Page 1
User Manual LVRSys™ - 3-phase / 1-phase Systems Low-Voltage-Regulation-System™ Outdoor Al Outdoor GRP Pole mounted Indoor Systems of the series: 180.1000.2xxx Delivery from 2017 and FW-Version 12.00.05 / 12.01.00...
Operating behavior in the low-voltage grid ................10 Voltage drop with load......................11 Voltage boost with generator (e. g. PV feeder) ..............12 Commissioning and Decommissioning LVRSys™ ............. 13 Indicator lamps & system switch ................... 13 Commissioning and decommissioning LVRSys™ ..............13 Check that there is no voltage present ..................
Page 3
9.10 Parameters ..........................26 9.10.1 Set point ..........................27 9.10.2 Tolerance band + and tolerance band - .................. 27 9.10.3 Reaction time .......................... 28 9.10.4 Impedance ..........................29 9.10.5 Balancing (Bal. active) ......................30 9.10.6 Overvoltage warning ....................... 30 9.10.7 Undervoltage warning ......................
Page 4
We take care of it. 10.5.2 CSV configuration of the IEC 60870-5-104 Slave ..............51 10.5.3 IEC 60870-5-104 Parameters ....................51 10.5.4 Redundancy System ....................... 52 10.5.5 Process information for monitoring ..................53 10.5.6 Process information for control ..................... 53 10.5.7 IEC 60870-5-104 register assignment ..................
User guidance This User Manual is a summary of the information needed for the installation,commisioning and operation of the low-voltage regulator. Read the User Manual in its entirety and do not use the product unless you have understood the User Manual. Target group The User Manual is intended for skilled technicians as well trained and certified operators.
We take care of it. Other symbols Instructions Structure of the instructions: Instructions for an action. Indication of an outcome, if necessary. Lists Structure of unnumbered lists: List level 1 – List level 2 Structure of numbered lists: 1) List level 1 2) List level 1 1.
LVRSys™ mounting instructions Circuit diagram of the LVRSys™control cabinet LVRSys™ test certificate Configuration possibilities The possibities of how an LVRSys can be configured cab be found in the Configuration help LVRSys in coorespondense with the sales partners: https://www.a-eberle.de/en/contact/partners Safety instructions ...
We take care of it. Technical Data Rated data Rated voltage 400 V / 230 V ±20 % (L-L/LE) 230 V / 133 V ±20 % (L-L/LE) Rated current 3-phase (400 V L-L) 3-phase (230 V L-L) ...
Page 9
Limits Rated impulse voltage 6 kV Rated short-time current resistance 5 kA (till 160 A) ( 1 s) 15 kA (200 A till 1005 A) Conditional rated short-circuit current 20 kA (to 160 A) 50 kA (200 A till 1005 A) Rated short-circuit current ...
Page 10
We take care of it. 160 cm/50 cm/100 cm 32 A – 910 A GRP - Base 113 cm/32 cm/90 cm 32 A – 160 A 146 cm/32 cm/90 cm 32 A – 355 A 8 % Steel base indoor (pre- 60 cm/60 cm/20 cm 32 A –...
(e.g. 9) steps. This technique is also refered to as Buck/Boost transformers The maximum control range depends on the model of LVRSys (e.g. from ±6% up to ±24%). The switching of the transformers is controlled by thyristors. The regulation steps are determined by the thyristors' various switching settings.
Page 13
We take care of it. Figure 7-1 Single-phase functional diagram Trafo 1 Additional transformer 1 Trafo 2 Additional transformer 2 F1, F2 Fuse Safety contactor Switching resistor Thyristors Thyristors control V_in Unregulated input voltage V_out Regulated output voltage Table 7-2 Explanation of the abbreviations Page 8...
Page 14
Figure 7-2 Example of 3% voltage reduction In the example shown in Figure 7-2, the output voltage is reduced by 3% compared with the input voltage. The transformer Trafo 1 (-4.5%) converts the primary voltage, which is switched by thyristors, in a negative direction and subtracts (bucks) 10.35 V (4.5% of 230 V) from the output voltage.
The low-voltage regulation systems are designed for a long, robust use in the low-voltage grid. In the following, grid scenarios are compared with the behavior of the low voltage regulation systems. Event reaction LVRSys™ Short circuit Ph1 Fuse blow off Ph1 Automatic bypass activated for all phases...
Figure 7-4 Low voltage grid with voltage drop along the cable Figure 7-5 Low voltage grid with voltage drop along the cable (example) Figure 7-6 Low voltage grid with voltage drop along the cable regulated through LVRSys [Simulation Screenshots made with Neplan®].
