For bulkhead entry of electrically heated tubetrace bundles (5 pages)
Summary of Contents for Thermon Terminator DS/DE
Page 1
Terminator DS/DE In-Line Splice/End Termination Kit INSTALLATION PROCEDURES For In-Line Splice Connection and End Termination Applications...
Page 2
The National Electrical Code (NEC) and Canadian Electrical Code (CEC) require ground-fault protection of equipment for each branch circuit supplying electric heat tracing. • Installation must comply with Thermon requirements and be in- Item Quantity Description...
Page 3
Terminator DS/DE 300 mm 300 mm (12") (12") For one or two cables. Locate bus connection Two cables. (HPT and FP only) and cable as shown. Cut end of cable at angle to aid in piercing grommet. Leave additional cable for expansion loop. For one or two cables.
INSTALLATION PROCEDURES 100 mm (4") Cut off end of cable. Push excess cable back through expediter. Tape Terminate cable with appropriate PETK or SCTK cable expansion loop to pipe. termination kit. Refer to kit installation instruc- tions. PETK Kit for Power/End Terminations SCTK Kit for Splice Connections For splice connections: Connect bus wires using Tighten cap securely.
Page 5
THERMON . . . The Heat Tracing Specialists ® • • 100 Thermon Dr. PO Box 609 San Marcos, TX 78667-0609 • • Phone: 512-396-5801 Facsimile: 512-396-3627 1-800-820-HEAT In Canada call 1-800-563-8461 www.thermon.com Specifications and information subject to change without notice.