Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x

SW mode 1735 - 1587

The Alert Annunciation Unit 1735 has to run in SW mode 1735 –
1587. 1735 succeeds the existing Display unit with alert annunciation
2235SE (with Swedish designation texts) but not as a spare part, since
the 2235SE unit is connected to a COM loop.
In system EBL512, 1735 units running in SW mode 1735 – 1587 have
to be connected to an Ext. FBP / DU interface board 1587 mounted
in the EBL512 c.i.e. EBL512 software version > 2.2 is required.
In system EBL128, 1735 units running in SW mode 1735 – 1587 are
connected directly to the main board connector "J1" but an optional
RS485 transceiver component 4552 has to be plugged on the main
board.
In system EBL512 G3, 1735 units running in SW mode 1735 – 1587
are connected directly to the main board connector "J4".

Alert Annunciation Unit 1736

Figure 2. The Alert Annunciation Unit (AAU) 1736. A neutral
front where the designation texts, by production, are made
separately and put into the transparent "text slot" for the LED
and push button respectively. (It also holds one extra LED &
two extra push buttons.)
The Alert Annunciation Unit consists of a compact size enclosure
made of grey (RAL 7035) high impact ABS, with temperature
resistance up to 85° C. Fitted with a supplementary "O" ring gasket, it
will comply with IP65, in respect of dust and moisture. The unit has
no door, i.e. the front is accessed directly, when required. The push
buttons are disabled until they are supposed to be used, i.e. when an
AA alarm is activated. The unit shall be wall mounted. The unit is
intended for indoor use and in dry premises. Two compression glands
TET 7-10 (IP67) for cable inlets are attached.

SW mode 1736 - 1587

The Alert Annunciation Unit 1736 has to run in SW mode 1736 –
1587. 1736 succeeds the existing Display unit with alert annunciation