IT rules ....................60 5.1.1 Repeater rules ................60 5.1.2 Cable lengths................61 Dedicated safety and security networks ..........61 5.2.1 Application example with commercial Ethernet components .62 5.2.2 Application example with Industrial Ethernet components ..63 5.2.3 Application example with OTN (Open Transport Network) ..65 Shared network ..................66 5.3.1 Information you need to give to your customer ......67...
About this document About this document Scope This document applies to the following Siemens FS products: – MM8000 Management Station – MK8000 OPC Server for Subsystems – MT8001 Management Terminal – NK8000 Networks (With WW8000 Composer) Target group This documentation is intended for the following users: Sales personnel Persons responsible for the sale of products, and service to customers.
Page 6
The following describes one way to search and find a document: To learn about other ways to locate a document, see DMS8000 Quick Reference Guidelines for Search and Finding DMS Documents in STEP (STEP #A6V10064704). 1. Click on the "STEP WEB Client" image.
Page 7
02.2004 MP1.31 Release Notes for MP1.30 007875_a 10.2003 MP1.30 Release Notes for MP1.20 007143_a 07.2003 MP1.20 Release Notes for MP1.10 007076_a 04.2003 MP1.10 Installation, Configuration and A6V10062407_a 06.2007 MP4.10 Commissioning (ICC) Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Page 9
OPC site: “White Papers” OPC via DCOM with XP SP2 2006-03-30 Also available in STEP #004971_h Training Siemens Fire & Security Products offers a comprehensive training program. You can find information about courses in the Siemens Intranet. Modification index Current version Date Notes A6V10063710_a_en 06.2007...
(Siemens) Building Automation products. Danger Management System. (Siemens) Fire Safety and Security products. Head end The head end of a system is the Management Station on the management level providing the User Interface to the final user.
Products concept Products concept One of Siemens Building Technologies’ (SBT) primary goals is to be able to provide complete integration solutions to our customers. Complete integration includes fire safety, security, and building automation systems built by various Siemens and third- party suppliers.
The NK822x Ethernet Ports are used to connect local and distributed safety and secu- rity devices to the NK8000 network. The NK822x port provides a first level of centrali- sation, and acts as a secure communication partner for DMS8000. All ports come with optional housing solutions with autonomous power supplies. Additionally, the NK8223 / NK8225 can be serially connected to a local management station.
Page 13
NK8225s (CS11 AlgoRex, FC700A, SIG- MASYS, D100, CS6 Guarto, Sintony SI410/420) The DMS8000 upstream devices (MM8000 or MK8000) must be equipped with the NS8011 Network Driver for BACnet/IP on Ethernet connectivity, the NS8210 Net- work Driver for TCP/IP on Ethernet connectivity, or with the NS8012 CDI-Net Driver for serial connectivity.
Composer (using the subsystem tool concept). Composer is the common configuration tool for all DMS8000 products. For more information on Siemens DMS products, refer to the “Reference docu- ments” section in “About this document” on page 6.
Management level configurations Management level configurations This section lists the management configuration types that are supported in DMS8000 MP4.10 for: – MM8000 Management Station – MK8000 OPC Server – NK8000 Networks To see network connectivity options, refer to Appendix A.
NK8000 safety and security networks are supported by MM8000 and MK8000 MP4.10 in the configurations described in section 2.1 (up to four hosts). Additionally, the NK8225 supports BACnet subsystem connectivity for up to fours hosts for MM8000 / MK8000. DMS8000 Multiple host configuration – CMSDL/IP 2.2.1 Characteristics: –...
Management level configurations DMS8000 single-host configuration – support of dial-up connections 2.2.3 Characteristics: – Communication layer equipped with NS8210 Network driver and modem(s) – NK822x dial-ups as primary (no Ethernet connection) or secondary (in case net- work is down) via PSTN Fig.
Automation level configurations Automation level configurations Configurations supported by MM8000 / MK8000 The MM8000 / MK8000 MP4.10 support the following: Automation level configuration types – Direct RS-232 – Cerloop – CDI-Net – NK8000 – Direct LAN Network components – NK822x –...
Page 21
Section 3.3 details the configuration types supported by MM8000 and MK8000. Note: Combinations of automation level configurations are also supported. For network connectivity options, see Appendix A. ‡ MM8000 only Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
The upstream side of the gateway (CK1142 or FG700A) is connected to the DMS via serial line. The downstream side of the gateway is connected to one (or more) CS11 AlgoRex (or FC700A) fire panels via the proprietary C-Bus. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products...
