RELION® 615 SERIES
Motor Protection and Control
REM615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION 615 Series

  • Page 1 — RELION® 615 SERIES Motor Protection and Control REM615 Product Guide...
  • Page 2: Table Of Contents

    16. Access control............16 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2018 ABB.
  • Page 3: Description

    Protection and Control IED ® process industry. REM615 is a member of ABB’s Relion Manager PCM600. Further, the application configuration product family and part of its 615 protection and control functionality of the relay supports the creation of multi-layer product series.
  • Page 4 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 REM615 MOTOR PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× 3× - Event log and recorded data Master Trip Master Trip - High-Speed Output module (optional) Configuration System...
  • Page 5 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 REM615 MOTOR PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× 3× - Event log and recorded data Master Trip Master Trip - High-Speed Output module (optional) Configuration System...
  • Page 6 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 REM615 MOTOR PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× 3× - Event log and recorded data Master Trip Master Trip - High-Speed Output module (optional) Configuration System...
  • Page 7 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 REM615 MOTOR PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× 3× - Event log and recorded data Master Trip Master Trip - High-Speed Output module (optional) Configuration System...
  • Page 8 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 2. Supported functions Function IEC 61850 Protection Three-phase non-directional overcurrent protection, low stage PHLPTOC Three-phase non-directional overcurrent protection, high stage PHHPTOC Three-phase non-directional overcurrent protection, PHIPTOC instantaneous stage Non-directional earth-fault protection, low stage EFLPTOC Non-directional earth-fault protection, high stage...
  • Page 9: Protection Functions

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 2. Supported functions, continued Function IEC 61850 Pulse timer (8 pcs) PTGAPC Time delay off (8 pcs) TOFGAPC Time delay on (8 pcs) TONGAPC Set-reset (8 pcs) SRGAPC Move (8 pcs) MVGAPC Generic control point (16 pcs)
  • Page 10 (Io) input and three combi-sensor inputs for such as ABB’s UniGear Digital, SafeRing and SafePlus, with phase currents and phase voltages. The connection of the three limited space for conventional measuring transformers, thus combi-sensors is made with RJ-45 type of connectors.
  • Page 11: Supported Abb Solutions

    The standard configuration D has been pre-configured (Rogowski coil) and voltage sensors (voltage divider) are used especially for ABB switchgears, for example, UniGear Digital. for the measurements. To prevent possible power system The use of this configuration is not restricted for that purpose instability due to busbar voltage collapse, the simultaneous only.
  • Page 12 COM600S also provides an overview of the whole substation, events during substation operation to enable improved system including relay-specific single-line diagrams, which makes supervision. information easily accessible. Substation devices and Table 3. Supported ABB solutions Product Version Substation Management Unit COM600S 4.0 SP1 or later 4.1 or later (Edition 2)
  • Page 13: Control

    GOOSE communication GOOSE communication GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN Figure 7. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA 6. Control outputs which have originally been configured for other REM615 integrates functionality for the control of a circuit purposes, when applicable, or an external input or output breaker via the front panel HMI or by means of remote controls.
  • Page 14: Measurement

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 The relay is provided with a load profile recorder. The load By default, the binary channels are set to record external or profile feature stores the historical load data captured at a internal relay signals, for example, the start or trip signals of the periodical time interval (demand interval).
  • Page 15: Condition Monitoring

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 PROCESS LEVEL USER LEVEL Process events 1024 (FIFO) Fault records (FIFO) Fault summary; Trip timestamp, Function, Currents, Voltages, etc. Audit trail events (FIFO) 2048 System and security-related events; Configuration changes, Control, Login, etc. Disturbance records n…100...
  • Page 16: Fuse Failure Supervision

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 14. Fuse failure supervision applications requiring sensitive earth-fault protection and The relay includes fuse failure supervision functionality. The featuring core-balance current transformers. The three phase- fuse failure supervision detects failures between the voltage voltage inputs and the residual-voltage input covers the rated measurement circuit and the relay.
  • Page 17: Station Communication

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 4. Input/output overview Std. conf. Order code digit Analog channels Binary channels Combi sensor 4 PO + 2 SO 4 PO + 6 SO AC / AD 4 PO + 2 SO + 3 HSO AG / AH 4 PO + 2 SO...
  • Page 18 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 The relay also supports IEC 61850 process bus by sending The IEC 61850 standard specifies network redundancy which sampled values of analog currents and voltages and by improves the system availability for the substation receiving sampled values of voltages.
  • Page 19 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 relays. If more than 30 relays are to be connected, it is recommended to split the network into several rings to guarantee the performance for real-time applications. COM600 Devices not supporting HSR SCADA Ethernet switch Redundancy...
  • Page 20 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Client A Client B Network A Network B Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN Figure 11. Self-healing Ethernet ring solution All communication connectors, except for the front port records are supported.
  • Page 21 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 The relay supports the following high accuracy time • Layer 2 mapping synchronization method with a time-stamping resolution of 4 µs • Peer to peer delay calculation required especially in process bus applications. •...
  • Page 22: Technical Data

