Technical data

6.4 Error codes

If, contrary to expectations, a device error should occur, error codes will ap-
pear on the display. Some of these are described below:
Error code
E.01
E.02
E.07
E.xx
isoRW425_D00052_01_M_XXEN / 03.2014
Meaning
PE connection error
Action:
Check connection, eliminate error. The error code will be
erased automatically once the error has been eliminated.
Connection error system,
Connection error polarity in DC systems
(an error will only be indicated when U
Action:
Check connection, eliminate error.
The error code will be erased automatically once the
error has been eliminated.
Permissible system leakage capacitance
of 300 μF exceeded
Action:
Device not suitable for the existing leakage capacitance:
uninstall device.
Device error
Action:
If necessary, eliminate connection error, otherwise per-
form reset. Restore the device to the factory setting. The
error code will be erased automatically once the error
has been eliminated.
Should the error persist, contact Bender Service.