1436 cPos Intelligent Positioner and integrated Process Controller OPERATING INSTRUCTIONS Status 05.2019 From version 2.0.3.6 1436 cPos...
Page 2
Quick commissioning of the GEMÜ 1436 cPos: Prerequisites: ● Mounted to the valve. ● Air supply, max. 7bar, connected. ● 24 V DC supply voltage connected. ● Set value and actual value signals need not be connected. ● For correct commissioning proceed as described in the following flow chart:...
Control parameters RS232 – Interface 16.4 Adaptation of the controller to the controlled system 45 Operation 16.5 Differential equation for the GEMÜ 1436 cPos Operating and display elements 16.6 Effects of the control parameters on the control Menu levels system 7.2.1...
The manufacturer shall undertake no responsibility ● Only qualified and trained personnel should for the GEMÜ 1436 cPos if these safety notes are not assemble, electrically connect and commission observed. the GEMÜ 1436 cPos.
1.4 Correct use Manufacturer's information w The GEMÜ 1436 cPos is suitable for use as defined in the data sheet. In order to ensure correct product function, the 2.1 Transport following notes should be observed. Pay attention to the information on the product labels.
0-20 mA -com 4-20 mA Actual value input for position Communication interface control using the travel sensor Profibus DP / DeviceNet / Profinet Digital inputs (optional) (Function programmable) Supply voltage 24 V DC Operation Keypad 1436 cPos 6 / 66...
2. Push the spring over the spindle. 3. Fix the spindle at point a SW27 (the spindle must not be damaged during this process). 4. Screw the operating bush onto the spindle. Travel sensor and actuator 4.1.3 Mounting the positioner Travel sensor mounted on actuator 1436 cPos 7 / 66...
Travel sensor with marking View X, only travel sensor View X, only travel sensor used on positioner in the design with an external travel sensor View X 1436 cPos 8 / 66...
Should the display show that this range is being exceeded, not UV-resistant and must therefore be protected check the mechanical mounting again and readjust the against direct exposure to weather. orientation of the travel sensor, if necessary (see chapter 4.2.2 or 4.2.4). 1436 cPos 9 / 66...
1. Connect 24V DC supply voltage to plug X1. 2. Connect analogue input (set value input) 0/4-20 mA to plug 3. If operating as a process controller, connect analogue input (actual value input) 0/4-20 mA to plug X3. 1436 cPos 10 / 66...
* Switching output switches device supply voltage Uv - drop voltage ** For options code 01 6.7 Digital inputs The GEMÜ 1436 cPos makes it possible to use digital inputs 6.1 Version with external actual value for specific functions. potentiometer (code S01) It is also available to order with two exclusively digital inputs.
R=1.2KΩ±5% Pv=1W I-, actual value input 6.8 Digital inputs (optional) The GEMÜ 1436 cPos has four digital inputs when a digital input card is installed. The actual value and set value inputs can be used as digital inputs under the following conditions:...
Minus-key Example: The operating mode is to be changed from OFF to Auto. 7.2 Menu levels The GEMÜ 1436 cPos uses two menu levels. These are the working level (Mode) and the configuration level (Setup). 7.2.1 Working level (Mode) The GEMÜ 1436 cPos is automatically at this level after the supply voltage is switched on.
While doing this, it is possible to choose between automatic initialisation and manual initialisation. When connecting the supply voltage, the following message is displayed by GEMÜ 1436 cPos after it has completed a short software check: NoInit XX.X% ـ...
"CtrlFn" parameter. If the parameter is set to AUTO, An incorrect control Parameter "CtrlFn" is set for a fixed the 1436 cPos determines the Wrong function function was recognised control function. This set control function corresponding control function and...
9.3 Initial commissioning with factory setting (positioner supplied mounted to the valve) goOpen: The open valve position is scanned during initialisation. If the GEMÜ 1436 cPos was already fully mounted This function must be started with the key if initialising to a valve in the factory, it is already factory manually and then confirmed.
Page 18
A manual initialisation should only ever be carried out if you have not achieved satisfactory control characteristics with the automatic initialisation or this was aborted due to an error message. 1436 cPos 18 / 66...
10 Operating modes 10.5 Test mode (T:) Test mode serves for test purposes to enable quick access to The GEMÜ 1436 cPos uses the operating modes A: AUTO, the basic settings as a positioner. Parameter changes in the M: MANUAL, F: MANUAL-FLEX, T:TEST and OFF.
