96
Commissioning
9.
Close the editor.
Pos : 78.15.19 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/BootP akti vier en - Teil 1 ( WAGO-BootP) @ 4\mod_1239097776437_21.doc x @ 30138 @ 4 @ 1
8.2.1.4
Activating BootP
1.
On your PC, go to Start and select the menu item Programs \ WAGO
Software \ WAGO BootP Server.
2.
Click on WAGO BootP server to open the dialog window.
3.
Click on [Start] in the dialog window that then appears. This activates the
query/response mechanism of the BOOTP protocol.
A number of messages is then output at the BootP server. Error messages indicate
that some services (such as Port 67, Port 68) are not defined in the operating
system.
Figure 45: Dialog window for the WAGO-BootP server, with messages
Pos : 78.15.20 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/BootP akti vier en - Teil 2 (C ontroll er) @ 6\mod_1264426449758_21.doc x @ 48435 @ @ 1
So that the new IP address is taken over in the fieldbus controller, you must now
restart the fieldbus controller with a hardware reset:
4.
Interrupt the power supply of the fieldbus controller for approx. 2 seconds
or press the mode selector switch, which is located behind the configuration
interface door.
The IP address is stored permanently in the fieldbus controller.
Pos : 78.15.21 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/BootP akti vier en - Teil 3 @ 6\mod_1264426499618_21.doc x @ 48588 @ @ 1
5.
To close the BootP server again, click [Stop] and then click the button
[Exit].
Pos : 78.15.22 /D okumentation allgemein/Gliederungselemente/---Sei tenwechsel--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-843 ETHERNET Controller 10 MBit
Manual
Version 1.2.0