Download Print this page

Philips B200G Installation And Operating Instructions Manual page 4

Industrial duty emergency unit

Advertisement

Page 4 of 7
10. Hookup AC service to the unit as follows: Caution: Do not connect AC until battery is installed.
White Wire
Black Wire
Blue Wire
Green Wire
OPERATING INSTRUCTIONS
Energize AC power to the unit. The unit will initiate normal power-up sequence (See Normal Power Up
Sequence).
Self-Diagnostic System Operation – Emergency Light or EXIT Sign Products
Normal Power Up Sequence
At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute
a "Power Up Quick Test" causing the green LED indicator to flash rapidly. If any faults are detected during the "Power Up
Quick Test" these will be evident by a flashing red LED indicator. If the audible diagnostic option has been ordered, the
flashing red LED will be accompanied by a simultaneous beeping tone. (Note: A continuous rapid alternating Red/Green
flash with rapid beeping tone indicates 277V applied to 120V input lead. TURN OFF POWER IMMEDIATELY!)
Philips Lighting Company
200 Franklin Square Drive
Somerset, NJ 08873
Phone: 855-486-2216
www.philips.com/luminaires
120 V
OPERATION
AC
- Common
- 120V Line
- Cap Wire
- Ground
277 V
AC
White Wire
Black Wire
Blue Wire
Green Wire
Figure 3
Philips Lighting Company
281 Hillmount Road
Markham ON, Canada L6C 2S3
Phone: 800-668-9008
www.philips.com/luminaires
OPERATION
- Common
- Cap Wire
- 277V Line
- Ground

Advertisement

loading