This menu is used to read out all information/diagnostics regarding the positioner, the connected signals and errors that occur. 2. SetBasics SetBasics is used to set the basic settings for the GEMÜ 1436 cPos such as the initialisation, selection of input signals and resetting to factory settings.
Page 21
11.3 Menu structure 1 Service 1436 cPos 21 / 66...
Page 25
11.7 Menu structure 5 Communication 1436 cPos 25 / 66...
Page 26
Submenu for displaying the tool identification Displays current software V:1.1.1.1 version Displays current serial S/N xxx number TAG1 11-digit ID number can be set TAG2 11-digit ID number can be set *Only for activated process controllers 1436 cPos 26 / 66...
Page 27
Safe / ON Determines the function of In 2 ParmSetB0 the digital input "In 2" ParmSetB1 Poti / Ix *Only for activated process controllers ** Parameter value is automatically calculated and set by the positioner during initialisation 1436 cPos 27 / 66...
Page 28
Delay time between warning Warn. Time recognition and warning 0.0 ... 100,0 s 0.0 s message Copies parameters to various CpyParaSet working memories (P1/P2/ P3/P4) Sets the function of analog AnalogOut Poti / Ix Poti output 1436 cPos 28 / 66...
Page 29
Auto RS 232 Auto connection Serial 38400 Defines the baudrate of the Bdrate RS 57600 115200 RS 232 connection 115200 *Only for activated process controllers ** Only relevant for Profibus DP, DeviceNet or Profinet versions 1436 cPos 29 / 66...
All parameters on the control system route must be checked. In w:x:1:2 Displays the current conditions of the digital inputs ( = Signal High). Relay: Displays the current position of the internal relays K1 and K2 ( = Relay switched). 1436 cPos 30 / 66...
Return Login I / O Status The configuration level of the GEMÜ 1436 cPos is protected in certain areas by various codes against improper changing of parameters. All menu items are marked by symbols indicating their write and read protection.
The codes for operation via the RS232-interface can only be assigned, activated or deactivated via the RS232-interface. The codes for direct operation via the GEMÜ 1436 cPos keypad can only be assigned, activated or deactivated via the keypad on the unit itself.
The help text language may be selected between D-German, GB-English and N-Norwegian. HelpText: The help texts that appear as a default in the second line of the display can be masked. If the help texts are masked, the key assignment is displayed. 1436 cPos 33 / 66...
Filtered signal input Avr: The actual value input signal is calculated by averaging. Unfiltered signal input Unfiltered signal input IxTime IxTime Filtered signal input Filtered signal input IxTime: Defines the filter time for the actual value input. 1436 cPos 34 / 66...
>2.0 (if the characteristic curve is 1:50) or >4.0 (if the characteristic curve is 1:25), in order to shut the valve fully. Current signal for Current signal for Memory which is ParmSetB1 ParmSetB0 read out 1436 cPos 35 / 66...
Sets the switch point in % under which output K1 is switched. AlarmMaxK1: Sets the switch point in % over which output K1 is switched. SSE1Time: Determines the delay time for output K1 between error recognition and error message for a permanent system deviation. 1436 cPos 36 / 66...
Memory 1 Memory 2 Memory 3 Memory 4 Factory settings The GEMÜ 1436 cPos automatically stores all parameters in working memory P1. 13.3.9 Defining the actual value output AnalogOut: Defining the function of the 4-20 mA actual value output. Poti: The actual valve position is emitted at the 4-20 mA output.
>2.0 (for characteristic 1:50) or >4.0 (for characteristic 1:25). SetW-free: Eleven calibration points on the control curve can be programmed as required. Y-Direction: Defines the direction of the process controller output (rising / falling). An inverted process control system can be realized. 1436 cPos 38 / 66...
Defines the point above which the set value signal activates an error message. I Min X: Defines the point below which the actual value signal activates an error message. I Max X: Defines the point above which the actual value signal activates an error message. 1436 cPos 39 / 66...
If you use a connection with a PC/laptop or industrial modem Serial If you use a connection with a PC/laptop Bdrate RS: Defines the baudrate of the serial connection. 38400 baud Bdrate RS 57600 baud 115200 baud (Werkseinstellung) 1436 cPos 40 / 66...
The positioner is in initialisation mode. leakage and carry out initialisation Error leakage was detected. again. The 1436 cPos tries to change the valve position, but it changes in the wrong ● Leakage in the system A failure of the direction.
