Do you have a question about the CBW and is the answer not in the manual?
Questions and answers
paul jones
March 3, 2025
how to line up front door on the boiler
1 comments:
Mr. Anderson
March 3, 2025
To align the front door on a Cleaver-Brooks CBW boiler:
1. Swing the door to the closed position. 2. Run all retaining bolts in until snug. 3. Tighten the bolts evenly, starting at the top center and alternating between the top and bottom bolts. 4. Avoid overtightening; continue tightening alternate bolts until all are secure and the door is gas-tight. 5. After closing, loosen the nut on the davit arm stud to release tension and prevent thermal stress damage. 6. Once the boiler is back in operation, retighten the door bolts to compensate for gasket compression.
Need help?
Do you have a question about the CBW and is the answer not in the manual?
Questions and answers
how to line up front door on the boiler
To align the front door on a Cleaver-Brooks CBW boiler:
1. Swing the door to the closed position.
2. Run all retaining bolts in until snug.
3. Tighten the bolts evenly, starting at the top center and alternating between the top and bottom bolts.
4. Avoid overtightening; continue tightening alternate bolts until all are secure and the door is gas-tight.
5. After closing, loosen the nut on the davit arm stud to release tension and prevent thermal stress damage.
6. Once the boiler is back in operation, retighten the door bolts to compensate for gasket compression.
This answer is automatically generated