Emergency Mode / Motor Error

Armstrong International
221 Armstrong Blvd., Three Rivers, Michigan, 49093 - USA
armstronginternational.com/brain
Maintenance to the DRV25 internal mechanism is
required. DRV25 continues to operate safely, but with
reduced performance. Check for the following:
Motor damage or signs of wear
Proportioning Assembly damage or signs of wear
Debris in the Drive Assembly
If this mode is not addressed then it is likely the DRV25
will stop working and develop into a critical motor error.
The following symptoms indicate motor / cable loom
failure or a malfunction of the positioning sensor. In the
first instance, power cycle/reboot the DRV25. If the error
persists, check for the following:
Internal PCBA connectors to DRV25 are
disconnected, damaged or possibly wet
Dirt or debris around motor
Motor is disconnected
Opto encoder is not coupled to the motor
Proportioning Assembly is sticking or has seized
Motor is loose
Drive belt is loose or dislodged
Replace in the following order if the problem still persists
after each:
1. P/N - D111636
2. P/N - D111639
3. P/N - D112643
4. P/N - D111638
5. P/N - D112645
see pages 33-39.
43
Dual Opto Motor Loom
Drive Belt
Front Cover Assy with PCBA
Stepper Motor
Drive Mechanism Assy