0-20 mA 4-20 mA 4-20 mA 15.2 Switching the process controller on or off (optional) r0w0 SETUP w XX.X: x XX.X Mode AUTO Automatic operation Automatikbetrieb r0w3 Mode w XX.X: x XX.X Manual operation manueller Betrieb Mode Service SetBasics SetFunction r0w3 ProcCtrlMode: ON...OFF 1436 cPos 42 / 66...
Page 43
15.3 Changing the control parameters (Proc P, Proc I, Proc D and Proc T) 1436 cPos 43 / 66...
"manually" by trial and error through experimentation or rule of thumb. Proc D: Slows down the manipulated variable y when Larger: Explanation of parameters of GEMÜ 1436 cPos: moving to the set value. Control is slower. Smaller: Set value is achieved faster. Proc P: K...
16.7 Control characteristics and transitory responses Transit function Sprungfunktion Control response Transitory response Regelverhalten Sprungantwort D component I component P component D-Anteil I-Anteil P-Anteil ≈T 1436 cPos 46 / 66...
Determines the function of the digital In 1 input "In 1" Determines the function of the digital In 2 input "In 2" K1 Switch Defines the type of output K1 K1 Fn Determines the function of output K1 1436 cPos 47 / 66...
Page 48
0/4mA signal Defines the display which corresponds 20 mA ≙ 100 % to a 20mA signal Configuration Display Function Factory settings level Submenu for setting the fieldbus 5 Communication Fieldbus address if available 1436 cPos 48 / 66...
Please contact us at the address on the last page for staff training information. Should there be any doubts or misunderstandings in the preceding text, the German version of this document is the authoritative document 1436 cPos 49 / 66...
- Operating hours counter, event list (for details see Transmission rates 125k / 250k / 500k Baud operating instructions) Profibus DP Parameterisation / process data - Digital inputs (option) for variable function control for Transmission rates 100 M Baud automation 1436 cPos 50 / 66...
22 Order data Note The GEMÜ 1436 cPos positioner can be directly or remotely mounted to linear or quarter turn actuators Direct mounting For direct mounting the following components are required which must be ordered separately: Linear actuators Quarter turn actuators Positioner GEMÜ...
Page 52
Order example 1436 SA01 Type 1436 Fieldbus (code) Accessory Action (code) Device version (code) SA01 Options (code) Flow rate (code) Travel length (code) 1436 cPos 52 / 66...
Page 54
1436S01Z211503000 R690 80-100 1436S01Z551305000 R690 80-100 1436S01Z562505000 R690 80-100 1436S01Z562505000 SUPM 1436S01Z292403000 Footnote 1) For control function DA use double acting positioner (action code 3). 4) For control applications use positioner with K number 2442 1436 cPos 54 / 66...
Page 55
Hole spacing 80x30, shaft height 30 Hole spacing 130x30, shaft height 30 Hole spacing 130x30, shaft height 50 Order example 1436 PTAZ Type 1436 Mounting kit (code) PTAZ NAMUR size (code) Measuring range (code) Control air connector (code) 1436 cPos 55 / 66...
Page 56
Order code - 1436 000 ZMP Connection kit GEMÜ 1436 S02 Z... Connection kit GEMÜ 1436 S02 Z... See order data - Connection kit See order data - Connection kit GEMÜ 1436 cPos Positioner GEMÜ 1436 S02Z Connection kit GEMÜ 1446 000 ZMP...
Page 57
Order example 4232 05M0 4001 Type 4232 Fieldbus Accessory Housing material (code) Travel length (code) Cable length (code) 05M0 Cable connection (code) 4001 1436 cPos 57 / 66...
(open, close, hold) (open, close, hold) under I Min X) Actual value > 20.0 mA (Range adjustable from 0...22 mA under I Max X) No. 3 and 4 only available for device version code PA01 1436 cPos 61 / 66...
24 Application examples 24.1 GEMÜ 1436 cPos as process controller with 4-wire transmitter (GEMÜ 3021) 24 V DC 24 V DC 1436 cPos Intelligent positioner Power supply 1436 cPos Intelligenter Stellungsregler Spannungsversorgung Intelligenter Stellungsregler Spannungsversorgung Intelligent positioner power supply Four wire flowmeter 4-Leiter Durchflussmessgeräte 4-Leiter Durchflussmessgeräte four wire flowmeter 4-20 mA...
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG Fritz-Müller-Straße 6-8 D-74653 Ingelfingen declare that the product listed below complies with the following directive: • EMC Directive 2014/30/EU Product: GEMÜ 1436 Joachim Brien Head of Technical Department Ingelfingen-Criesbach, September 2016 1436 cPos 63 / 66...