Model ESFR-1
14.0 K-Factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-1 Pendent Sprin-
klers are Early Suppression, Fast
Response (ESFR) sprinklers having
a nominal K-factor of 14.0. They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage.
Model ESFR-1 Sprinklers are primarily
designed for protection of the following
storage arrangements:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• some storage arrangements of
rubber tires, roll paper, flammable
liquids
For more specific criteria, refer to
Table A as well as the applicable design
standard.
Applications for the TYCO ESFR Sprin-
klers are expanding beyond currently
recognized installation standards. For
information on research fire tests (with
flammable liquids and aerosols, for
example) that may be acceptable to an
authority having jurisdiction, contact
the Tyco Fire Protection Products
(TFPP) Technical Services.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
NOTICE
The
Model
ESFR-1
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authorities
having jurisdiction (e.g., FM Global).
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA,
FM Global installation standard, or
other applicable standard, must be
referenced to ensure applicability and
to obtain complete installation guide-
lines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Sprinkler
Identification
Number (SIN)
TY6226
TY6226 is a re-designation for Central
SIN C6226, Gem SIN G8440, and Star
SIN S8000.
MARCH 2015
Sprinklers
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Approved (Cert. Nos. 094b and
007l)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT
Discharge Coefficient
K=14.0 gpm/psi
Temperature Ratings
165°F (74°C) and 212°F (100°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Sealing Assembly . Beryllium Nickel w/TEFLON
1/2
1/2
(201,6 lpm/bar
)
TFP318

Advertisement

loading
Need help?

Need help?

Do you have a question about the ESFR-1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco ESFR-1

  • Page 1 TYCO Model ESFR-1 Pendent Sprin- ble standards of the National Fire Pro- klers are Early Suppression, Fast tection Association (NFPA), in addition...
  • Page 2 The following general guidelines pro- tion (e.g., smooth ceiling, bar joists, the rated temperature is reached, the vided for the TYCO ESFR-1 Sprinklers beam and girder, and so forth) solder melts and the two link halves can be used for quick reference.
  • Page 3 Link Assembly, and handle using the appropriate sprinkler wrench. W-TYPE 2 Failure to do so can lead to an unstable the Model ESFR-1 Sprinkler only by the SPRINKLER WRENCH Frame arms. link assembly and premature activation of the sprinkler. Damaged sprinklers Step 2.
  • Page 4 Care and Limited Ordering Maintenance Warranty Procedure TYCO Model ESFR-1 Early Suppres- For warranty terms and conditions, visit Contact your local distributor for avail- sion, Fast Response 14.0K Pendent www.tyco-fire.com. ability. When placing an order, indicate Sprinklers must be maintained and ser- the full product name and part number viced in accordance with this section.