Page 24
Automation level configurations Subsystems that can be connected in this way Type Name Supported by MM8000 MK8000 MT8001 MP4.10 MP4.10 MP3.15 Fire panel CS11 AlgoRex Fire panel FC700A Network devices required Type Name Version ‡ Gateway for CS11 CK1142 ‡ Gateway for FC700A FG700A Additional components required for the various management station types...
The downstream side of the MK7022 is connected via Cerloop to different fire & secu- rity control units. A CS11 AlgoRex cluster can be connected to the Cerloop via the CK1142 gateway (configured for Cerloop). Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products...
Page 26
Automation level configurations Subsystems that can be connected in this way Type Name Supported by MM8000 MK8000 MT8001 MP4.10 MP4.10 MP3.15 Fire panel CS11 AlgoRex Fire panel CZ10 Intrusion panel CS440 Intrusion panel Intrusion panel CZ12 Gas panel CC60 Digital PLC unit MF/MM7033 Système de STT11...
NS8015 MM8000 Fire CNDL Driver NS8015 MP4.10 Limits and restrictions Type Version Restrictions MM8000 MP4.10 Up to four serial connections to CNDL driver. MK8000 MT8001 MP3.15 CS1115 / FC330A not supported. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations 3.3.4 SI410/420 Sintony direct configuration Fig. 11 Serial configuration via RS-232 Fig. 12 Serial configuration via LAN tunnelling System architecture This configuration allows for integration of SI410/420 Sintony intrusion panels. Communication / connection The connection can be via: –...
Page 29
(for LAN tunnelling) (or equivalent) documentation Limits and restrictions Type Version Restrictions MM8000 MP4.10 Connectivity limited to number of serial and virtual MK8000 serial ports. MT8001 MP3.15 SI410/420 Sintony direct connectivity not supported. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
SISTORE SX TELSCAN video web server IP cameras (fixed) See DMS8000 Video Connectivity Configu- party systems ration guide (STEP #A6V10062457). Note: IP cameras can be connected to SISTORE MX. If connected directly, they are configured as single-line TELSCAN. Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en...
Page 31
TELSCAN party device systems IP camera devices CCIS1337-LP CFVA-IP CVVA-IP See section 3.5 on page 54 and DMS8000 Video Connectivity Configuration guide (STEP #A6V10062457) for supported 3 party subsystems. Limits and restrictions Type Version Restrictions MM8000 MP4.10 None MK8000 MP4.10...
MK8000 MT8001 MP4.10 MP4.10 MP3.15 ‡ Access control SiPass Integrated party See DMS8000 Access Control Connectivity systems Guide (STEP # A6V10062451). Network devices required Type Name Version LAN devices ‡ See MM8000 MP4.10 Release Notes (STEP #A6V10062455) Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en...
Page 33
MP4.10 OPC Server MK8000 MM8000 / Access Control SiPass Integrated MK8000 software SiPass Driver NS8018 Limits and restrictions Type Version Restrictions MM8000 MP4.10 None MK8000 MT8001 MP3.15 Not supported Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations 3.3.7 BACnet/IP LAN configuration Fig. 15 Direct LAN configuration for subsystems System architecture This configuration allows for the integration of DESIGO PX building automation con- trollers. Communication / connection The subsystems are connected to the DMS via LAN. Subsystems that can be connected in this way Type Name...
MM8000 Paging dispatching services Limits and restrictions Type Version Restrictions MM8000 MP4.10 1 paging system MK8000 MP4.10 Paging system not supported MT8001 MP3.15 ‡ See MM8000 MP4.10 Release Notes (STEP #A6V10062455) Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations 3.3.9 OPC integration configuration Fig. 17 OPC integration configuration System architecture This configuration allows for the integration of 3 party subsystems equipped with an OPC server. OPC connectivity for subsystems can be provided in “light” or “full” mode. - Light: Free, but requires more engineering (e.g.
On the downstream side, the NK822x is connected via serial lines and/or via LON-bus to a number of different fire & security control units. For supported downstream configurations/protocols of NK822x, please refer to the NK822x-Ethernet Port datasheets. (See “Reference documents page 6.) Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Page 38
Automation level configurations Subsystems that can be connected in this way Type Name Supported by MM8000 MK8000 MT8001 MP4.10 MP4.10 MP3.15 Fire panel CS11 AlgoRex Fire panel FC700A Fire panel CZ10 Fire panel SIGMASYS Fire panel D100 Intrusion panel CS440 Intrusion panel Intrusion panel CZ12...
