Page 4
Limited Warranty and Limitation of Liability Your Amprobe product will be free from defects in material and workmanship for 1 year from the date of purchase, unless local laws require otherwise. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling.
KTS1625 Digital Multifunction Tester PFC PSC LCD Display Test Button Function Buttons (F1, F2, F3, F4) Rotary Switch F1: Display Backlight COM / N Terminal(Black) Continuity Buzzer L / V / Ω Terminal(Red) 0° or 180° phase selection for RCD test...
Page 6
Screen Display 13 14 15 2 3 4 5 7 8 9 PFC PSC L – N or L – PE Loop Test Fault Voltage Between N and PE Conductor Exceeds 50V Presence of Hazardous Voltages RCD Ramp Test Continuity Buzzer Low Battery Indicator Over-temperature! Allow Noise Between N and PE Conductor...
KTS1625 Digital Multifunction Tester CONTENTS SYMBOL .........................2 SAFETY INFORMATION ..................2 UNPACKING AND INSPECTION ................3 FEATURES .......................4 MAKING MEASUREMENT ..................5 Rotary Switch Positions ..................5 Function Buttons ....................6 Measuring AC Voltage ..................8 Measuring Insulation Resistance ..............9 Measuring Continuity ..................11 Measuring Loop Impedance ................14 Measuring RCD Tripping Time .................17...
SYMBOLS Caution ! Risk of electric shock. � Caution! Refer to the explanation in this Manual The equipment is protected by double insulation or reinforced insulation Do not use in distribution systems with voltages higher than 440V Earth (Ground) Battery �...
Page 9
CENELEC Directives The instruments conform to CENELEC Low-voltage directive 2006/95/EC and Electromagnetic compatibility directive 2004/108/EC X� Warning: Read Before Using • To avoid possible electrical shock or personal injury, follow these instructions and use the Meter only as specified in this manual. •...
They are critical to prevent loss of productivity due to power interruption. Robin-Amprobe KTS1625 is a multifunction installation tester measuring various parameters of the electrical system to provide complete safety analysis. It features loop impedance measurements as well as measurement of continuity and insulation resistance of motors, transformers or wires, testing of RCD systems, measuring voltage and frequency.
Rotary Switch Positions Switch Position Measurement Function Volts AC Voltage / Frequency measurement. 250V Insulation Resistance at DC 250V. Insulation 500V Insulation Resistance at DC 500V. 1000V Insulation Resistance at DC 1000V. Continuity Continuity measurement. Ω NO TRIP L – PE(PSC) or L – N(PFC) Loop impedance NO TRIP mode Loop L –...
Page 13
F2 Button “Test Lock” for continuous measurement. Press F2 to enable Test Lock mode ( symbol is shown on the screen) and press TEST button for continuous measurement. Under Test Lock mode, TEST button will hold for Dielectric Absorption Ratio Test (DAR) purpose. DAR value can be calculated by Riso(1min)/Riso(30s).
Error message display 1. Over-temperature: wait while the temperature cools down for next measurement 2. Fault Voltage: Check voltage between N and PE conductor. Measuring AC Voltage X� • To avoid personal injury or damage to the tester, do not apply voltage higher than 440V.
Page 15
F1 b u t t o n Figure 1: Measuring AC voltage by test leads...
Figure 2: Measuring AC voltage by 3-wire mains test cord Measuring Insulation Resistance X� • Make sure disconnecting circuit power and de-energize the circuit before test. • When measuring insulation resistance, make sure test leads are separated and are not twisted together. •...
Page 17
• When the measurement is completed, do not touch the circuit as the circuit may store energy, which may cause electric shock. Allow time for circuit to discharge • Warning buzzer will sound when the Tester detects a voltage >30Vac or ...
Figure 5: Measuring insulation resistance Measuring Continuity X� • Disconnect circuit power and de-energize the circuit before test. • Do not measure continuity at live high voltage circuit. • Do not carry out measurement when the battery compartment is open or accessible.
Page 19
Figure 6: Tester detects a voltage >30Vac Figure 7: Tester detects a voltage >30Vdc To measure continuity: 1. Turn the rotary switch to Continuity position. 2. Use the red and black (Ω – COM) terminals for this test with test leads. 3.
Page 20
4. Press TEST button The primary display shows the continuity resistance. The secondary (smaller digits on the right side) display shows the actual output DC voltage. When symbol on screen, buzzer threshold ≤ 20Ω ZERO Figure 8: Measuring continuity...
Measuring Loop Impedance X� • The Tester is designed for measurement on single phase system only – AC 230V, 50Hz (operating voltage range: AC 230V +10%/-15%, 50Hz). • Make sure the wiring is correct and the ground wire is reliably connected earth.