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 19. Technical data Table 6. Dimensions Description Value Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth 201 mm (153 + 48 mm) Weight Complete protection relay 4.1 kg...
  • Page 23 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 9. Energizing inputs (sensors) Description Value Current sensor input Rated current voltage (in secondary 75 mV...9000 mV side) Continuous voltage withstand 125 V Input impedance at 50/60 Hz 2...3 MΩ...
  • Page 24 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 12. Signal output X100: SO1 Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R<40 ms, at 1 A/0.25 A/0.15 A...
  • Page 25 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 15. Single-pole power output relays Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A...
  • Page 26 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 19. IRIG-B Description Value IRIG time code format B004, B005 Isolation 500V 1 min Modulation Unmodulated Logic level 5 V TTL Current consumption <4 mA Power consumption <20 mW According to the 200-04 IRIG standard Table 20.
  • Page 27 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 23. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst disturbance test IEC 61000-4-18 IEC 60255-26, class III IEEE C37.90.1-2002 • Common mode 2.5 kV •...
  • Page 28 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 23. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity test Binary inputs only IEC 61000-4-16 IEC 60255-26, class A • Common mode 300 V rms •...
  • Page 29 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 26. Environmental tests Description Type test value Reference Dry heat test • 96 h at +55ºC IEC 60068-2-2 • 16 h at +85ºC Dry cold test • 96 h at -25ºC IEC 60068-2-1 •...
  • Page 30 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Protection functions Table 30. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 × I ±1.5% of set value or ±0.002 ×...
  • Page 31 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 32. Non-directional earth-fault protection (EFxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz EFLPTOC ±1.5% of the set value or ±0.002 × I EFHPTOC ±1.5% of set value or ±0.002 ×...
  • Page 32 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 34. Directional earth-fault protection (DEFxPDEF) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz DEFLPDEF Current: ±1.5% of the set value or ±0.002 × I Voltage ±1.5% of the set value or ±0.002 ×...
  • Page 33 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 35. Directional earth-fault protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start value DEFLPDEF 0.010...5.000 × I 0.005 0.10...40.00 × I 0.01 DEFHPDEF Directional mode DEFLPDEF and DEFHPDEF 1 = Non-directional 2 = Forward 3 = Reverse...
  • Page 34 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 37. Three-phase undervoltage protection (PHPTUV) main settings Parameter Function Value (Range) Step Start value PHPTUV 0.05...1.20 × U 0.01 Time multiplier PHPTUV 0.05...15.00 0.01 Operate delay time PHPTUV 60...300000 ms PHPTUV Definite or inverse time...
  • Page 35 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 40. Negative-sequence overvoltage protection (NSPTOV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±1.5% of the set value or ±0.002 × U Minimum Typical Maximum 1)2)
  • Page 36 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 43. Frequency protection (FRPFRQ) main settings Parameter Function Value (Range) Step Operation mode FRPFRQ 1 = Freq< 2 = Freq> 3 = df/dt 4 = Freq< + df/dt 5 = Freq>...
  • Page 37 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 46. Loss of load supervision (LOFLPTUC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±1.5% of the set value or ±0.002 × I Start time Typically 300 ms Reset time...
  • Page 38 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 50. Motor start-up supervision (STTPMSU) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±1.5% of the set value or ±0.002 × I Minimum Typical Maximum...
  • Page 39 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 53. Phase reversal protection (PREVPTOC) main settings Parameter Function Value (Range) Step 0.05...1.00 x I Start value PREVPTOC 0.01 Operate delay time PREVPTOC 100...60000 ms Operation PREVPTOC 1 = on 5 = off Table 54.
  • Page 40 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 57. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function Value (Range) Step Current value CCBRBRF 0.05...2.00 × I 0.05 Current value Res CCBRBRF 0.05...2.00 × I 0.05 CB failure mode CCBRBRF 1 = Current...
  • Page 41 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 61. Multipurpose protection (MAPGAPC) main settings Parameter Function Value (Range) Step Start value MAPGAPC -10000.0...10000.0 Operate delay time MAPGAPC 0...200000 ms Operation mode MAPGAPC 1 = Over 2 = Under...
  • Page 42 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Control functions Table 62. Emergency start-up (ESMGAPC) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × U Table 63. Emergency start-up (ESMGAPC) main settings Parameter Function Value (Range)
  • Page 43 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Condition and supervision functions Table 64. Circuit-breaker condition monitoring (SSCBR) Characteristic Value Current measuring accuracy ±1.5% or ±0.002 × I (at currents in the range of 0.1…10 × I ±5.0% (at currents in the range of 10…40 ×...
  • Page 44 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Measurement functions Table 69. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±0.5% or ±0.002 × I (at currents in the range of 0.01...4.00 × I Suppression of harmonics DFT: -50 dB at f = n ×...
  • Page 45 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 74. Sequence voltage measurement (VSMSQI) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz At voltages in range 0.01…1.15 × U ±1.0% or ±0.002 × U Suppression of harmonics DFT: -50 dB at f = n ×...
  • Page 46 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Other functions Table 78. Pulse timer (PTGAPC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms Table 79. Time delay off (8 pcs) (TOFPAGC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms...
  • Page 47: Local Hmi