Figure 7-7 Low voltage grid with voltage boost along the cable Figure 7-8 Low voltage grid with voltage boost along the cable (example) Figure 7-9 Low voltage grid with voltage boost along the cable regulated through LVRSys [Simulation Screenshots made with Neplan®].
CAUTION! Destruction of components due to overload! Only switch the LVRSys™ ON or OFF according to the sequence of actions described below. Never use BYPASS-separation terminals while the system is in CONTROL - mode.
Page 19
(remove knives). 3 . Open LVRSys OUT (remove 4 . Set the system switch to the ON posi- knives/fuses). tion. 4 . Open LVRSys IN (remove knives/fuses). The regulator starts up automatically. The LVRSys™ is completely disconnect- ...
Only measure with fused measuring devices with overvoltage category IV. Check there is no voltage at the input (LVRSys-IN). Check there is no voltage at the output (LVRSys-OUT). Systems with circuit breakers: Check there is no voltage measured on L1/L2/L3 (directly at the circuit breaker) with respect to PEN/PE rail.
Page 21
We take care of it. Figure 8-4 Connection and BYPASS function Circuit breaker for LVRSysIN – F1 Circuit breaker for BYPASS – F3 Circuit breaker for LVRSysOUT – F5 Table 8-3 Explanation of numbering Figure 8-5 Circuit breaker state OFF Page 16...
8.4.2 Operation of systems with switch disconnectors DANGER! Risk of fatal injury from electric shock! Never partially open the LV switch disconnector. Actuate the LV switch disconnector using the handle. Its intended that LV fuses are to be used only by qualified electricians or persons trained in electrical engingeering,eg IEC 60269-2 or certified with respect to the local wiring and safe- ty regulations applicable in your country.
Page 23
We take care of it. 1 2 3 4 5 Figure 8-7 NH switch disconnectors CAUTION! Voltage interruption in the low voltage network! (2) Contact strip LV mains input, never switch! (4) Contact strip LV mains output, never switch! Connection switch disconnector for LVRSysIN – F1 (internal/transformer block secondary line input) Connection of switch disconnector for external input cables (mains connection transformer –...
8.4.3 Operation of systems with LV fuse-switch-disconnectors DANGER! Risk of fatal injury from electric shock! Never partially open LV fuse switch disconnectors Operate the LV fuse switch disconnectors on the handle. Its intended that LV fuses are only used by qualified electricians or persons trained in elec- trical engineering eg: IEC 60269-2 or certified with respect to the local wiring and safety regulations applicable in your country.
Page 25
We take care of it. Abbildung 8-9 LV fuse switch disconnector CAUTION! Voltage interruption on the low voltage network! (1/5) Operate fuse switch disconnector according to instructions! (3) Operate BYPASS fuse switch disconnector according to instructions! See chapter Fehler! Verweisquelle konnte nicht gefunden werden. REF _Ref515268057 \h \* MERGEFORMAT Fehler! Verweisquelle konnte nicht gefunden werden.
We take care of it. Indicator lamps – Control cabinet The indicator lamps red and green indicate the status of the system: Red: Error state; system is in automatic BYPASS. Green: Operating state; system is in faultless operation. If the indicator lamp is red, follow the instructions in the service manual. ...
After the boot process is completed (approx. 45 seconds), the regulator is now in automatic mode. The boot process must be completed in order to carry out all activities such as setting the LVRSys up, changing the display pages, etc. Menu navigation In normal operation, the regulator is in automatic mode by default.
We take care of it. Automatic mode After the boot process (applying the supply voltage) is completed, the controller switches to Automatic mode. In Automatic mode, the controller is active. Figure 9-6 Display Automatic mode The display shows: three phase voltages current step positions of the phases Manual mode The regulator is not active in Manual mode.
We take care of it. 9.10 Parameters The individual controller parameters are described in detail below. Figure 9-9 Setting the regulator parameters Select the Parameter menu (See Section 9.9 Overview display). To select sub items, press the up or down key. ...
9.10.1 Set point The default is: 230 V (400 V phase - phase) or 133 V (230 V phase - phase) Set the set point (100 V – 260 V). 9.10.2 Tolerance band + and tolerance band - The defaults are: 97% for tolerance band –...
We take care of it. 9.10.3 Reaction time The default is 10 Vs. Reaction time adjustable from 1 Vs to 100 Vs in 0.1 steps Reaction time adjustable from 0 Vs to 100 Vs in 0.1 steps (FW 12.01.00) NOTICE! Reaction time 0 Vs is the high speed option <...
Resistance symbol appears in the status window. Figure 9-12 Display impedance active When the impedance is selected, the load current is included in the regulation algorithm. Example: PV Feeder LVRSys™ 0.4kV 500 m Figure 9-13 Example grid branch with 500 m cable section Cable data...