Page 39
- Upstream serial connectivity is limited to one host MK8000 - Host must be equipped with NS8012 CDI-Net Driver - NS8012 CDI-Net Driver supports max. 3 NK822x’s MT8001 MP3.15 Serial connection to the NK822x is not supported Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations 3.3.11 NK822x LAN/WAN configuration Fig. 19 NK8000 LAN/WAN configuration System architecture This configuration allows for integration of a number of Cerloop (proprietary Class A loop), Cerban and/or RS485 connectable control panels. In addition it allows for CS6 Guarto integration via LON-bus.
Page 41
Network devices required Type Name Version MP4.10 Ethernet Port NK822x ‡ Gateway for CS11 CK1142 ‡ Gateway for FC700A FG700A Gateway for STT11 SK11 ‡ See MM8000 MP4.10 Release Notes (STEP #A6V10062455) Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Page 42
MK8000 MP4.10 Network Driver NS8210 MM8000 Network Driver NS8210 MP4.10 Modem NK8021 (Analog); Siemens M20 or MC35i (GSM) Limits and restrictions Type Version Restrictions MM8000 MP4.10 - NK822x supports logical connections to a max. of 4 MK8000 hosts (MM8000 and/or MK8000) via CMSDL/IP protocol...
& security control units. For supported downstream configurations/protocols of NK8225 please refer to the NK8225 Ethernet Port with BACnet Gateway datasheet. (See “Reference docu- ments” page 6.) Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Page 44
Automation level configurations Subsystems that can be connected in this way Type Name Supported by MM8000 MK8000 MT8001 MP4.10 MP4.10 MP3.15 Fire panel CS11 AlgoRex Fire panel FC700A Fire panel SIGMASYS Fire panel D100 Intrusion panel SI410/420 Sintony Intrusion panel CS6 Guarto Network devices required Type...
Page 45
- Max. 10,000 pairs of BACnet multi-state input and multi- state output objects are supported (soft limit) See section 3.3.11 for configuration details for these protocols. See section 4.4 for details on interactions. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations NK8000 Networks This section provides more specific details of the NK8000 components For network connectivity options, see Appendix A. 3.4.1 Hardware configurations NK8223 / NK8225 The NK8223/NK8225 Ethernet ports are available in four hardware configurations: NK8223.2 Base module –...
Page 47
Further options: Cable for connecting SI410 to NK822x must be or- dered separately from the intrusion product range (80064100001 SAQ18 Cable link X25 SAQ18). – Modem NK8021 analog modem Analog modem for public switched telephone network (PSTN) Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations 3.4.1.1 Installation Typically NK822x are installed in the enclosure of the subsystem and powered from the supervised power supply of the subsystem. NK822x Ethernet Ports are supplied in a plastic box, easy to install on DIN-rails. Alternatively the NK822x can be installed without the plastic box using the specific mounting kits for CS11 AlgoRex/CS440, CS6 Guarto, or SI410/420 Sintony.
Page 49
NK822x. NE8002 the empty enclosure including the mounted DIN-rail Fig. 24 NE8001 housing with installed NK822x and DF80xx modules Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
Automation level configurations 3.4.2.2 Subsystems connected via RS485 interface The following control units are supported: Siemens CF9000 I/O systems (CF9003, DF8020, DF8040, DF8045, DF8046 mod- ules) Fig. 26 Example of a subsystem connected via RS485 interface Note: The serial interface COM1 can be configured either as RS232 or RS485 inter- face.
Automation level configurations 3.4.2.4 Cerloop network connected via MK7022 The following control units are supported in a Cerloop configuration: Fire detection systems: – CS11 AlgoRex – CZ10 – STT11 (Système de Télécommande et Télésignalisation) – STT20 – STT2410 Intrusion detection systems: –...
Automation level configurations party systems The MM8000 and MK8000 Danger Management Systems, and the NK8000 Networks MP4.10 support the following 3 party systems: Note: The following systems are available as add-on packages. Please refer to product-specific documentation. Automation level configuration types –...
(Gas), SI410/420 Sintony, CS440, CS4, and CZ12 intrusion control units. Optionally, DF80xx modules for up to 16 digital inputs, 8 relay outputs, or power supply supervision can also be installed on the local I C bus. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
NK8000 Application examples Distributed, campus-style systems Examples for campus size systems are: – Universities – Airports – Amusement parks (e.g. Disneyland) – Industries – Pharmaceutical companies – Hospitals – Automobile manufacturing plants The following figure shows a typical campus site configuration. The subsystems of each building are connected to an NK822x Ethernet Port.
