Page 1
• “Low Flow”: from 78 l/h up to 1722 l/h; • “High Flow”: from 244 l/h up to 8586 l/h. Pagina 1 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...
After DPC cartridge removal and manual full opening of the valve, it is possible to flush the system branch where the valve is installed; when flushing process is over, reposition the DPC control cartridge. Pagina 2 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...
Screw the plastic cap completely to open the valve and achieve the required flow rate 777). alternatively, assemble the electric actuator for modulating purposes (Cim Pagina 3 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...
Cim 777 776. The following table shows the dimensions of the full range of valves Picture 3 1/2” 95,5 3/4” 96,5 1” 102,5 1”1/4 1”1/2 2” Pagina 4 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...
With continuous modulation, control is excellent even with small flow opening. This eliminate on/off effect. Presetting dial Calibrated flow cartridge Picture 4 Picture 5 Pagina 5 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...
Page 6
Actuating force: 250 N; Input impedance: › 100 k Ohm (DC 0-10v); Actuating time: 150s for 3 positions version; 75s for proportional 0-10V version. Picture 6 Pagina 6 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...
Page 7
Actuating force: 400 N; Input impedance: › 100 k Ohm (DC 0- 10v); Actuating time: 170s for 3 positions version; 43s for 0-10V proportional version. Picture 7 Pagina 7 di 16 Technical leaflet Cim 776 & Cim 777 Revisione 0 Emissione 03/2011...