Electronic controllers for “forced air” refrigerating units

Advertisement

Quick Links

USER INTERFACE
The user has a display and four keys for
controlling status and programming of the
instrument.
KEYS AND MENUS
UP key
Scrolls through the menu
items Increases the values
Activates manual def. function
DOWN key
Scrolls through the menu items
Decreases the values
Programmable by parameter
fnc key
ESC function (exit)
fnc
Programmable by parameter
set key
Accesses the setpoint
set
Accesses the menus
Confirms the commands
Displaying the alarms (if present)
At start-up the instrument performs a
Lamp Test; for few seconds the display and
the leds blink, in order to verify their inte-
grity and correct operation. The instru-
ment has two main menus: the "Machine
Status" and "Programming" menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which
can be accessed by pressing and quickly
releasing the "set" key ("Machine Status"
menu) or by holding down the "set" key
for more than 5 seconds ("Programming"
menu).
To access the contents of each folder, indi-
cated by the relevant label, just press the
"set" key once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions.
If you do not use the keyboard for over
15 seconds (time-out) or if you press the
"fnc" key once, the last value shown on
the display is confirmed and you return to
the previous screen mask.
LED
Position
Related Function
Compressor or relay 1
Defrost
Alarm
Fans
ID 974
electronic controllers for "forced air" refrigerating
units
MACHINE STATUS MENU
To access the "Machine Status" menu
Press and quickly release the "set" key.
If alarms are not present, the label "SEt"
appears. By using the "UP" and "DOWN"
keys you can scroll through the other fold-
ers in the menu:
-Pb1: probe 1 value folder;
-Pb2: probe 2 value folder
-SEt: Setpoint setting folder.
Set Setting
Access the "Machine Status" menu by
pressing and quickly releasing the "set"
key. The label of the "SEt" folder appears.
To display the Setpoint value press the
"set" key again.
The value appears on the display.
To change the Setpoint value, use the "UP"
and "DOWN" keys within 15 seconds.
If the parameter is LOC = y the Setpoint
cannot be changed.
Alarm on
If alarm condition exists, when accessing
The "Machine Status" menu the "AL" fold-
er label appears (see the "Diagnostics"
section).
Displaying Probes
By pressing the "set" key when the appro-
priate label appears, the value of the pro-
be associated to it is displayed.
PROGRAMMING MENU
To enter the "Programming" menu, press
the "set" key for more than 5 seconds.
If specified, the access PASSWORD will be
requested, (parameter "PA1"), and the
label of the first folder will follow.
To scroll through the other folders, use
the "UP" and "DOWN" keys.
To enter the folder, press "set". The label
of the first visible parameter appears. To
scroll through the other parameters, use
the "UP" and "DOWN" keys; to change the
parameter, press and release "set", then
set the desired value using the "UP" and
"DOWN" keys, and confirm with the "set"
key to move to the next parameter.
Status
ON when the compressor is started up; blinking in case of delay,
protection or blocked enabling
ON when defrosting; blinking in case of manual
enabling
ON when the alarm is enabled; blinking when the alarm is silenced
ON when the fan is working
PASSWORD
The password allows access to program-
ming parameters. In the standard configu-
ration password is not present.
To enable and assign it the desired value,
access the "Programming" menu, within
the folder with the "diS" label. If pass-
word is enabled, you will see it at the
entrance of the "Programming" menu.
MANUAL ACTIVATION OF THE
DEFROSTING CYCLE
To manually activate the defrosting cycle,
press the "UP" key for 5 seconds.
If defrosting conditions are not present,
(for example the evaporator probe
temperature is higher than defrost stop
temperature), the display
will blink three (3) times, in order to
indicate that the operation will not be
performed.
COPY CARD
The Copy Card is an accessory connected
to the TTL serial port which allows pro-
gramming quickly the instrument parame-
ters. The operation is performed as fol-
lows:
Format
This command allows copy card formatting,
an operation recommended in case of first
use.
Warning: if the copy card has been pro-
grammed, using the "Fr" the data entered
are erased. This operation cannot be can-
celled.
Upload
This operation loads the programming
parameters from the instrument.
Download
This operation downloads to the instru-
ment the programming parameters.
The operations are performed accessing
the folder identified by the "FPr" label and
selecting, according to the case, "UL", "dL"
or "Fr" commands; the operation is con-
firmed by pressing the "set" key. If the
operation is successful an "y" is displayed,
on the contrary, if it fails a "n" will be dis-
played.

Advertisement

loading
Need help?

Need help?

Do you have a question about the ID 974 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eliwell ID 974

  • Page 1 ID 974 electronic controllers for “forced air” refrigerating units USER INTERFACE MACHINE STATUS MENU PASSWORD To access the “Machine Status” menu The password allows access to program- The user has a display and four keys for Press and quickly release the “set” key.
  • Page 2 For the capacity of the terminals, see the - use on boards which do not guarantee label on the instrument. adequate protection against electric shock, ID 974 LX...
  • Page 3 2 = visualizza la label “deF” durante lo sbrinamento e fino al successivo raggiungimento del valore di Setpoint. display read-out. Selezione °C o °F per la visualizzazione temperatura letta dalla sonda. flag 0 = °C, 1 = °F. ID 974 LX...
  • Page 4 ** LEVEL column: indicates the level of visibility of parameters accessible by PASSWORD (see the related paragraph) Wiring diagram TERMINALS Common relay contact N.A. defrost relay ID 974 - 12 V N.C. defrost relay Compressor relay output Fan relay output 6 - 7...