Electrical Data - Mitsubishi Electric CLIMAVENETA NECS-ME Series Technical Bulletin

Condenserless chiller
Table of Contents

Advertisement

6.

ELECTRICAL DATA

Size
0152
0182
0202
0252
0262
0302
0352
0412
0452
0512
0552
0604
0612
0704
0804
0904
1004
1104
1204
1404
1604
F.L.I.
Full load power input at max admissible condition
F.L.A. Full load current at max admissible condition
L.R.A. Locked rotor amperes for single compressor
S.A.
Starting current
(1) Values calculated referring to the version with the maxi-
mum number of fans working at the max absorbed current
(2) Safety values to be considered when cabling the unit for
power supply and line-protections
Compressor
n
F.L.I.
F.L.A.
[kW]
2
2x9
2x15.3
2
2x10.1
2x16.4
2
2x11.8
2x20.4
2
2x13.2
2x22.6
2
2x14.4
2x25.5
2
2x17
2x30.5
2
1x17+1x22.3
1x30.5+1x36.1
2
2x22.3
2x36.1
2
1x22.3+1x27.4
1x36.1+1x45.8
2
2x27.4
2x45.8
2
1x27.4+1x35.8
1x45.8+1x58.9
4
4x17
4x30.5
2
2x35.8
2x58.9
4
2x17+2x22.3
2x30.5+2x36.1
4
4x22.3
4x36.1
4
2x22.3+2x27.4
2x36.1+2x45.8
4
4x27.4
4x45.8
4
2x27.4+2x35.8
2x45.8+2x58.9
4
4x35.8
4x58.9
4
2x35.8+2x46.5
2x58.9+2x73.6
4
4x46.5
4x73.6
NECS-ME
Maximum values
L.R.A.
[A]
[A]
2x95
2x111
2x118
2x118
2x140
2x173
1x173+1x225
2x225
1x225+1x272
2x272
1x272+1x310
4x173
2x310
2x173+2x225
4x225
2x225+2x272
4x272
2x272+2x310
4x310
2x310+2x394
4x394
Power supply:
Voltage tolerance:
Maximum voltage unbalance: 3%
19
Total unit (1) (2)
F.L.I.
F.L.A.
[kW]
[A]
18
30.6
20.2
32.8
23.6
40.8
26.4
45.2
28.8
51
34
61
39.3
66.6
44.6
72.2
49.7
81.9
54.8
91.6
63.2
104.7
68
122
71.6
117.8
78.6
133.2
89
144.4
99
163.8
110
183.2
126
209.4
143
235.6
164.6
265.0
186
294.4
400/3/50
10%
NECS_ME_0152_1604_201004_GB
S.A.
[A]
110
127
138
141
166
204
256
261
308
318
356
265
369
322
333
390
409
461
487
585
615
HFC R410A