Alarms Menu

(Main Menu > Alarms >)
Acknowledge and Configure Alarms by categories.
Acknowledge Alarm
(Main Menu > Alarms > Acknowledge Alarm)
User acknowledgment of alarms can be performed at this menu, only Latched alarms can
be acknowledged. Normal alarms cannot be acknowledged.
When a Latched alarm is set up in the Pen, Alarms menu and a latched relay is configured,
it will maintain its active state until the alarm has been acknowledged.
A latched alarm will continue to flash, if an alarm marker is displayed, until it is acknowl-
edged and it is out of alarm state.
tification.
(Main Menu > Alarms > Configure)
This is a short-cut to change alarm levels, this will display all available Pens with alarms set
up. To change the configuration, select the desired pen, this will display the alarm details.
Select the Edit button to change the alarm level. If the Edit button is greyed-out go to the
Pens > Alarms menu and select the relevant alarm number, then activate Allow Change.
(Main Menu > Alarms > View)
This will display all available Pens with alarms set up. To view the configuration, select the
desired pen, this will display the alarm details.
112
Ack Alarm
• All - Select this button to acknowledge all active latched alarms.
• By Group - Select this button to acknowledge latched alarms in a group of pens. Pen
groups can be set up in the Pens menu
• By Pen - Select this option to acknowledge latched alarms for individual pens.
Configure
View
Power up
See "Alarm Markers" on page 162
for flash colour iden-
43-TV-25-35 GLO Iss.4 Dec 06 UK