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 20. Local HMI default single line diagram. The SLD view can also be accessed The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD a small one.
  • Page 48: Mounting Methods

    (PST), a Next-Generation Order Number circuiting the CT secondary circuits when a relay unit is Tool, supports order code creation for ABB Distribution withdrawn from its case. The relay case is further provided with Automation IEC products with emphasis on, but not exclusively a mechanical coding system preventing the current measuring for, the Relion product family.
  • Page 49: Accessories And Ordering Data

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 24. Accessories and ordering data Table 83. Cables Item Order number Optical sensor for arc protection, cable length 1.5 m 1MRS120534-1.5 Optical sensor for arc protection, cable length 3.0 m 1MRS120534-3 Optical sensor for arc protection, cable length 5.0 m 1MRS120534-5...
  • Page 50: Tools

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 25. Tools (Internet Explorer). For security reasons, the Web HMI is The protection relay is delivered as a preconfigured unit. The disabled by default but it can be enabled via the local HMI. The default parameter setting values can be changed from the front- Web HMI functionality can be limited to read-only access.
  • Page 51: Cyber Security

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 86. Supported functions Function Web HMI PCM600 Relay parameter setting ● ● Saving of relay parameter settings in the relay ● ● Signal monitoring ● ● Disturbance recorder handling ●...
  • Page 52: Terminal Diagrams

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 27. Terminal diagrams GUID-B2057B3C-DDFD-4A85-98AF-9E14D947439D V1 EN Figure 17. Terminal diagram of standard configuration A...
  • Page 53 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 GUID-FB8CC4CD-F5ED-4FE5-837D-B39CB06ED67C V1 EN Figure 18. Terminal diagram of standard configuration B...
  • Page 54 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 GUID-1589F909-AB4D-44A7-9445-057B7385AFD7 V2 EN Figure 19. Terminal diagram of standard configuration C...
  • Page 55: Certificates

    Figure 20. Terminal diagram of standard configuration D 28. Certificates 29. References DNV GL has issued an IEC 61850 Edition 2 Certificate Level A1 www.abb.com/substationautomation portal provides information on the entire range of distribution automation ® for Relion 615 series. Certificate number: 7410570I-OPE/INC products and services.
  • Page 56: Functions, Codes And Symbols

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 30. Functions, codes and symbols Table 87. Functions included in the relay Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, PHLPTOC1 3I> (1) 51P-1 (1) low stage Three-phase non-directional overcurrent protection, PHHPTOC1 3I>>...
  • Page 57 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 87. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Multipurpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4)
  • Page 58 Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 87. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Load profile record LDPRLRC1 LOADPROF (1) LOADPROF (1) Fault record FLTRFRC1 FAULTREC (1) FAULTREC (1) Three-phase current measurement CMMXU1 3I (1)
  • Page 59: Document Revision History

    Motor Protection and Control 1MRS756890 N REM615 Product version: 5.0 FP1 Table 87. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1) SPCGAPC2 SPC (2) SPC (2) Analog value scaling SCA4GAPC1 SCA4 (1)
  • Page 64 ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 ABB Distribution Automation Maneja Works Vadodara-390013, India Phone +91 265 2604386 +91 265 2638922 www.abb.com/mediumvoltage www.abb.com/relion www.abb.com/substationautomation © Copyright 2018 ABB. All rights reserved.