We take care of it. In the example, the calculated voltage value of the regulator is reduced by -100 A x 0.05 Ω = -5 V for a feeding current of the PV system of 100 A. As a result, the desired voltage setpoint is regulated at the end of the cable.
9.10.7 Undervoltage warning The default is 90 % (related to setpoint). Adjustable from 0% to 95%. The undervoltage warning is active if the 10 second mean value of the voltage above the undervoltage warning margin which can set as required. The undervoltage waring is visible in through flags in the communication protocols and as a waring message in the Event data.
We take care of it. If NTP time Sychronisation is activated (see section 10.6) the time will be updated automatically. 9.11.5 Language Possible languages: German English 9.12 Device Info Figure 9-15 Device info display Select the Device info menu (see section 9.9 Overview display). ...
Page 38
Copying the update files to a USB stick: Extract the zip file (from email or download: https://www.a-eberle.de/de/download-center-categories/firmware-1). Save the files on a FAT32 formatted USB stick The folder structure below is mandatory, no parent folders on the USB stick (USB stick:\unpacked files;...
We take care of it. 9.12.3 Logbook The logbook contains following items: Event data Event data list contains: Parameters New settings State (Automatic/Manual) Change of state (Automatic-Manual) Over- / Undervoltage warnings Error. Measurement data Measurement data list contains: U1 to U3 (10 minutes average values in V) U1Z to U3Z (10 minutes average values in V, only with option Current transformer and Impedance is set) I1 to I3 (10 minutes average values in A;...
Page 40
Figure 9-18 Overview read logbook 9.12.3.1 Download Logbook via USB stick To download the logbook via USB stick you have to be in front of the LVRSys and follow these steps. Insert the USB stick. Select menu item Logbook.
Page 41
Download via LVRSysUpdater To download the logbook via remote access on the device you have to follow these steps: Ensure stable remote connection to LVRSys (e. g. ping-test) Open LVRSysUpdater. Press Button “Log Download” (see Figure 9-19 Logs Download LVRSysUpdater) ...
Page 42
Evaluating the logbook (measurement data) with Microsoft Excel (alternative spreadsheet programs can also be used). A. Eberle provides an Excel macro and a descriptive video on the homepage. https://www.a-eberle.de/en/downloads/low-voltage-regulation/analysis-support Evaluation without macro Open the Measurement data in Excel. Select the first column (A).
Page 43
We take care of it. Figure 9-21 Selecting data and text in columns Convert Text to Columns Wizard - Step 1 of 3 select Delimited. Press Next to confirm. Figure 9-22 Text conversion wizard - Step 1 of 3 ...
Page 44
Figure 9-23 Text conversion wizard - Step 2 of 3 Convert Text to Columns Wizard - Step 3 of 3 press on Advanced... Figure 9-24 Text conversion wizard - Step 3 of 3 Page 39...
Page 45
We take care of it. Decimal separator: Select Point. Press OK to confirm. Press Finish in the Convert Text to Columns Wizard to confirm. Figure 9-25 Further text import settings Measurement data is divided into columns. 9.12.3.4 Evaluating the logbook (Event data) in Notepad++ (alternative text editing programs can also be used).
9.12.4 Firmware-Version Menu item FW-Version contains information about: Firmware - version Cortex-firmware - version Kernel - version Files ystem – version The version number is determined automatically. No changes possible. 9.12.5 LOG ERR Display of the last occurred error. ...
We take care of it. The individual error codes add up as follows: Error Error code Internal regulation error 0x01000 Service switch 0x00200 Internal regulation error 0x00080 Under voltage 0x00004 LOG ERR 0x1284 Table 9-7 Menu tab LOG ERR The zeros after the x are not displayed. 9.12.6 Type number Menu item Type number contains information about:...
Figure 9-27 Setting the factory parameters Select the Setup menu (See Section 9.9 Overview display). To select the item submenu, press the up or down key. Press the Enter key. Configuration: Enter the PIN number by pressing the up/down and left/right keys. ...
We take care of it. 9.13.4 Resetting the indicator The Indicator or Drag indicator sets 15 min average values for the: maximum voltages (Ph 1-3) maximum currents (Ph 1-3) maximum power values (Ph 1-3) maximum and minimum temperature in the switch cabinet in °C (T). Reset indicator: ...
Communication 10.1 Ethernet Ethernet interface serves as communication interface for Modbus and IEC 60870-5-104 applications. Figure10-28 Ethernet interface 10.2 Overview communication settings Figure 10-29 Overview of the communication settings Page 45...
