WIRING
Terminal
Terminal
Symbol
Name
Analog current
CA
output
Analog voltage
AM
output
(3) Communication
Terminal
Terminal Name
Symbol
-- --- --- ---- --- --- --
PU connector
TXD+
Inverter transmission
terminal
TXD-
RXD+
Inverter reception
terminal
RXD-
SG
Earth (Ground)
-- --- --- ---- --- --- --
USB connector
13
Description
Select one e.g. output frequency from monitor items.
Not output during inverter reset.
The output signal is proportional to the magnitude of
the corresponding monitoring item.
Use Pr. 55, Pr. 56, and Pr. 866 to set full scales for the
monitored output frequency, output current, and
torque.
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard : EIA-485 (RS-485)
. Transmission format
. Communication speed : 4800 to 38400bps
. Overall length
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard
Transmission format
Communication speed : 300 to 38400bps
Overall length
Non-connection
Output item:
Output
frequency
(initial
setting)
Description
: Multidrop
: 500m
: EIA-485 (RS-485)
: Multidrop link
: 500m
Rated Specifications
Load impedance 200 to
450
Output signal 0 to 20mADC
Output signal 0 to 10VDC
Permissible load current
1mA
(load impedance 10k or
more) Resolution 8 bits