Configuration - Free Chlorine/Redox (Pb200, Cle 3, Jesco, Redox) - Pahlen Autodos M1 User Manual

Table of Contents

Advertisement

Autodos M
Autodos M
Electrode-specific configuration - free chlorine/redox (PB200, CLE 3, Jesco, Redox)
For configuration of free chlorine electrodes.
Autodos M3 model - Free chlorine, redox, pH:
For all other models:
This is indicated via the text "SEt FCL" and flashing of the "Off" and "Auto" LEDs.
To exit configuration, press the Cal. button [0] or scroll past the last line.
Autodos M2 and M3
Select the desired line with the ↑ or ↓ button under the relevant display.
While the ↑ or ↓ button is depressed, display 2 shows the selected configuration type (e.g. "FCL" "-01") and display 3 shows
the actual line number.
When the button is released, display 2 shows a text indicating which setting can be changed and display 3 shows a text or a
numeric value.
To change a text or value, press ↑ or ↓ under the relevant display.
The selected configuration is indicated via one of the following texts: "SEt", "FCL", "CCL", "ACi" or "bAS".
Autodos M1
Select the line for which you want to change the setting by pressing the Alarm high [12] or Alarm low [14] button.
When the Alarm high [12] or Alarm low [14] button is held depressed, the display shows the actual line number.
When the button is released, the display shows either a text or a numeric value. To change a text or value, press ↓ or ↑ .
The selected configuration is indicated via one of the following texts:: "SEt", "FCL", "ACi" or "bAS" depending on type.
The following can be modified in the channel-specific configuration – Free chlorine:
Line
Text
Setting
-01
doS
oFF
ono*
Pdo
FrE
Cur
-02
P
0.10–2.00 (0,20*)
-03
I
000–100
-04
d
000–100
-05
dF
010–180
-06
Pdo
005–015
-07
Ldt
000–060
-08
oFt
000–600
-09
ont
000-600
-10
Cur
- - 0 / - - 4
-11
C-L
0.00–9.99
-12
C-H
0.00–9.99
-13
AHd
005–600
-14
ALd
005–600
* Factory default!
press the buttons Set alk/Cl [13] + Select function [1].
press the buttons Set value [13] + Select function.
ppm
(000*)
minutes
(000*)
seconds
(100*)
strokes/minute
(010*)
minutes
(000*)
minutes
seconds
seconds
(- - 4*)
(0.00*) ppm
(5.00*) ppm
(005*)
seconds
(005*)
seconds
Explanation
Selection of dosing outlet and function.
No dosing.
On-/Off-dosing.
Pulse width dosing..
Frequency dosing..
Dosing via current output..
P-band. (Pdo, FrE, Cur)
I-time, 000 = no I-regulation. (Pdo, FrE, Cur)
D-tid, 000 = no D-regulation. (Pdo, FrE, Cur)
Max. frequency dosing. (FrE)
Pulse width during pulse width dosing. (Pdo)
Long dosing time alarm, 0 = no function.
Min. time OFF for relay, 0 = no function. (ono)
Min. time ON for relay, 0 = no function. (ono)
Current output, selection of range 0–20mA / 4–20mA.
Current output, value for 0/4mA.
Current output, value for 20mA.
Delay time for high alarm.
Delay time for low alarm.
27
ENGLISH