is continuously circulating through the cooler to prevent freezing. Damage caused by freezing is considered abuse and may void the Sterling warranty. Operating Limitations TEMPERATURES (See Table 41 for 30RA Standard Tem-...
  • Page 76: Voltage - All Units

    45 F (7 C) for sizes 010-030 or below 32 F (0° C) for sizes 032-055 are expected, accessory Motormaster® V con- trol must be installed. Refer to separate installation instructions for operation using this accessory. Contact your Sterling repre- sentative for details. Brine duty application (below 40 F [4.4 C] LCWT) for chiller normally requires factory modification.
  • Page 77: Appendix Ascn Tables

    A_UNIT (General Unit Parameters) DESCRIPTION VALUE Control Mode 0 = Test 1 = Local Off 2 = SCN Off 3 = Clock Off 4 = Emergency Stop 5 = Local On 6 = SCN On 7 = Clock On 8 = Heat Enabled 9 = Pump Delay Occupied No/Yes...
  • Page 78 CIRCBDIO (Circuit B Discrete Inputs/Outputs) DESCRIPTION VALUE CIRC. B DISCRETE OUTPUTS Compressor B1 Relay On/Off Compressor B2 Relay On/Off Minimum Load Valve Relay On/Off CIRC. B DISCRETE INPUTS Compressor B1 Feedback On/Off Compressor B2 Feedback On/Off CIRCB_AN (Circuit B Analog Parameters) DESCRIPTION VALUE CIRCUIT B ANALOG VALUES...
  • Page 79 ALARMDEF (Alarm Definition Table) DESCRIPTION VALUE Alarm Routing Control 00000000 Equipment Priority 0 to 7 Comm Failure Retry Time 1 to 240 Re-alarm Time 1 to 255 Alarm System Name XXXXXXXX BRODEFS (Broadcast POC Definition Table) DESCRIPTION VALUE SCN Time/Date Broadcast Yes/No SCN OAT Broadcast Yes/No...
  • Page 80 OPTIONS1 (Options 1 Configuration) DESCRIPTION VALUE Cooler Fluid 1 = Water 2 = Med. Brine Minimum Load Vlv Select No/Yes Return Gas Sensor Enable Dsable/Enable Motormaster Select No/Yes Cooler Pump Control Off/On Cooler Pump 1 Enable No/Yes Cooler Pump 2 Enable Dsable/Enable Cooler Pmp Periodic Strt No/Yes...
  • Page 81 RESETCON (Temperature Reset and Demand Limit) DESCRIPTION COOLING RESET Cooling Reset Type 0 = No Reset 1 = 4-20 mA input 2 = External temp – OAT 3 = Return Fluid 4 = External temp - SPT 4-20 MA RESET 4-20 –...
  • Page 82 DESCRIPTION VALUE Compressor A1 Size 8 to 15 Compressor A2 Size 0 to 15 Compressor B1 Size 0 to 15 Compressor B2 Size 0 to 15 Suction Superheat Setpt 10 to 40 Refrigerant 1 = R22 Fan Staging Select 1 = 1 Fan 2 = 2 Fans 3 = 3 Fans 4 = 4 Fans...
  • Page 83 CURRMODS: Maintenance Display DESCRIPTION FSM controlling Chiller On/Off WSM controlling Chiller On/Off Master/Slave control On/Off Ramp Load Limited On/Off Timed Override in effect On/Off Low Cooler Suction TempA On/Off Low Cooler Suction TempB On/Off Slow Change Override On/Off Minimum OFF time active On/Off Dual Setpoint On/Off...
  • Page 84 LEARNFNS: Maintenance Display DESCRIPTION VALUE Fan 1 Delta SCT point 1 snnn.n Fan 1 Delta SCT point 2 snnn.n Fan 1 Delta SCT point 3 snnn.n Fan 1 Delta SCT point 4 snnn.n Fan 1 Delta SCT point 5 snnn.n Fan 2 Delta SCT point 1 snnn.n Fan 2 Delta SCT point 2...
  • Page 85 PM-COIL: Maintenance Display DESCRIPTION VALUE Coil Cleaning Srvc Inter nnnnnn Coil Service Countdown nnnnnn Coil Cleaning Maint.Done Yes/No Coil Cleaning Maint.Date mm/dd/yy hh:mm Coil Cleaning Maint.Date mm/dd/yy hh:mm Coil Cleaning Maint.Date mm/dd/yy hh:mm Coil Cleaning Maint.Date mm/dd/yy hh:mm Coil Cleaning Maint.Date mm/dd/yy hh:mm PM-PUMP: Maintenance Display DESCRIPTION...
  • Page 86 RUNTEST: Maintenance Display DESCRIPTION VALUE Percent Total Capacity Percent Available Cap. Discharge Pressure nnn.n Suction Pressure nnn.n Calculated HP Setpoint A nnn.n Saturated Condensing Tmp nnn.n Saturated Suction Temp nnn.n Compr Return Gas Temp nnn.n Suction Superheat Temp nnn.n Compressor A1 Relay On/Off Compressor A2 Relay On/Off...
  • Page 87 STRTHOUR: Maintenance Display DESCRIPTION VALUE Machine Operating Hours nnnnnn Machine Starts nnnnnn Circuit A Run Hours nnnnnn Compressor A1 Run Hours nnnnnn Compressor A2 Run Hours nnnnnn Circuit B Run Hours nnnnnn Compressor B1 Run Hours nnnnnn Compressor B2 Run Hours nnnnnn Circuit A Starts nnnnnn...
  • Page 88 WSMDEFME: Maintenance Display DESCRIPTION VALUE WSM Active? Chilled water temp snn.n Equipment status Commanded state Enable Dsable None CHW setpoint reset value nn.n Current CHW setpoint snn.n UNITS POINT NAME WSMSTAT °F CHWTEMP CHLRST CHLRENA CHWRVAL °F CHWSTPT...
  • Page 89: Starters

    FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP, OVERLOAD UNIT RELAY (CA1) VOLTAGE VOLTAGE SIZE SETTING FOR V-PH-Hz SERIES 30RA COMPRESSOR 575-3-60 -100 15.5 380-3-60 -200 24.2 230-3-60 -400 37.1 208/230-3-60 -500 41.2 460-3-60 -600 19.2 230-3-50 -800 40.9 380/415-3-50 -900 23.8 575-3-60 -100 22.7...
  • Page 90: Starters

    FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP, OVERLOAD UNIT RELAY (CA1) VOLTAGE VOLTAGE SIZE SETTING FOR V-PH-Hz SERIES 30RA COMPRESSOR 230-3-50 -800 31.4 380/415-3-50 -900 17.4 575-3-60 -100 14.6 380-3-60 -200 22.7 230-3-60 -400 35.3 208/230-3-60 -500 39.2 460-3-60 -600 17.5 230-3-50 -800 49.9...
  • Page 91: Appendix C - Building Interface

    Building Interface — The 30RAN chiller can be inter- faced with multi-vendor control systems through 3 levels of inter-operability using BAClink, DataPort™, or DataLink™ controls. BAClink controls function as a gateway between a SCN and a BACnet™ system to facilitate the passing of data from the SCN to BACnet.
  • Page 92 LEGEND NA — Not Available RO — Read Only RW — Read/Write Copyright 2003 Sterling Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 533-00047...
  • Page 93: Project Information

    START-UP CHECKLIST FOR 30RA LIQUID CHILLER I. Project Information JOB NAME ______________________________________________________________________________ ADDRESS _______________________________________________________________________________ CITY ____________________________________________ STATE _______________ ZIP______________ INSTALLING CONTRACTOR ________________________________________________________________ SALES OFFICE ___________________________________________________________________________ START-UP PERFORMED BY ________________________________________________________________ Design Information CAPACITY CEAT UNIT MODEL ______________________________ SERIAL ________________________________ II. Preliminary Equipment Check IS THERE ANY PHYSICAL DAMAGE? DESCRIPTION ____________________________________________________________________________ ________________________________________________________________________________________...
  • Page 94: Unit Start-Up

    5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER. 6. CHILLED WATER FLOW SWITCH IS OPERATIONAL. 7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40). 8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C). ANTIFREEZE TYPE _____________________ CONCENTRATION __________%. IF OUTDOOR AMBIENT IS BELOW 32 F (0°...
  • Page 95: Operating Data

    OPERATING DATA: RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN MACHINE IS IN A STABLE OPERATING CONDITION: PRESSURE/TEMPERATURE DISCHARGE PRESSURE SUCTION PRESSURE SATURATED CONDENSING TEMP SATURATED SUCTION TEMP LIQUID LINE TEMPERATURE* DISCHARGE LINE TEMPERATURE* RETURN GAS TEMPERATURE* *Readings taken with a digital thermometer.
  • Page 96 Record Software Versions MODE — RUN STATUS SUB-MODE ITEM DISPLAY VERS MARQ NAVI (PRESS ENTER & ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS) COMMENTS: _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ SIGNATURES:...
  • Page 97: Record Configuration Settings

    III. Unit Start-Up (cont) RECORD CONFIGURATION SETTINGS SUBMODE ITEM UNIT SZA.1 SZA.2 SZB.1 SZB.2 SH.SP REFG FAN.S PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: SUBMODE ITEM OPT1 FLUD MLV.S MMR.S...
  • Page 98 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. SUBMODE ITEM OPT2 CTRL SCNA SCNB BAUD LOAD LLCS LCWT DELY ICE.M CLS.C LS.MD LS.ST LS.ND LS.LT SUBMODE ITEM...
  • Page 99 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: SLCT (Setpoint and Ramp Load Configuration) SUBMODE ITEM SLCT CLSP RL.S CRMP SCHD Z.GN PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE ARROW KEYS TO SCROLL TO THE SET POINT LED.
  • Page 100: Component Test

    NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Copyright 2003 Sterling Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Table of Contents