Page 22
1 button (NO TRIP only) (NO TRIP only) Figure 9: Measuring Loop by 3-wire mains test cord...
Page 23
NEUTRAL EARTH PHASE Figure 10: Measuring Loop by test leads Loop Impedance (Line to Protective Earth L-PE) To measure L-PE loop impedance: 1. Turn the rotary switch to Hi PSC position. 2. Use the red, green and black (L – PE – N) terminals for this test. You can use test leads or mains test cord when measuring loop impedance.
Measuring loop impedance NO TRIP mode: To prevent tripping RCDs in the circuit: • Use the NO TRIP function for loop measurements. • An RCD with a nominal fault current of 15mA or above will trip. To measure L-PE loop impedance NO TRIP mode: 1.
Page 25
Tester indicates >50V Uf having been generated by the measurement. The measurement interruption caused by excess of Uf is only generated by the actual voltage present between the neutral conductor (N) and the protective earth (E). • Time-delayed residual current devices trip at nominal residual current within 130…500ms, for double nominal fault current within 60…200ms.
Page 26
• “L-PE” and “N-PE” symbols blinking indicate missing PE wiring connection or incorrect wiring of PE conductor • “L-N” and “N-PE” symbols blinking indicate missing N wiring connection or incorrect wiring of N conductor F1 button F2 button F4 button 10mA 30mA 100mA...
Page 27
NEUTRAL EARTH PHASE Figure 12: Measuring RCD trip time by test leads To perform Auto RCD test: 1. Turn the rotary switch to AUTO position. 2. Use the red, green and black (L – PE – N) terminals for this test. You can use test leads or mains test cord when measuring loop impedance.
4. Press F2 to select waveform or selective mode (a 30 second time delay) Delayed response to test S-type AC (time delayed AC RCD) Half-wave current to test type A (pulse-DC sensitive RCD) Delayed response to S-type A (time delayed pulse-DC sensitive RCD) AC current to test type AC (standard AC RCD) 5.
Page 29
X1/2, X1 10mA, 30mA, 100mA, 300mA, 500mA 10mA, 30mA, 100mA, 300mA 10mA, 30mA, 100mA 10mA, 30mA 4. Press F1 button to select test current phase 0° or 180°. 5. Press F2 button to select waveform or selective mode Delayed response to test S-type AC (time delayed AC RCD) Half-wave current to test type A (pulse-DC sensitive RCD)
Using Test Probe with Remote Test Button This test probe with remote test button allows users to perform measurement by pressing TEST button on the probe when both hands are holding test probes during measurement. Below measurements can be made by using the test probe with remote test button: •...
SPECIFICATION Ambient temperature: 23°C ±5°C (73.4°F ±9°F); Relative temperature: ≤75% Accuracy: ±(% of reading + LSD) Display: maximum reading is 9999. Over-range indication: maximum reading Operating Condition: 0°C to +40°C, <85% Relative Humidity Storage Condition: -20°C to +60°C, <90% Relative Humidity Dimension (L x W x D): 189 ×...
Page 32
Continuity Measurement Range Range Test Voltage Accuracy (Auto ranging) 1.99Ω 0.01Ω >4Vdc 19.9Ω 0.1Ω >4Vdc ± (2% Rdg +5 LSD) 199Ω 1Ω >4Vdc Note: Measuring current (short-circuited) ≥ 200mA Nominal open-circuit output voltage: 5Vdc Buzzer threshold: 20Ω Live circuit detection: >30Vac or dc Test probe zeroing: can subtract up to 10Ω...
RCD Measurement Operating Rated Voltage: 195 – 253Vac, 45 – 65Hz RCD Test Current Selection Function Accuracy 10mA 30mA 100mA 300mA 500mA 0% to +10% at √ √ √ X1 and X5 AUTO -10% to 0% @ test √ √ 1/2X 50%~110% Default nominal...
Page 34
Note: *G – General, no delay *S – Time delay EN 61557 Measurement Range EN 61557 Function Display Range Measurement Range Nominal Values Operating Error 10Vac – 400Vac, Volts 100Vac – 400Vac, = 230Vac 45Hz – 65Hz EN 61557-1 45Hz – 65Hz f = 50Hz ±(5% + 2 LSD) = 250/ 500/...
MAINTENANCE AND REPAIR If the Tester fails to operate, check battery, test leads, etc., and replace as necessary. Double check the followings: 1. Check the battery. Replace the battery immediately when the symbol “ ” appears on the display. 2. Review the operating instructions for possible mistakes in operating procedure.
Page 36
Battery:1.5V Alkaline Batteries (AA or equivalent).