ABB CRN-1 Instruction Leaflet
ABB CRN-1 Instruction Leaflet

ABB CRN-1 Instruction Leaflet

Reverse power relay 50 and 60 hz
Hide thumbs Also See for CRN-1:

Advertisement

Quick Links

ABB
ABB
ABB
ABB
Effective: July 1999
Supersedes I.L. 41-251.21B, dated July 1998
(
) Denotes Change Since Previous Issue
R
!
CAUTION
Before putting relays into service, remove all
blocking which may have been inserted for the
purpose of securing the parts during ship-
ment, make sure that all moving parts operate
freely, inspect the contacts to see that they
are clean and close properly, and operate the
relay to check the settings and electrical con-
nections.
1.0 APPLICATION
These relays have been specially designed and
tested to establish their suitability for Class 1E appli-
cations in accordance with the ABB Power T&D
Company program for Class 1E Qualification Testing
as detailed in bulletin STR-1.
"Class 1E" is the safety classification of the electric
equipment and systems in nuclear power generating
stations that are essential to emergency shutdown of
the reactor, containment isolation, cooling of the
reactor, and heat removal from the containment and
reactor, or otherwise are essential in preventing sig-
nificant release of radioactive material to the environ-
ment.
The type CRN-1 relay is a single phase directionally
controlled timing relay used to protect ac generators
from motoring. When such a condition occurs and
persists for a predetermined time interval, the gener-
All possible contingencies which may arise during installation, operation or maintenance, and all
details and variations of this equipment do not purport to be covered by these instructions. If further
information is desired by purchaser regarding this particular installation, operation or maintenance
of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
ABB Automation Inc.
Substation Automation and Protection Division
Coral Springs, FL 33065
Type CRN-1
Reverse Power Relay
50 and 60 Hz
Class 1-E Applications
ator may be tripped or an alarm sounded. The
CRN-1 may also be used to sense lagging power
factor load flow in an abnormal direction. The direc-
tional unit has 30 degree maximum torque character-
istics and the timer unit is adjustable from
approximately 2 to 40 seconds.
2.0 CONSTRUCTION AND OPERATION
The relay consists of a directional unit, a timing unit,
and an indicating contactor switch unit.
These units have been specially designed to meet
the fragility requirements of a seismic environment.
In most cases, the construction is similar to the non-
seismic units except spring restraint is greater and
therefore more power is required to make them oper-
ate.
The timer unit is similar to Type CV relay described in
I.L. 41-201.4.
The CV unit contains a special shield covering the
spring, located above the disc, to prevent the spring
from contacting grounded elements during extreme
vibrations.
The ICS has a single operate rating and requires
special calibration procedures to make it less sensi-
tive to vibration.The internal schematic of the CRN-1
is shown in figure 1, page 7.
2.1
CV TIMER UNIT (T)
A spring shield covers the reset spring of the CV unit.
To remove the spring shield, requires that the damp-
Instruction Leaflet
41-251.21C

Advertisement

Table of Contents
loading

Summary of Contents for ABB CRN-1

  • Page 1 If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
  • Page 2 41-251.21C Type CRN-1 Reverse Power Relay ing magnet be removed first. The screw connection The moving element assembly consists of a spiral holding the lead to the moving contact should be spring, contact carrying member, and an aluminum removed next. The second screw holding the moving...
  • Page 3: Installation

    Reverse Power Relay 3.0 CHARACTERISTICS INDICATING CONTACTOR SWITCH (ICS) There are no settings to make on the indicating con- The type CRN-1 relay is available with either a 120, tactor switch (ICS). 208, or 240 volt rating. 5.0 INSTALLATION TIMER UNIT (T)
  • Page 4: Acceptance Check

    Section 6.1, (“Acceptance Check”) should be Figure 2 (page 8)shows the time curve for the followed. CRN-1 relay. With the time dial set to the indi- cated position, apply the voltages specified and All contacts should be cleaned periodically. A contact measure the operating time of the relay.
  • Page 5 Type CRN-1 41-251.21C Reverse Power Relay every year or at such other time intervals as may be To remove the spring shield, requires that the damp- dictated by experience to be suitable to the particular ing magnet be removed first. The screw connection application.
  • Page 6 41-251.21C Type CRN-1 Reverse Power Relay 6.6.1 Adjustment and Calibration With the moving contact in the normally opened posi- tion, i.e., against the right stop on bridge, screw in the Initially adjust unit on the pedestal so that armature stationary contact until both contacts just close as fingers do not touch the yoke in the reset position indicated by a neon lamp in the contact circuit.
  • Page 7: Energy Requirements

    However, interchangeable parts can be furnished to CRN-1 relay are as follows: the customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data. Sub 2 3528A06 Figure 1: Internal Schematic of the Type CRN-1 Relay...
  • Page 8 41-251.21C Type CRN-1 Reverse Power Relay *Sub 2 184A547 Figure 2: Typical Time curves of the timer unit of the 120 volt type CRN-1 relay. Proportional voltages apply for the 208 and 240 volt relay.
  • Page 9 Type CRN-1 41-251.21C Reverse Power Relay...