5.2 Soak mode(PAF : B=1)
Suitable for the process which does not need to establish the temperature slope, can simplify the
programming and more effective. Each step also can set parameter "SPr" to define temperature
raise slope, if "SPr=0" raising speed will set to maximum. Because cannot know the actual time
which spend on temperature raising, user can enable "rdy"function to ensure the correct soak
time.
Time setting
Set "t-xx" = 0.1~3200 (min)
Set the time of xx StEP. (Time units can be change to Hour by parameter "PAF".)
Set "t-xx" = 0.0
The program hold on StEP xx, program will hold running and hold counting time.
Set "t-xx" = -121.0
The program stops, and switches to stop status.
Set "t-xx" = -0.1~-122.0
Negative value of this range represents a jump operation which will jump to step xx and event
output. Range -1~-120 is for step jumping application. The step jumping cannot greater than"Pno"
(No. of Program step).
Decimal point use for control the event output from AL1 and AL2. (Modular), Note, if parameter
AOP was assigned alarm action will trigger from AL1 and AL2, the event output also will cause
alarm from AL1 and AL2.
When set
-XXX.1, AL1 activate, AL2 release
-XXX.2, AL1 release, AL2 activate
-XXX.3, AL1 and AL2 activate
-XXX.4, AL1 and AL2 release
Example:
Example 1 : t -5 = -1.1 ; means when the program arrived step 5, AL1 activate, AL2 release
and will jump to step 1 continues running
Example 2 : t-6 = -0.3 ; means when the program arrived step 6, AL1 and AL2 activate and
continuous next step.
32