8. Troubleshooting
8.3. Troubleshooting Sequence
Error code
(Dec)
CH0
CH1
23
123
Sampling Count value range exceeded
24
124
Compared output 0 type range exceeded
25
125
Compared output 1 type range exceeded
26
126
Preset value exceeded counter range
Ring counter minimum value ≥ Ring counter
27
127
maximum value input
Compared output0 minimum value exceeded
28
128
maximum input range
Compared output0 maximum value exceeded
29
129
maximum input range
Compared output 0 minimum Value >
30
130
compared output 0 maximum value set
Compared output1 minimum value exceeded
31
131
maximum input range
Compared output1 maximum value exceeded
32
132
maximum input range
Compared output1 minimum Value >
33
133
compared output1 maximum value set
34
134
Pulses per revolution range exceeded
35
135
Frequency input mode range exceeded
200
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
Description
Honeywell
Action
Set section count value to (0-60000) (only if
Auxiliary Mode type selected is sampling count or
revolutions per Unit time )
Set compared output 0 type to (0-6)
Set compared output 1 type to (0-6)
Set preset value within counter range
Set to Ring counter minimum value < maximum
value range (if counter type of Ring counter
selected)
Set compared output0 minimum Value/maximum
value) within counter range
Set to compared output0 minimum value <
maximum value range
Set compared output1 minimum value (maximum
value) within counter range
Set compared output1 minimum value < compared
output1 maximum value range setting
Set pulses per revolution to (1-60000). (Only if
Auxiliary Mode type selected is revolutions per
hour measurement)
Set frequency input mode to (0-3). (Only if
Auxiliary Mode type selected is input frequency
measurement )
R200
May 2010