Micatrone MF-PFTT Operating And Installation Manual

Programmable differential pressure transmitter for pressure or flow measurement and control with purging function for flow sensors

Advertisement

Quick Links

Programmable differential pressure transmitter
for pressure or flow measurement and control
with purging function for flow sensors.
NOTE !
Read the entire instruction carefully before start.
Application
MicaFlex PFTT is a pressure and flow transmitter
with built in PI-controller and a temperature input
which makes it possible to compensate flow mea-
surement for temperature changes.
MF-PFTT can be programmed to activate a purging
unit, MF-PU-2, for automatic cleaning of flow sen-
sors with compressed air on set intervals.
With the four key pad, ¹, ¸, PGM and ESC
sired function is selected as well as setting and scal-
ing is done. The dual row LCD display clearly indi-
cates the selected function.
Installation
MF-PFTT is designed to be placed on a wall or for
recessed mounting through a wall or cabin door.
When
recessed
mounting,
MFM-PANEL is used. The unit is fixed to the wall by
four screws, max 4 mm. The location of the holes is
shown at the back of the enclosure.
Unscrew the four screws of the front cover and use
the bottom screws to attach the front cover on the
upper end of the casing, see Fig 2. This makes in-
stallation and electrical connection easier.
Connect power supply according to the electrical
connection.
To each front cover the CPU is mounted, since the
I/O calibration of the main circuit board is stored on
the CPU-board, it is not possible to move the front
cover between different units.
Output signal
MF-PFTT has two analogue outputs to be used for
actual value of pressure and flow, temperature,
purging unit or PI-control output for pressure or flow.
VDC or mA output signal must be set by the
DIL-switch (DIL1). The same programming must
then also be done under "Outputs".
PL1
L3
D1
DIL 1:
1 on, 2 off
3 on, 4 off
1 off, 2 on
3 off, 4 on
®
,
the de-
a
mounting
J5
ON
1 2 3 4 5
DIL1
Output/Utsignal
1
2
Fig 1
volt output 1
volt output 2
mA output 1
mA output 2
Operating and installation manual
Instruction : mi-261gb_090212
A
Use the front cover bottom screws (marked A) to fix the front
cover at the enclosures top edge during installation.
Basic programming instruction
kit,
When the power supply is connected a start menu
will be displayed. With ¹¸ it is possible to scroll
through the different start menus. To always have
the same start menu, the selection is programmed
under "System settings". Pressing ESC when some
other menu is displayed returns to the menu pro-
grammed under "Display".
Programming
Press PGM until "PROGRAM-MENU" appears. Re-
lease the key and the display shows parameter
group, see table on page 2.
With ¹¸ it is possible to scroll through the parame-
ter groups.
1. Current values
2. System settings
3. Outputs
4. Pressure
5. Flow
6. Temperature
7. PI2 controller
8. Purging unit
9. Communication
10. Internals
When the parameter group to be programmed is
shown, press PGM. The parameters are then
shown, with ¹¸ select the parameter to be pro-
grammed and press PGM.
MF-PFTT
A
Fig 2

Advertisement

loading
Need help?

Need help?

Do you have a question about the MF-PFTT and is the answer not in the manual?

Questions and answers

Summary of Contents for Micatrone MF-PFTT

  • Page 1 Use the front cover bottom screws (marked A) to fix the front Installation cover at the enclosures top edge during installation. MF-PFTT is designed to be placed on a wall or for recessed mounting through a wall or cabin door. Basic programming instruction...
  • Page 2 Par.no: Parameter Range Value Par.no: Parameter Range Value 33 Scale flw 0...32767 Internals 34 Set flow 0...32767 0 Prog ver 0.00...9.99 92 Compens Current values ACTUAL 100 dP -32768...32767 NORMAL 0 101 Flow -32768...32767 Temperature 102 PI2 0.00...100.00 93 Input 0..10V 103 PI2 CSP -32768...32767...
  • Page 3 Scrolls start menus 48,5Pa in the opposite way AB MICATRONE Flow 4,80m3/s Flow 4,80m3/s AB MICATRONE 48,5Pa 48,5Pa Flow 4,80m3/s 15,9% 20,4% Flow/dP Flow/dP Auto Hand Output % Press key until displayed text disappears. (PGM) Current values Scrolls parameter group in the opposite way...
  • Page 4 1. Current values key lock. 100 dP -32768...32767 Contact Micatrone if the code has been lost! 101 Flow -32768...32767 Entering code 102 PI2 0.00...100.00...
  • Page 5 4..20mA Sign for dP When measuring a negative pressure normally the MF-PFTT will show the same as measuring a positive Select the sources for the two analogue outputs. The pressure (no sign). When programming “Sign dP” NEG selection is possible between actual value of pres- you get a negative (-) sign before the actual value.
  • Page 6 5. Flow When the parameter is set to "ACTUAL", the letter "A" is displayed in front of the selected flow unit, e.g. Am3/s, and when set to "NORMAL 0", the letter "N" 31 Unit flow m3/s is displayed in front of the selcted flow unit, e.g. m3/h Nm3/h.
  • Page 7 DP/Flow If the PI-controller is not used, you do not need to do any programming under the parameter group “PI-controller”. MF-PFTT has a PI-controller specially made for Setpoint pressure and flow control. The controller has two I-time BZ programmable integral times.
  • Page 8 When zero set is ready, the unit displays ZERO OFFSET DONE and automatically returns to start menu. AB Micatrone Telephone: +46 8-470 25 00 Åldermansvägen 3 Fax: +46 8-470 25 99 SE-171 48 SOLNA Internet: www.micatrone.se SWEDEN E-mail: info@micatrone.se web reference - http://www.micatrone.se/prod_detail.php?lang=gb&id=53...