We take care of it. 10.3 TCP/IP Configuration via Ethernet Figure 10-30 Overview of the TCP/IP configuration The TCP/IP interface is the basis for all communication protocols and must be set according to the remote station. 10.4 Modbus 10.4.1 Modbus Setup Figure 10-31 Modbus Setup ...
Configuration: Set the parameters by pressing the up/down and left/right keys. Enter the PIN number by pressing the up/down and left/right keys. Press Enter to confirm the PIN. Press Enter to confirm the selection. Standard parameters for the Modbus Communication are: TCP-Port 502 10.4.2 Modbus register assignment...
Page 53
We take care of it. Holding registers (16-Bit data, read and write) Name permitted values Standard Addressing Reset indicator 0/1 1 - Command Reset indicator Table 10-12 Operating status and regulator commands Input register (16-Bit data, read only) Name permitted values Unit Addressing Step size...
Page 54
Input register (16-Bit data, read only) Name permitted values Unit Addressing Drag indicator U2 max. 0 - 65000 0.1 V Drag indicator U3 max. 0 - 65000 0.1 V Drag indicator I1 max. 0 - 65000 0.1 A Drag indicator I2 max. 0 - 65000 0.1 A Drag indicator I3 max.
10.5.1 Unlock IEC 60870-5-104 License This chapter can be skipped if the protocol was already activated by A-Eberle on delivery. Figure 10-32 T104 licensing The licensce file is transmitted by the A. Eberle support team and is linked to the serial number of the system.
10.5.2 CSV configuration of the IEC 60870-5-104 Slave The LVRSys™ IEC 60870-5-104 slave can be configured through a CSV file. When the system is started, the CSV file is loaded and the IEC 60870-5-104 slave is then ready for operation.
We take care of it. LVRSys™ IEC 60870-5-104 slave can be bound to a system IP address in the first instance. This is useful if redundancy systems are used for communication or there is an additional connection via other networks such as WLAN or UMTS. LVRSys™ IEC 60870- 5-104 slave then only listens to the first instance.
10.5.5 Process information for monitoring Process information implemented as standard for monitoring: Type identification Process information Single message Double message Measured value, shorted floating point number Single message with time stamp Double message with time stamp Measured value, shorted floating point number with time stamp Table 10-16 Process information for monitoring Process information for control 10.5.6...
We take care of it. 10.5.7 IEC 60870-5-104 register assignment The register assignment is valid for firmware version 12.00.04 in combination with the CSV configuration (# T104 csv file for LVRSys V1.3 – 9U #). Values Description: ON -> OFF -> 0 Alarms/Message IEC60870-104...
Page 60
Measured values + counter Permitted val- IEC60870-104 IEC60870-104 Name Standard Addressing Type Step size 0 – 1000 Step Phase 1 0 - 8 Step Phase 2 0 - 8 Step Phase 3 0 - 8 Voltage Phase 1 Voltage Phase 2 Voltage Phase 3 Current Phase 1 Current Phase 2...
Page 61
We take care of it. Drag indicator P1 max. Drag indicator P2 max. Drag indicator P3 max. Drag indicator Temp. cabinet max. Drag indicator Temp. cabinet min. Table 10-20 Measured values +counter register Regulation parameters actual values Permitted IEC60870-104 IEC60870-104 Name Standard values...
10.6 NTP Time Synchronization Figure 10-1 NTP Display NTP time synchronization takes place via the connection to an NTP server. Connection to network or Internet required. Set the desired server IP NTP IP1, NTP IP2. Possible IP for Internet connection 192.53.103.108 (PTB, Braunschweig) ...
We take care of it. IT-Security Figure 11-1 Overview security parameters Selection of the sub item security for setting security-relevant parameters. Change and adjust the PIN. Shut down and allow protocols. Shut down and allow remote access. Encrypt TCP/IP packets. Shut down and activate Ethernet interface.
I15, I3), fuse terminals for the voltage taps and current transformers for the current measurement at the output bus bar are installed. DANGER! Danger of electric shock! Establish BYPASS operation. WARNING! To ensure there is no voltage on the PQI-DA smart the LVRSys must be in BYPASS mode. Page 59...
Make sure the LVRSys™ is completely de-energised. Remove low voltage cables. Remove local cabinet grounding. The disposal of the LVRSys™ is carried out by A. Eberle GmbH & Co. KG. Send all components to: A. Eberle GmbH & Co. KG Frankenstraße 160...
Warranty A. Eberle GmbH & Co. KG. warrants that this product and accessories will be free from defects in materials and workmanship for a period of three years from the date of purchase. Warranty does not apply to damage caused by: Accidents Misuse Abnormal operating conditions...
Page 67
We take care of it. Notes Notes Page 62...
Need help?
Do you have a question about the LVRSys and is the answer not in the manual?
Questions and answers