NK822x are connected via the LAN or WAN to the remote management station(s). Additionally, dial-ups are available via modem as backup connectivity in case the net- work is down. Fig. 31 Example of a wide area expansion system Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
NK8000 Application examples Interactions Interactions are possible between the subsystems connected to NK822x and the lo- cally connected I/O modules. Incoming messages can trigger one or more command messages to other subsystems. Note: Incoming messages can be combined with the logical operators AND, OR, XOR, and NOT.
Page 59
Local and network-wide interactions on NK8225 Limitations: Network-wide interactions on the NK8225 via BACnet/IP are possible for the same subsystems as local interactions. Note: Network-wide interactions and dial-up connections are not currently compatible. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
NK8000 Network planning NK8000 Network planning NK8000 networks can be built as a dedicated safety- and security IP network, or can be integrated into an existing customer network (shared network). The IT rules apply in both cases. IT rules The NK8000 network supports the IEEE 802.3 Ethernet 10BaseT standard, which is based on a star topology.
Disadvantages of dedicated safety- and security networks are: – You need trained staff for commissioning and maintenance of the network; – You may need to keep some additional spare parts in stock. – Higher installation costs. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
NK8000 Network planning 5.2.1 Application example with commercial Ethernet components The following drawing shows a NK8000 network based on commercial Ethernet components. MM8000 MM8000 MM8000 MM8000 MM8000 Server Client Client Stand-alone Client Switch Switch Router CO N SO L E L O O P Upli nk Upli nk...
NK8000 Network planning 5.2.2 Application example with Industrial Ethernet components With Industrial Ethernet from Siemens A&D, it is possible to build up large and power- ful networks. Components that are designed specifically for industry enable problem- free data exchange over long distances.
Page 64
The maximum length for the fibre optic cable is: – 3 km with multimode fibre optic cable – 26 km with single mode fibre optic cable You can find more information about Industrial Ethernet at: http://www.siemens.com/industrial-ethernet Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire Safety & Security Products 06.2007...
5.2.3 Application example with OTN (Open Transport Network) OTN (Open Transport Network) from Siemens Atea is an optical fibre based transmis- sion system for voice, data, LAN, and video information. This system allows intercon- nection of electronic equipment found in complex, basically industrial installations through one single network, irrespective of the distances to be bridged.
NK8000 is only one of the applications that can share the OTN network, together with CCTV-, access control-, and telephony applications (not shown in Fig. 39). You can find more information about OTN at: http://www.ic.siemens.be/icn/otn/eng/about.shtm Shared network It is possible to integrate FS NK8000 and management station products into a cus- tomer’s network, however you need to be aware of / satisfy the following require-...
If the network is down, it is not possible to receive any information via the network; The responsible person for the network is the customer, and not Siemens FS/FIS/SES. The customer should sign a contract that Siemens FS/SES disclaims any liability for the customer’s existing network.
1000BaseLX 2-wire Star 1000 Mbps ST, SC or 5000 Meter @ 9 m fibre 9 various m, 50 or connector 550 Meter @ 62,5 m 50 m 550 Meter @ 62,5 m Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
NK8000 Network planning 5.4.5 FDDI / CDDI Transceiver Media Max. Nodes Topol- Max. Connector Max. Distance Remarks per Segment Speed Type without spe- cial HW FDDI 2-wire 500 DAS Sta- Dual ring 100 Mbps 2 km from fibre 62,5 tions station to sta- m tion...
For more details, please consult the “Details for ordering” section in the product datasheet or contact your local sales distribution centre. Be aware that actual calculations are available through the local sales channels. Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
MM/MK CerPass CC30 (via SiPass) MM/MK ESPA Pager Autronica BSxxx LIST SCU 2000 (field test only) MAXSYS PC601 CP100 CDDL/CDSF units (field test only) MODBUS units (field test only) M5 R-card Siemens Building Technologies DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en Fire & Security Products 06.2007...
If yes, manufacturer and model of subsystem? Do you know if this subsystem is supported by any of our gateways? If no, check with FS-DMS hotline to learn if this protocol is supported. fs.support.sbt@siemens.com Phone: +49 89 9221 8000 Fax:...
Page 74
Appendix B – Checklist Network Point-to-point (serial) connections Are we in control of all the lines? Is the specification of all the cabling available? Are all lines to be used within the specification (distance limits)? Are leased lines / PSTN / ISDN lines to be used? Network connections (a) Management station connectivity How many management stations are foreseen?
Page 75
Appendix B – Checklist (c) Network configuration For each DMS-PC and Ethernet Port we need to know: IP-Address Subnet mask Default Gateway Note: IP addresses must be static (DHCP not supported). Who is the responsible person for the IP-addresses and router configuration? Is a remote access neccessary? If yes, how? (IntERnet IntRAnet, dial-up) Firewall configuration:...
Page 76