ECOCONDENS SILVER PLUS
The figure above shows an example of display with error code E 01 with symbols reset and
5.8.4. Error list
Error code
No flame on the burner:
3 automatic reignition attempts are taken (for LPG - 2
attempts). Each attempt is preceded by 30 sec. break for
ventilation of the boiler. After the failure of attempts follows:
switching off the boiler with blockade, displaying the symbol E
RESET
No flame on the burner:
Turning off the boiler with blockade after unsuccessful
attempts of gas ignition. The reason of failure may be:
1. Lack of gas.
2. Erroneous connection to power source (phase detection)
The water temperature in the gas-water heat exchanger
exceeds 95 ° C.
The boiler is turned off with a blockade.
The flue gas temperature has exceeded the permitted
value. The one-time thermal fuse was burned off and the
boiler was switched off with blockade.
Damage in the circuit of NTC sensor of heating water
temperature.
The burner is turned off.
Failure in the electronic system of the boiler.
The burner is turned off
Failure of the measuring system of fan speed or failure of
the fan.
Failure of water pressure transducer (in CH system)
The burner is turned off, the pump operates for 180 sec.
Incorrect pressure in CH system.
if:
operates for 180 sec,
operates for 180 sec,
if:
Failure in the circuit of NTC temperature sensor (in DHW
system).
The burner is turned off.
Error cause
01
P > 2.8 bar - controller turns off the burner, the pump
P < 0.5 bar - controller turns off the burner, the pump
P <= 2.5 bar - return to the normal operation.
P >= 0.5 bar - return to the normal operation.
ISU-646:2016/GR-H
The boiler is in the process of gas ignition tests
When the pressure in CH is higher than 2.8 bar
The pressure may be to high if there has been
to high initial pressure in the system or if there
occurred damage in the compension vessel.
If the pressure in the CH system is below 0.5
bar you should fill in the system with water and
Way of error removing
and will return to normal operation.
Check if the gas cocks are opened
and if the gas reaches the boiler.
Press reset button
To fix: - turn off power
- switch lines of power cable
Press reset button
Call Authorized Service Company
Call Authorized Service Company
Call Authorized Service Company
Call Authorized Service Company
Call Authorized Service Company
some water should be drained
from installation.
check for leaks
Call Authorized Service Company